Plumbing Flashcards
(65 cards)
Building sewers shall be tested by completely filling the sewer with water from the
A. Lowest to the highest point
B. Lowest to at least five-foot head
C. Lowest to at least ten-foot head
D. Lowest to at least ground level
C
Hot and cold-water piping may be tested with
A. 40 psi or 150 psi water for ten minutes
B. 35 psi for at least 15 minutes
C. 50 psi or line working pressure of the water in the system for at least 15 minutes
D. 100 psi of air for at least len minutes
C
The required clearance in iront of a three-inch cleanout is
A. 12 inches
B. 18 inches
C. 24 inches
D. 36 inches
B
A stack as defined in the code is
A. The main vent
B. Any vertical vent
C. The vertical main of a soil, waste or vent piping which extends one or more stories
D. The horizontal main of a soil, waste or vent stack
C
- Above ground PEX piping installed horizontally shall be supported at intervals not to exceed
A. Depends on the pipe size
B. 24 inches
C. 32 inches
D. 36 inches
C
The minimum true vertical length for a gravity type venting system serving a fuel fired water heater is
A. 4 feat
B. 5 feet
C. 10 feet
D. Based on the Btu rating
B
The maximum horizontal distance of a trap arm is measured from the inner edge of the vent to the
A. Weir of the trap
B. Dip of the trap
C. Inlet of the trap
D. None of the above
A
Sleeves shall be provided to protect piping
A. Passing through floors or concrete walls
B. Passing through concrete and masonry walls
C. Passing through wood or concrete walls
D. Passing through all locations listed above
B
The drain connecting the compartments of a set of fixtures to its trap is called a
A. Continuous waste
B. Combination waste and vent
C. Indirect waste
D. None of the above
A
A device to prevent backflow into the potable water system is called a
A. Backflow connection
B. Backflow preventer
C. Backwater preventer
D. Both A and B
B
Copper tube and fittings used for drainage and vent piping installed above ground shall be at least
A. Type L
B. Type M
C. Type K
D. Type DWV
D
All trenches deeper than the footing of any building or structure and paralleling the same must be at least
A. 45 degrees therefrom
B. 4 feet therefrom
C. 2 feet deeper
D. 90 degrees therefrom
A
The minimum size trap and trap arm for a kitchen sink is
A. 1½ inches
B. 2 inches
C. 1-1/4 inches
D. Ether A or B
A
Horizontal drainage lines connecting with other horizontal drainage lines shall enter through
A. 45-degree wye branches
B. Sanitary tee branches
C. 1/4 bend with end outlet
D. Side inlet sweep
A
For each run of horizontal drain piping, the distance between cleanouts shall not exceed
A. 50 feet
B. 75 feel
C. 100 feet
D. None of the above
C
A plumbing vent shall terminate not less than
A. 3 feet from an air intake
B.10 feet from an air Intake
C. 1 foot above the roof
D. 3 feet above a parapet wall
B
Each drainage stack which extends 5 or more stories above the building drain shall be served by
A. Cleanouts
B. A parallel vent stack
C. A parallel stack vent
D. Straps every 10 feet
B
Chemical or industrial liquid wastes which are likely to damage the public sanitary sewer system shall
A. Be drained into a holding tank
B. Not be used under any condition
C. Pretreated to render them innocuous
D. Be drained into a storm drain
C
Special venting for island fixtures is used for
A. Bathiubs
B. Showers
C. Kitchen sinks
D. Washing machines
C
The vertical distance between a fixture outlet and the trap weir shall not exceed.
A. 12 inches
B. 18 inches
C. 24 inches
D. 30 inches
C
Fixture traps shall have a water seal of not less than
A. 2 inches
B. 4 inches
C. 1 inch
D. 1-1/2 inches
A
Concealed slip joint connections require a
A. 10 X 12 access panel
B. 12 X 12 access panel
C. 18 X 18 inches
D. None of the above
B
The distance from the center of a water closet to a sidewall shall not be closer than
A. 15 inches
B. 16 inches
C. 18 inches
D. 20 inches
A
The depth of the finished dam or threshold for any shower, measured from the top of the drain, shall not be less than
A. 2 inches
B. 3 inches
C. 4 inches
D. Either A or C
A