PEC 1.3-1.10 Flashcards
(32 cards)
What is the title of 1.3?
ELECTRICAL PLANS AND
SPECIFICATIONS
For a dwelling unit having a floor area of not more than 50 square meters with a total load not exceeding 3680 VA, a drawing sheet of size is?
A drawing sheet of size 297 mm x 420 mm (A3 size) is permitted.
Title of 1.3.1.1 is?
Drawing Sheet sizes
Title of 1.3.2
Plans and Specifications
What are the Plan requirements?
(name all 7)
Location and Site Plans
Legend or Symbols
General Notes and/or Specifications
Electrical Layout
Schedule of Loads
Design Analysis
One Line Diagram
Title of 1.3.2.2 is?
Title Block
1.3.3 is?
Substation Plans and Specifications
1.3.3.2
Outdoor substation
1.10
Requirements for Electrical Installations
Voltages
The voltage rating shall not be less than the nominal voltage of a circuit to which it is connected
Conudctors
Copper or Aluminum.
If not specified, sizes apply to copper
conductors
Conductor sizes expressed in?
Metric System (SI)
Wiring Integrity
Shall be free from short circuits and from grounds.
Interrupting rating is?
equipment intended to interrupt current at fault levels shall have Interrupting rating sufficient for the nominal circuit voltage and at least equal to the current available.
Deteriorating Agents
No conductors or equipment shall be located in damp or wet locations. or excessive temp. or gases, fumes, vapors.
Electrical connections
Dissimilar metals shall not be intermixed
Terminals
connection by nuts that have upturned lugs or the equivalent shall be permitted for 5.5 mm^2 (2.6 mm dia.)
Arcing Parts
Parts that produce arcs, sparks, flames or molten metals shall be enclosed/separated from all combustible materials
1.10.2 is?
1000 Volts, Nominal or Less
Spaces about electrical Equipment
Sufficient access and working space
Low Voltage
All exposed live parts operate at not greater than 30 volts rms, 42 volts peak or 60 volts DC.
1000v or less. An equipment installed above lay-in ceiling shall not smaller than?
559mm x559mm. If crawl Spaces, 559 mm x 762mm
Minimum Width of the working space is?
762mm
Personnel doors
Rated in 800A . Working space less than 7600mm from the nearest edge of the working space.