PEC 1.3-1.10 Flashcards

(32 cards)

1
Q

What is the title of 1.3?

A

ELECTRICAL PLANS AND
SPECIFICATIONS

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

For a dwelling unit having a floor area of not more than 50 square meters with a total load not exceeding 3680 VA, a drawing sheet of size is?

A

A drawing sheet of size 297 mm x 420 mm (A3 size) is permitted.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Title of 1.3.1.1 is?

A

Drawing Sheet sizes

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Title of 1.3.2

A

Plans and Specifications

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What are the Plan requirements?
(name all 7)

A

Location and Site Plans
Legend or Symbols
General Notes and/or Specifications
Electrical Layout
Schedule of Loads
Design Analysis
One Line Diagram

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Title of 1.3.2.2 is?

A

Title Block

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

1.3.3 is?

A

Substation Plans and Specifications

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

1.3.3.2

A

Outdoor substation

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

1.10

A

Requirements for Electrical Installations

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Voltages

A

The voltage rating shall not be less than the nominal voltage of a circuit to which it is connected

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Conudctors

A

Copper or Aluminum.
If not specified, sizes apply to copper
conductors

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Conductor sizes expressed in?

A

Metric System (SI)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Wiring Integrity

A

Shall be free from short circuits and from grounds.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Interrupting rating is?

A

equipment intended to interrupt current at fault levels shall have Interrupting rating sufficient for the nominal circuit voltage and at least equal to the current available.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

Deteriorating Agents

A

No conductors or equipment shall be located in damp or wet locations. or excessive temp. or gases, fumes, vapors.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

Electrical connections

A

Dissimilar metals shall not be intermixed

17
Q

Terminals

A

connection by nuts that have upturned lugs or the equivalent shall be permitted for 5.5 mm^2 (2.6 mm dia.)

18
Q

Arcing Parts

A

Parts that produce arcs, sparks, flames or molten metals shall be enclosed/separated from all combustible materials

19
Q

1.10.2 is?

A

1000 Volts, Nominal or Less

20
Q

Spaces about electrical Equipment

A

Sufficient access and working space

21
Q

Low Voltage

A

All exposed live parts operate at not greater than 30 volts rms, 42 volts peak or 60 volts DC.

22
Q

1000v or less. An equipment installed above lay-in ceiling shall not smaller than?

A

559mm x559mm. If crawl Spaces, 559 mm x 762mm

23
Q

Minimum Width of the working space is?

24
Q

Personnel doors

A

Rated in 800A . Working space less than 7600mm from the nearest edge of the working space.

25
1.10.3 is?
Over 1000 Volts, Nominal
26
Enclosure for Electrical Installation requirement is
A fence shall not be less than 2100 mm in height or a combination of 1800mm or more of fence fabric and a 300 mm or more extension utilizing three or more strands of barbed wire or equivalent.
27
Illumination
Illumination. Illumination shall be provided for all working spaces about electrical equipment
28
1.10.4 is?
Tunnel Installations over 1000Volts, Nominal
29
Grounded and bonded intervals is?
300 m throughout the tunnel.
30
1.10.5
Manholes and Other Electric Enclosures Intended for Personnel Entry
31
Dimensions for manholes is?
Dimensions. Rectangular access openings shall not be less than 650 mm x 550 mm. Round access openings in a manhole shall not be less than 650 mm in diameter.
32
Cabling Workspace