Module 2 Flashcards
Review past questions
Use a method that can be used to estimate the capacity of an air conditioning unit.
Divide the compressor RLA (rated load average) by 2 for a very old unit or 4 for a 10 SEER unit or better (typically since 1995).
Divide the compressor RLA (rated load average) by 3 for a very old unit or 6 for a 10 SEER unit or better (typically since 1995).
Divide the compressor RLA (rated load average) by 5 for a very old unit or 4 for a 10 SEER unit or better (typically since 1995).
Divide the compressor RLA (rated load average) by 7 for a very old unit or 6 for a 10 SEER unit or better (typically since 1995).
Divide the compressor RLA (rated load average) by 8 for a very old unit or 4 for a 10 SEER unit or better (typically since 1995).
Divide the compressor RLA (rated load average) by 7 for a very old unit or 6 for a 10 SEER unit or better (typically since 1995).
The following statement(s) is/are true about SEER (Seasonal Energy Efficiency Ratio):
8 or 10 SEER is the current minimum efficiency manufactured.
13 or 14 SEER is the current minimum efficiency manufactured.
Units before 1995 may be only 4 or 5 SEER.
Units with a higher SEER are approximately the same physical size as units with a lower SEER (but this is starting to change).
The previous standard for SEER was 5.
13 or 14 SEER is the current minimum efficiency manufactured.
When inspecting an air conditioning unit, which of the following is considered a major problem?
The outside unit has 12 inches of clearance on each side.
Foliage is present around the unit but is trimmed back 6 inches all around.
The outside unit has 5 feet of clearance from the home.
Refrigerant lines are frozen.
The insulation on the suction line is old, deteriorated and damaged.
Refrigerant lines are frozen.
The following ASHI standard of practice requires home inspectors to tell the client:
The age of the unit.
The capacity of the unit.
When the equipment is beyond its normal lifespan.
The serial number, model number, and maximum amperages.
The age, capacity, and model number.
When the equipment is beyond its normal lifespan.
When inspecting an AC unit installed in an attic, what is the foolproof way to ensure leaking is detected and doesn’t spill over onto the floor or ceiling?
You should see a proper drip pan.
You should see a drip pan and a drain on the pan that flows out the side of the house.
You should see a drain that carries the water to the basement.
You should see a drip pan and an emergency float switch.
A float pan is not necessary because in warm weather, the hot air in the attic causes quick and efficient evaporation of the water.
You should see a drip pan and an emergency float switch.
When measuring the supply temperature in an AC unit, what is the appropriate range you are looking for?
The perfect range is 5-10 degrees.
The perfect range is 10-12 degrees.
The perfect range is 15-20 degrees.
The perfect range is 15-22 degrees.
The perfect range is 15-30 degrees.
The perfect range is 15-22 degrees.
When providing a report to your client on maintaining their air conditioning equipment, direct them to:
contact a qualified heating contractor for more information on maintenance best practice.
have their A/C equipment maintained two times per year by a qualified heating contractor.
have their A/C equipment maintained every year by a qualified heating contractor.
have their A/C equipment maintained every other year by a qualified heating contractor.
have their A/C equipment maintained every five years by a qualified heating contractor; if the system is over ten years old it should be maintained every other year.
have their AC equipment maintained every year by a qualified heating contractor.
A single-wall vent connector at the furnace needs at least:
Six inches of clearance from combustibles.
Eight inches of clearance from combustibles.
Ten inches of clearance from combustibles.
Twelve inches of clearance from combustibles.
Eighteen inches of clearance from combustibles.
6 inches of clearance from combustibles.
Which of the following is NOT an appropriate action when a line-set is frozen in an AC unit you are inspecting?
It is appropriate to tell any real estate agents that you are involved with the sale of the home.
If they are not at home, leave a note.
Turn the unit off until the line is thawed and resume use.
If they are not at home, leave a note.
Ask the client for permission to talk to the current owner about this.
Turn the unit off until the line is thawed and resume use.
Most mini-split ductless systems will not operate if the interior temperature is below:
75 degrees
70 degrees
65 degrees
60 degrees
A mini-split ductless system will operate at any interior temperature.
70 degrees
A typical ductless split system bottom discharge unit should be a mininum _ above the floor measuring to the underside of the air handler.
6 feet
5 feet
4 feet
3 feet
2 feet
6 feet
Which of the following is true of high velocity (Hi-V) AC systems?
Hi-V systems are less flexible than systems with conventional large ductwork.
Hi-V systems provide less efficient moisture removal than conventional systems.
Hi-V systems are less energy-efficient than conventional systems.
Hi-V systems have similar operating characteristics to convention systems.
Hi-V systems provide better moisture removal than conventional systems.
Hi-V systems provide better moisture removal than conventional systems.
A hi-V system removes _ more humidity than a conventional central air conditioning system.
10%
15%
20%
25%
30%
30%
What is the first thing to consider when inspecting an air source heat pump?
Make sure that it sounds OK when it is operating.
The location and condition of the exterior unit and the line set and data from the exterior nameplate.
The condition of the interior air handler and line set.
The condensate drain.
The filter and blower compartment.
The location and condition of the exterior unit and the line set and data from the exterior nameplate.
When checking the emergency heat after checking the heat pump, you will adjust the thermostat by _ to get the heat pump to start in heating mode, and then, once you are done checking the heat pump, adjust the temperature up another _ to get it to kick into emergency heat system.
1 or 2 degrees, 2 or 3 degrees
2 or 3 degrees, 2 or 3 degrees
3 or 4 degrees, 3 or 4 degrees
4 degrees, 2 or 3 degrees
5 degrees, 2 or 3 degrees
2 or 3 degrees, 2 or 3 degrees.
What temperature should you test a heat pump in cooling mode?
50 degrees
55 degrees
65 degrees
70 degrees
A heat pump should be tested in cooling mode only if the outside temperature is at or above 60 degrees.
A heat pump should be tested in cooling mode only if the outside temperature is at or above 60 degrees.
What is the appropriate temperature drop for a heat pump in heating mode?
For cold air, it is 10 to 15 degrees.
For cold air, it is 10 to 20 degrees.
For cold air, it is 15 to 20 degrees.
For cold air, it is15 to 25 degrees.
For cold air, it is 15 to 30 degrees.
For cold air, it is 15 to 30 degrees.
Which of the following is/are NOT true of geothermal heat pumps?
They are associated with high installation costs.
The technology is cumbersome.
They were first installed in 1935.
They were low energy costs at the time.
They are also knowns as GeoExchange, earth-coupled, ground-source, or water-source heat pumps.
They were first installed in 1935.
According to the industry, the ground loops should last well over _ and they expect the high-density polyethylene ground loop tubing to last well in excess of _.
25 years, 50 years
30 years, 60 years
40 years, 80 years
50 years, 100 years
Both are expected to last up to 100 years.
50 years, 100 years
What is the approximate expected life span for an air source heat pump?
10-15 years
12-14 years
11-16 years
12-17 years
13-18 years
12-14 years
Using Ohm’s Law, which of the following scenarios is NOT an acceptable circuit load for a single outlet that is 15-amp, 120-volt circuit?
A client can run a 2-slice toaster (rated 800 watts) and a hand mixer (rated at 250 watts) on the same outlet.
A client cannot run a coffeemaker (rated 900 watts) and a microwave (rated 1200 watts) on the same outlet.
A client can run a coffeemaker (rated 900 watts) and a microwave (rated 1200 watts) on the same outlet.
A client can run an electric oven (rated 1000 watts) and a microwave (rated 800 watts) on the same outlet.
All of these scenarios require a combined wattage that exceeds Ohm’s law for a 15-amp, 120-volt circuit.
A client can run a coffeemaker (rated 900 watts) and a microwave (rated 1200 watts) on the same outlet.
According to the Standard of Practice, what is the representative number of installed lighting fixtures, switches, and receptacles you are required to inspect?
At least one per room for multiple similar interior components.
At least two per room for multiple similar interior components
At least two per room for multiple similar interior components and at one exterior on each side of the building for multiple similar exterior components
At least one per room for multiple similar interior components and at least two exterior on each side of the building for multiple similar exterior components
You are only required to inspect one per room for multiple similar interior components and all exterior on each side of the building for multiple similar exterior components.
At least one per room for multiple similar interior components.
Which of the following service drop clearances does NOT meet inspection requirements?
Over roofs with 4:12 slope or greater: 3 feet minimum clearance
Over roofs with less than 4:12 slope: 8 feet minimum
Over swimming pools: 22 and ½ feet minimum clearance
Over swimming pools: 20 1/2 feet minimum clearance
From tress, antennas, chimneys, etc., use common sense
Over swimming pools: 20 1/2 feet minimum clearance
Should be 22.5
For attic installation, NM cable should be properly secured every _.
4 feet
4 ½ feet
5 feet
5 ½ feet
6 feet
4 1/2 feet