PROVISIONS FOR ELECTRICAL SYSTEM DESIGN 2 Flashcards

WIRING AND PROTECTION (65 cards)

1
Q

This article provides requirements for the identification of terminals, grounded conductors in premises wiring system, and identification of grounded conductors.

A

Article 2.0 Use and Identification of Grounded Conductors

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

This article provides the general requirements for branch circuits.

A

Article 2.10 Branch Circuits

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

In dwelling units and guest rooms or guest suites of hotel, motels and similar occupancies, the voltage shall no exceed _________, between conductors that supply (1) luminaires (s) chord-and-plug connected loads 2760 volt amperes, nominal, or less or less than ½ hp.

A

230 V nominal

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Multi-outlet branch circuits greater than _____ shall be permitted to supply non lighting outlet loads on industrial premises where conditions of maintenance and supervision ensure that only qualified persons service the equipment.

A

50 A

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

For ranges of 8 ¾ kW rating, the minimum branch circuit rating shall be _____.

A

40 A

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Where a branch circuit supplies continuous loads or any combination of continuous and non continuous loads, the rating of the overcurrent protective device shall not be less than the noncontinuous loads plus _____ of the continuous loads.

A

125%

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

The rating of any cord-and-plug-connected utilization equipment not fastened in place not exceed _____ of the branch-circuit ampere rating.

A

80%

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

A ________ branch circuit shall be permitted to supply lighting units or other utilization equipment, or a combination of both

A

15- or 20 A

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

A ________ branch circuit shall be permitted to supply fixed Lighting Units with Heavy-Lamp holder other than Utilization Equipment.

A

30 A

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

A _____ branch circuit shall only supply non-lighting outlet loads

A

50 A

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

A ________ branch circuit shall be permitted to supply cooking appliances that are fastened to place

A

40-50 A

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

In every kitchen, family room, dining room, living room, parlor, library, den, sunroom, bedroom, recreation room, or similar room or area of dwelling units, receptacle outlets shall be installed not more than ________ horizontally from the other receptacle outlet.

A

1800 mm (1.8m)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Receptacle outlets shall be located above, but not more than _______ above, the countertop.

A

500 mm

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Bathrooms shall have at least one receptacle within ______ from the outside edge of each basin.

A

900 mm

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

For a one-family dwelling and each unit of dwelling units shall have at least one accessible outlet at grade level not more than _______ in front and back of the dwelling unit.

A

2000 mm

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

Laundry areas, basement and garages shall have at least _______ receptacle installed for the laundry.

A

one

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

In dwelling units, hallways that have __________ or more in length shall require at least one receptacle outlet.

A

3000 mm (3m)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
17
Q

Special individual outlets such as heating, air-conditioning and refrigeration equipment outlet shall be installed and be located on the same level _______ within the equipment.

A

7600 mm

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
18
Q

Where a feeder supplies continuous loads or any combination of continuous and noncontinuous loads, the minimum feeder conductor size shall have an allowable ampacity not less than the noncontinuous load plus _______ of the continuous load

A

125%

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
19
Q

Where a feeder supplies continuous loads or any combination of continuous and noncontinuous loads, the rating of the overcurrent device shall not be less that the noncontinuous load plus ______ of the continuous load.

A

125%

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
20
Q

This Article provides requirements for calculating branch-circuit, feeder and other service loads.

A

Article 2.20 Branch Circuit, Feeder, and Service Calculations

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
21
Q

Conductors that supply a single motor used in a continuous duty application shall have an ampacity of not less than _______ of the motor full-load current rating.

A

125%

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
22
Q

Outlets for heavy-duty lamp holders shall be calculated at a minimum of ___________.

A

600VA

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
23
Q

Outlets for sign and outline lighting shall be calculated at a minimum of ___________.

A

1200VA

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
24
Receptacle outlets shall be calculated at not less than _______ for each single or for each multiple receptacle on one yoke.
180 VA
25
In each dwelling unit, the small-appliance circuit load shall be calculated at ______ for each 2-wire small-appliance branch circuit.
1500 VA
26
A load of not less than shall be ________ included for each 2-wire laundry branch circuit installed.
1500 VA
27
It shall be permissible to apply a demand factor of ______ to the nameplate rating load of four or more appliances fastened in place, other than electric ranges, clothes dryers, space-heating equipment, or air-conditioning equipment, that are served by the same feeder or service in one-family, two-family, or multifamily dwelling.
75%
28
The load for household electric clothes dryers in a dwelling unit(s) shall be either ______ of the nameplate rating, whichever is larger, for each dryer served.
5000 VA
29
This article covers service conductors and equipment for control and protection of service and their installation requirements.
Article 2.30 Services
30
The overhead service conductors shall not be smaller than _____________.
8.0 mm^2 Cu or 14 mm^2 Al or copper-clad aluminum.
31
Each service drop, set of overhead service conductors, set of underground service conductors, or service lateral shall supply only ____ set of service entrance conductors.
one
32
The minimum service entrance conductor size shall have an allowable ampacity not less than the sum of the non-continuous load plus _____ of the continuous load.
125%
33
Protects all the internal components of the circuit breaker. It also supports the components and provides insulation to contain the arc. Depending on the current and voltage used, they are further available in three forms: molded, insulated, and metal.
Frame or external casing
34
Its function is to open or close the contacts of the circuit breaker. All types of circuit breakers use some method to disconnect the power supply. These typically include spring-loaded switches, solenoid, hydraulic, and pneumatic switches.
Operating Mechanism
35
The function of contacts is to pass the current through the circuit breaker when they are closed. Generally, a circuit breaker has two electrical contacts: a static contact and a temporary contact.
Electrical contacts
36
This usually extinguishes the arc in the event of a fault. When the contacts are disconnected, electricity can jump through the gap between the end parts of the contact. This causes an arc of electricity that can reach very high temperatures.
Arc Extinguisher
37
It helps to detect abnormal current flow in the event of overcurrent and short circuit. It causes the operating mechanism to open the contacts.
Trip Unit
38
Is a safety switch usually built into your home’s electrical system. It looks like a switch that helps to stop the flow of electricity to any component or device that consumes a lot of power.
AC Circuit Breaker
39
This type of circuit breaker is used with a voltage rating of more than 600 volts. These are powered by solenoids, with current sensing protective relays driven through current transformers.
High Voltage Circuit Breaker
40
This type of circuit breaker is suitable for circuits rated at 600 volts or less. The most commonly used low-voltage circuit breaker is a molded case circuit breaker. Low-voltage circuit breakers are commonly seen in domestic, commercial, and industrial applications.
Low Voltage Circuit Breaker
41
These types of circuit breakers serve as a substitute for fuses and are used to protect the circuit from excess current. They protect low voltage circuits 240/415V AC with a wide range of current ratings below 125V.
Miniature Circuit Breaker (MCB)
42
are designed to provide protection against over-current. They are suitable for use in circuits where the maximum expected current is known and relatively constant, such as lighting circuits.
Type A MCBs
42
are designed to provide protection against over-current and short circuits. They are suitable for use in circuits where the load is variable, such as in motor circuits.
Type B MCBs
43
are designed to provide protection against both over-current and earth fault currents.
Type C MCBs
43
are designed to provide protection against over-current and earth fault currents, with a higher tripping threshold than Type C MCBs.
Type D MCBs
44
are designed to provide protection against over-current and earth fault currents in residual current devices (RCDs) used in electrical systems.
Type G MCBs
45
are designed to provide protection against over-current and earth fault currents in electrical systems that are powered by direct current (DC).
Type H MCBs
46
are designed to provide protection against over-current and short circuits in electrical systems with high fault levels.
Type K MCBs
47
is a circuit breaker with a high current rating of up to 2500 amps. These are generally seen where the current rating exceeds the limits of the MCB (Miniature Circuit Breaker).
Molded Case Circuit Breaker (MCCB)
48
This circuit breaker works on a thermal-magnetic tripping mechanism where the thermal mechanism is used for overloading and magnetic is used for short circuit conditions.
Molded Case Circuit Breaker (MCCB)
49
These molded case breaker types are meant to trip if they detect a current 3-5 times higher than what they are rated for, usually within 0.04 to 13 seconds, dependent on the rating of the breaker.
Type B MCCB
50
These types of molded case breaker are built to trip at fault currents that are between 5-10 times the rated current, with durations of 0.04-5 seconds.
Type C MCCB
51
This type of MCCB has a higher tolerance to fault currents. It trips at between 10-20 times its rated current, which is quite high, and for between 0.04 and 3 seconds.
Type D MCCB
52
These molded case circuit breaker types trip when they detect current values between 15-20 times the rated value and in a time range of 0.04 to 5 seconds. These are specifically designed for short circuit currents, hence their high sensitivity rating.
Type Z MCCB
53
is specifically designed to trip when the current reaches between 8-12 times the rated value and for 0.04 to 5 seconds.
Type K MCCB
54
is the most common type and used in all kinds of low-voltage AC systems.
AC MCCB
55
is mainly used in solar power systems to protect against DC overloads and other DC circuit faults.
DC MCCB
56
A _________________ protects electrical equipment operating with DC. It has additional arc extinguishing measures. These are relatively new technologies for most homeowners because most appliances are used in the homework with AC. These circuit breakers use 24 VDC to 48 VDC programmable logic controllers (PLCs).
DC Circuit Breaker
57
is a switching device that interrupts the normal flow of current in the circuit. These circuit breakers provide a very efficient way of power transmission over long distances. Nowadays, there are used in various green energy generation.
HVDC Circuit Breaker
58
These types of circuit breakers use an insulating oil (which has better dielectric strength than air). The insulating oil is a dielectric medium to extinguish the arc and break the circuit safely.
Oil Circuit Breaker
59
These types of circuit breakers use oil arc quenching media as well as insulating media between the current-carrying contacts and the earthing parts of the breaker. The amount of oil required in this circuit breaker depends on the system voltage.
Bulk Oil Circuit Breaker
60
is an electrical protection device used for short circuit and overcurrent protection. It operates in air at atmospheric pressure and uses air blast as an arc quenching medium. ACBs are commonly used in low voltage applications, up to 15kV, with amperage ratings ranging from 800A to 10kA.
Air Circuit Breaker (ACB)
61
Multiple grounding rod installed shall not be less than _______ apart.
1800 mm (6 ft.)
61
The electrode shall be installed such that at least _______ of length is in contact with the soil.
2400 mm