P75 - Div 1/2 Diesels Flashcards

(46 cards)

1
Q

What’s the maximum load for the diesel unless necessary for safe plant conditions?

A

5740 kw

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What’s the maximum load for break-in following a ring replacement?

A

7000 kw

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What’s the starting air pressure lowering logic?

A

220 - psig motor driven compressor starts
200 psig - low starting air alarm
160 psig - tech spec limit
120 psig - auto start not available alarm
50 psig - low control air pressure alarm
40 psig - diesel trip

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What is the power supply for the jacket water heater and pump? (ESF or BOP)

A

BOP

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

what is the purpose of the jacket water heater and pump?

A

maintain jacket water approximately 160 deg F when diesel in standby

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Where should the crane be stored in the diesel room?

What should happen if it’s not stored there and why?

A

West

INOP the diesel due to seismic concerns

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What should the CRO do if a fire is detected in the Diesel room?

A

stop the fans in the room with the fire, and

start the fans in all rooms not affected

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What temp does the outside air fan maintain the room at?

A

<120 degrees F

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What trips are in for a DIV 1 or 2 Local/Emergency start?

A

Overspeed
All electrical

“OverAlls”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

How many starting air trains are there for the diesels and how many times can each train start the diesel?

A

2 trains, 5 times each from 160 psig

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What trips are in for a LOP/BUV?

A

Differential
Overcurrent with voltage restraint
Generator ground overcurrent
All mechanical

“DOG-All”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What trips are in for a LOCA?

A

Generator differential and overspeed

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

***Where is the generator differential sensed from?

A

At the generator, (Breaker must be closed to detect it)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

How long after the diesel trip can it be restored?

Can this be overridden?

A

2 minutes

can be overridden with an emergency start or ECCS initiation

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

What pump is the primary supplier for fuel to the diesel engine?

A

Engine driven fuel oil pump

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

what is the power supply of the lube oil oil heater pump? (ESF or BOP)

A

BOP

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
17
Q

What is the purpose of the lube oil heater pump?

A

Prelubes essential diesel parts and maintains lube oil approximately 170 deg F while in standby

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
18
Q

How long do starting solenoids stay energized?

A

Until engine speed >200 rpm

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
19
Q

When is flash field energized?

20
Q

What is the power supply for the flash field?

21
Q

What is the tech spec limit for the fuel oil day tank?

A

220 gallons for 30 minutes @ max load post-LOCA

22
Q

What is the purpose of the fuel oil drip return pump?

A

Pumps excess fuel in the drip tank back to the day tank

23
Q

What is the power supply to the fuel oil drip return pump? (ESF or BOP)

24
Q

What happens if the fuel oil drip return pump fails?

A

Fuel oil is routed to the diesel oily waste sump

25
How long can the diesel run without adding additional water to the jacket water standpipe?
30 days
26
What must you perform after diesel output breaker is racked out and back in?
Run diesel with breaker closed synced to the grid
27
How does diesel start for LOCA?
attempts to start continuously until 120 psig
28
How does diesel start for BUV signal?
5 seconds, regardless of air pressure. Then it must be reset
29
What is the power supply to the fuel oil transfer pumps? (ESF or BOP)
ESF
30
What are the generator electrical trips?
"RULOGG" ``` Reverse power Underfrequency Loss of excitation Overcurrent with ground restraint Ground overcurrent Generator differential ```
31
What are the diesel mechanical trips?
Low lube oil pressure -----------------------30 psig Low turbo oil pressure ----------------------15 psig Low control air pressure -------------------40 psig High lube oil temp ----------------------------200 deg F High bearing temp ---------------------------228 deg F High jacket water temp --------------------200 deg F High crankcase pressure ------------------3 psig High engine vibration ------------------------12 mils Engine overspeed -----------------------------517.5 rpm
32
What level does fuel oil transfer pump start and stop?
34" - 41"
33
Auto start and stops of motor driven air compressor for Div 1 and 2 diesels?
On - 220 psig | Off - 245 psig
34
What is the power supply to the motor driven air compressors for div 1 and 2 diesels? (ESF or BOP)
BOP
35
What are the above the line requirements?
Stored diesel fuel oil, lube oil, and air shall be within required limits
36
What's the tech spec numbers?
3.8.3
37
Can each diesel have separate LCO logs for the concerns?
Yes
38
What is the tech spec limit for diesel fuel oil level?
9.6 feet or 68,744 gallons
39
How long can diesel run at the tech spec imit?
7 days
40
What is the power supply to the motor driven fuel oil | booster pump? (AC or DC)
DC
41
When does the motor driven fuel oil pump auto start?
When HS in Auto, Pump starts on a 1.5 second time delay when: the Engine driven fuel oil pump discharge pressure decreases to 10 psig, AND engine control air pressure is >45 psig.
42
What is the tech spec level for the jacket water standpipe?
146"
43
When will the motor driven jacket water pump auto start? stop?
Engine speed > 425 rpm and pressure < 15 psig stops > 70 psig
44
What is the power supply to the motor driven Lube Oil pump (AC or DC)
DC
45
When will the motor driven lube oil pump auto start?
Engine > 425 rpm and pressure < 30 psig (after 5 second time delay)
46
When will the motor driven lube oil pump trip?
Pressure > 110 psig