Practice Quiz: Commissioning DFMAs Flashcards

(10 cards)

1
Q

Before commissioning a DFMA, what key documentation and approvals must be in place?

A

Proper permits, product approval, and a signed-off engineering design.

These documents ensure compliance and safety in the commissioning process.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

If a make-up air unit uses a forward curved fan and the external static pressure is overestimated, what can be the result?

A

Too much airflow and over current the fan motor.

Overestimating static pressure can lead to improper airflow and potential damage to the system.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What are two options available to correct issues with airflow if the unit is supplying too much air?

A
  • Making adjustments with sheaves and belts
  • Using a variable frequency drive (VFD)

These methods allow for better control of airflow without extensive modifications.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What is the primary advantage of using a Variable Frequency Drive (VFD) for airflow adjustment during Testing, Adjusting, and Balancing (TAB)?

A

It allows for quick and accurate TAB by enabling speed adjustments without ordering and installing new belts and sheaves.

VFDs enhance efficiency and flexibility in managing airflow.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

For kitchens that communicate directly with the seating area, the exhaust capacity cannot be less than 90% of the supply air according to B149.1-7.20.14. (True/False)

A

True

This regulation ensures proper ventilation and safety in kitchen environments.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

The total air replacement of an installation in a spray booth shall not exceed the total exhaust capacity of the booth. (True/False)

A

True

Adhering to this guideline is crucial for maintaining safety and environmental standards.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Before firing the main burner on site, what are three critical checks that should be confirmed regarding the unit’s installation?

A
  • Confirm wiring is per drawings
  • Gas pressure aligns with rating plate
  • Valve train complies with code

These checks ensure the safe and efficient operation of the burner.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

During the commissioning procedure, what two important checks should be performed on the blower motor?

A
  • Check for correct voltage and overload protection
  • Check for correct rotation

These checks are essential to ensure the blower motor operates safely and effectively.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

During the commissioning procedure, a leak test of the valve train should be performed with the test firing cock open. (True/False)

A

False

The leak test should be performed with the test firing cock closed to ensure accurate results.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What is the typical (and maximum) discharge air temperature setting for a DFMA?

A

72 degrees Fahrenheit (max 75 degrees)

Proper temperature settings are crucial for system efficiency and comfort.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly