If you have not directly worked on an appliance regulation 34 states…
If you know or have reason to believe that the appliance may be a risk to people you should inform the responsible person or, failing that, the transporter
If you have worked on an appliance regulation 26 states that you should check 4 things – what are they?
1) Effectiveness of the flue
2) Supply of combustion air
3) Operating pressure and/or heat input
4) Its operation – functioning safely
Prior to a tightness test the cooker lid should be…
Opened
Prior to purging an installation do you need to do a tightness test?
Yes
From a safety perspective why would you purge an installation?
Remove the possibilities of explosive mixtures
If you have a U6 meter and the pipework is <= 28mm what is the purge volume
0.01m3
How do you calculate the purge volume for a G4 meter with pipe work greater than 28mm?
Meter volume x5 (0.01m3) + IV of pipework & fittings x 1.5
What is IV?
Installation volume = Pv + (Pv x 0.1) for fittings
If the IV <0.02m3 do you purge to:
a) air
b) flame
c) either
a) air
If the IV >0.02m3 do you purge to:
a) air
b) flame
c) either
b) flame