Plumbing 1st Importance Flashcards
(84 cards)
1” copper tubing installed horizontally shall be supported every___________
feet.
6 feet
Suspended piping shall be supported at intervals not to exceed those shown in Table 313.3.
Direct connections between potable water piping and sewer connected wastes shall not exist under any condition with or without________protection.
Backflow
Direct connections between potable water piping and sewer-connected wastes shall not be permitted to exist under any condition with or withol backflow protection. Where potable water is discharged to the drainage system, it shall be by means of an approved air gap of two pipe diamete of the supply inlet, but in no case shall the gap be less than 1 inch (25. mm). Connection shall be permitted to be made to the inlet side of a tra provided that an approved vacuum breaker is installed not less than 6 inches (152 mm), or the distance according to the device’s listing, abov the flood-level rim of such trapped fixture, so that at no time will such device be subjected to backpressure.
Underground piping systems shall be installed within a minimum of________inches of cover.
12 inches
Underground piping systems shall be installed with a minimum of 12 inches (305 mm) of cover. The minimum cover shall be increased to 18 inches (457 mm) if external damage to the pipe or tubing from external forces is likely to result. Where a minimum of12 inches (305 mm) of cover cannot be provided, the pipe shall be installed in conduit or bridged (shielded). [NFPA 54:7.1.2.1 (A) (B)] (NFPA 54: National Fuel Gas Code)
No urinal shall be set closer than________ inches center to center.
24 inches
Fixtures shall be set level and in proper alignment with reference to adjacent walls. No water closet or bidet shall be set closer than 15 inches (381 mm) from its center to a side wall or obstruction nor closer than 30 inches (762 mm) center to center, to a similar fixture.
The clear space in front of a water closet or bidet shall be not less than 24 inches (610 mm). No urinal shall be set closer than 12 inches (305 mm) from its center to a side wall or partition nor closer than 24 inches (610 mm) center to center.
Indirect waste piping must discharge into the building drainage system through an:
An air gap or air break
Indirect waste piping shall discharge into the building drainage system through an air gap or air break as set forth in this code.
Where a drainage air gap is required by this code, the minimum vertical distance as measured from the lowest point of the indirect waste pipe or the fixture outlet to the flood-level rim of the receptor shall be not less than 1 inch (25.4 mm).
Water Closet and Urinal Flushometer Valve shall be equipped with a listed__________
Atmospheric vacuum breaker (AVB)
Water closet and urinal flushometer valves shall be protected against backflow by an approved backflow prevention assembly, device, or method. Where the valves are equipped with an atmospheric vacuum breaker, the vacuum breaker shall be installed on the discharge side of the flushometer valve with the critical level not less than 6 inches(152 mm), or the distance according to its listing, above the overflow rim of a water closet bowl or the highest part of a urinal.
What is the maximum fixture unit loading allowed on a 2” waste stack?
16 units
Table 703.2 shows the maximum number of fixture units allowed on a vertical or horizontal drainage pipe, building drain, or building sewer of a given size; the maximum number of fixture units allowed on a branch interval of a given size; and the maximum length (in feet and meters) of a vertical drainage pipe of a given size.
The maximum distance between manholes shall not exceed______________feet.
300 feet
Approved manholes shall be permitted to be installed in lieu of cleanouts, where first approved by the Authority Having Jurisdiction.
The maximum distance between manholes shall not exceed 300feet (91 440 mm). The inlet and outlet connections shall be made by the use of a flexible compression joint not less than 12 inches (305 mm) and not exceeding 3 feet (914 mm) from the manhole.No flexible compression joints shall be embedded in the manhole base.
Plastic and copper piping run through framing members to within__________inch of the exposed
framing shall be protected by steel nail plates not less than 18 gauge.
1 inch
Plastic and copper or copper alloy piping penetrating framing members to within 1 inch (25.4 mm) of the exposed framing shall be protected by steel nail plates not less than No. 18 gauge(0.0478 inches) (1.2 mm) in thickness. The steel nail plate shall extend along the framing member no less than 1-1/2 inches(38 mm) beyond the outside diameter of the pipe or tubing.
What is the minimum separation when sewer piping materials are used with water pipe?
12 inches
(1) The bottom of the water pipe, shall be not less than 12 inches(305 mm) above the top of the sewer or drain line.
All water service yard piping shall be at least_________inches below the average local frost
12 inches
Piping, equipment, appurtenances, and devices shall be installed in a workmanlike manner in accordance with the provisions and intent of the code. Building supply yard piping shall be not less than 12inches (305 mm) below the average local frost depth. The cover shall be not less than 12 inches (305 mm) below finish grade.
Unions shall be installed in the water supply piping within____________inches of equipment
which may require service by removal or replacement.
12 inches
Unions shall be installed in the water supply piping not more than 12 inches (305 mm) of regulating equipment, water heating, conditioning tanks, and similar equipment that requires service by removal or replacement in a manner that will facilitate its ready removal.
Termination of each vent must be a minimum of
__________________in any direction from a lot line,
alley and street excepted.
3 feet
Each vent shall terminate not less than 10 feet (3048 mm) from, or not less than 3 feet (914 mm) above, an openable window, door, opening, air intake or vent shaft, or not less than 3 feet (914 mm) in every direction from a lot line, alley and street excepted.
No more than_____________of the total permitted
length of any minimum sized vent shall be installed in a horizontal position.
1/3
Not more than one-third of the total permitted length, in accordance with Table 703.2, of a minimum-sized vent shall be installed in a horizontal position.
Exception: Where a minimum-sized vent is increased one pipe size for its entire length, the maximum length limitation shall not apply.
No trap for any clothes washer standpipe receptor shall be installed below the floor, but shall be roughed in not more than_____________ inches above the floor.
18 inches
Plumbing fixtures or other receptors receiving the discharge of indirect waste pipes shall be approved for the use proposed and shall be of such shape and capacity as to prevent splashing or flooding and shall be located where they are readily accessible for inspection and cleaning. No standpipe receptor for a clothes washer shall extend more than 30 inches (762 mm), or not less than 18 inches (457 mm) above its trap. No trap for a clothes washer standpipe receptor shall be installed below the floor, but shall be roughed in not less than 6 inches (152 mm) and not more than 18 inches (457 mm) above the floor.
No trap for any clothes washer standpipe receptor shall be installed below the floor, but shall be roughed in not less than__________inches above the floor.
6 inches
Plumbing fixtures or other receptors receiving the discharge of indirect waste pipes shall be approved for the use proposed and shall be of such shape and capacity as to prevent splashing or flooding and shall be located where they are readily accessible for inspection and cleaning. No standpipe receptor for a clothes washer shall extend more than 30 inches (762 mm), or not less than 18 inches (457 mm) above its trap. No trap for a clothes washer standpipe receptor shall be installed below the floor, but shall be roughed in not less than 6 inches (152 mm) and not more than 18 inches (457 mm) above the floor.
Water closets shall have an average consumption of not more than___________gallons of water per flush.
1.6 gallons
Water closets, shall have a maximum consumption not to exceed1.6 gallons (6.0 Lpf) of water per flush.
Each vent pipe or stack shall extend through its flashing and shall terminate vertically not less than_________________foot from any vertical
surface.
1 foot
Each vent pipe or stack shall extend through its flashing and shall terminate vertically not less than 6 inches (152 mm) above the roof nor less than 1 foot (305 mm) from a vertical surface. ABSand PVC piping exposed to sunlight shall be protected by waterbased synthetic latex paints.
Water heaters in garages shall be located or protected so it is not subject to__________by a moving vehicle.
Physical damage
Appliances installed in garages, warehouses, or other areas subject to mechanical damage shall be guarded against such damage by being installed behind protective barriers or by being elevated or located out of the normal path of vehicles.
An appliance for supplying hot water for domestic or commercial purposes.
Water Heater
An appliance designed primarily to supply hot water for domestic or commercial purposes and equipped with automatic controls limiting water temperature to a maximum of 210°F (99°C).
This code refers to water that meets the requirements of the Authority Having Jurisdiction to be satisfactory for culinary, domestic, and drinking purposes as:
Potable water
Water that is satisfactory for drinking, culinary, and domestic purposes and that meets the requirements of the Health Authority Having Jurisdiction.
Urinals shall have an average water consumption of not more than___________gallons of water per flush.
1.0 gallon
Urinals shall comply with ASME A112.19.2/CSA B45.1, ASMEA112.19.19, or CSA B45.5/IAPMO Z124. Urinals shall have an average water consumption not to exceed 1 gallon (3.8 Lpf) of water per flush.
To protect against rodents, strainer plates on drain inlets must be designed and installed so that no opening is greater than__________in the
least dimension.
1/2”
Strainer plates on drain inlets must be designed and installed so that no opening exceeds 1/2 of an inch (12.7 mm) in the least dimension.
Hose connections in health care or laboratory areas shall not be less than__________feet above the floor.
6 feet
Vacuum breakers for washer-hose bedpans shall be located not less than 5 feet (1524 mm) above the floor. Hose connections in health care or laboratory areas shall be not less than 6 feet(1829 mm) above the floor.