PROVISIONS FOR ELECTRICAL SYSTEM DESIGN 2 Flashcards
WIRING AND PROTECTION (65 cards)
This article provides requirements for the identification of terminals, grounded conductors in premises wiring system, and identification of grounded conductors.
Article 2.0 Use and Identification of Grounded Conductors
This article provides the general requirements for branch circuits.
Article 2.10 Branch Circuits
In dwelling units and guest rooms or guest suites of hotel, motels and similar occupancies, the voltage shall no exceed _________, between conductors that supply (1) luminaires (s) chord-and-plug connected loads 2760 volt amperes, nominal, or less or less than ½ hp.
230 V nominal
Multi-outlet branch circuits greater than _____ shall be permitted to supply non lighting outlet loads on industrial premises where conditions of maintenance and supervision ensure that only qualified persons service the equipment.
50 A
For ranges of 8 ¾ kW rating, the minimum branch circuit rating shall be _____.
40 A
Where a branch circuit supplies continuous loads or any combination of continuous and non continuous loads, the rating of the overcurrent protective device shall not be less than the noncontinuous loads plus _____ of the continuous loads.
125%
The rating of any cord-and-plug-connected utilization equipment not fastened in place not exceed _____ of the branch-circuit ampere rating.
80%
A ________ branch circuit shall be permitted to supply lighting units or other utilization equipment, or a combination of both
15- or 20 A
A ________ branch circuit shall be permitted to supply fixed Lighting Units with Heavy-Lamp holder other than Utilization Equipment.
30 A
A _____ branch circuit shall only supply non-lighting outlet loads
50 A
A ________ branch circuit shall be permitted to supply cooking appliances that are fastened to place
40-50 A
In every kitchen, family room, dining room, living room, parlor, library, den, sunroom, bedroom, recreation room, or similar room or area of dwelling units, receptacle outlets shall be installed not more than ________ horizontally from the other receptacle outlet.
1800 mm (1.8m)
Receptacle outlets shall be located above, but not more than _______ above, the countertop.
500 mm
Bathrooms shall have at least one receptacle within ______ from the outside edge of each basin.
900 mm
For a one-family dwelling and each unit of dwelling units shall have at least one accessible outlet at grade level not more than _______ in front and back of the dwelling unit.
2000 mm
Laundry areas, basement and garages shall have at least _______ receptacle installed for the laundry.
one
In dwelling units, hallways that have __________ or more in length shall require at least one receptacle outlet.
3000 mm (3m)
Special individual outlets such as heating, air-conditioning and refrigeration equipment outlet shall be installed and be located on the same level _______ within the equipment.
7600 mm
Where a feeder supplies continuous loads or any combination of continuous and noncontinuous loads, the minimum feeder conductor size shall have an allowable ampacity not less than the noncontinuous load plus _______ of the continuous load
125%
Where a feeder supplies continuous loads or any combination of continuous and noncontinuous loads, the rating of the overcurrent device shall not be less that the noncontinuous load plus ______ of the continuous load.
125%
This Article provides requirements for calculating branch-circuit, feeder and other service loads.
Article 2.20 Branch Circuit, Feeder, and Service Calculations
Conductors that supply a single motor used in a continuous duty application shall have an ampacity of not less than _______ of the motor full-load current rating.
125%
Outlets for heavy-duty lamp holders shall be calculated at a minimum of ___________.
600VA
Outlets for sign and outline lighting shall be calculated at a minimum of ___________.
1200VA