Primary Reformer Trips Flashcards

1
Q

Primary Reformer Fuel Gas trips

A

Low= .9psig

High= 26psig

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Flue Gas Temperature trip (ID Fan protection)

A

670 degrees F

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Flue Gas Temperature trip to Low Fire (Temp Coil protection)

A

618 degrees Fahrenheit

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Process Steam Trip

A

47.5 MLBs./hour

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Process Feed Gas Trip

A

250 MSCF/Hour

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Secondary Reformer Transfer Header jacket water level

A

10 minute timer

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Primary Reformer Transfer Header jacket water level

A

10 minute timer

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Secondary Process Condensate K.O. Drum

A
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Primary Reformer Radiant Outlet Temp Trips

A

1650 degrees Fahrenheit

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Primary Reformer Common Header Temp Trip

A

1600 degrees Fahrenheit

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Primary Reformer Common Header Temp Trip to Minimum Fire

A

1575 degrees Fahrenheit

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

All ID Fans Total Flow (inferred)

A

3000 MSCF/ Hour

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Primary Reformer CO trip

A

200 PPM

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

All ID fans total flow (inferred) minimum fire

A

2000 MSCF/ Hour

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

Primary Reformer CO Minimum Fire

A

200 PPM

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

Primary Reformer Convection Section low fuel gas trip

A

1 psig

17
Q

Primary reformer convection section High fuel gas trip

A

26 psig

18
Q

Primary Reformer Superheated steam outlet located at the south end of the, second deck

A

900 degrees Fahrenheit