What is the fire rating for building having more than 2 basements?
All structural members up to and including the floor of the lowest level of discharge of underground buildings more than 7000 mm below or more than two level below the lowest level of exit discharge (i.e. All High depth Underground Buildings or Structures) shall be at least 2 hours fire rated construction.
What is the maximum size of a kitchen allowed in a non-sprinklered building?
For a non-sprinkler protected building, the floor area of the kitchen compartment shall not exceed 150 m2.
What is the definition of a high-rise building or structure?
The occupancies or Multiple and Mixed occupancies, facilities, buildings and structures having total height of occupiable or usable space of more than 23 Meters above the lowest grade or lowest level of Fire Service Access into that occupancy is categorized as Highrise Building.
What is the definition of a midrise building or structure?
The occupancies or Multiple and Mixed occupancies, facilities, buildings and structures having total height of occupiable or usable space between 15 Meters to 23 Meters from the lowest grade or lowest level of Fire Service Access into that occupancy is categorized as Midrise Building.
What is the definition of a low-rise building or structure?
The occupancies or Multiple and Mixed occupancies, facilities, buildings and structures having total height of occupiable or usable space up to 15 Meters from the lowest grade or lowest level of Fire Service Access into that occupancy is categorized as Low-rise Building.
What is the definition of a low depth structure or building?
A structure or a building with up to two basements or up to 7 m below the level of exit discharge
What is the definition of a high depth structure or building?
A structure or a building with more than two basements or more than 7 m below the level of exit discharge.
What is the fire rating and the minimum size of the Emergency Command Centre?
The Emergency command centre shall be separated from other parts of the same building by compartment walls and floors having fire resistance of at least 1 hour with fire suppression system. Minimum size shall be 8.9 m2.
At what level shall the fire pump be installed within the building?
Fire pumps shall be located on the ground floor or below grade level with protected dedicated access from the fire engine access level.
At what level shall the intermediate fire pumps and water tanks be located for high-rise buildings?
Where multiple pump sets are required in a Highrise building, Intermediate Fire Pumps and Water tanks shall be located at not more than 90 m intervals from the First Fire Pump located at the lowest level of the structure.
When can the separation between the kitchen and the dining area be exempted?
Separation requirement for kitchen could be exempted when all the cooking facilities in the kitchen are fitted with an approved extinguishing system such as Kitchen hood suppression. Separation requirement for kitchen could also be exempted when an eating establishment is separated from other parts of the same building by walls and floors having fire resistance of at least 1 hour and doors having fire resistance of at least half an hour.
What is the fire rating for the separation between theatre, cinema or concert hall from other parts of the building?
A theatre, cinema or concert hall shall be separated from other parts of the same building, which is of a different purpose group, by compartment walls and floors having a fire resistance of at least 2-hour. If the building is protected by an automatic sprinkler system, the fire resistance rating of the compartment walls or floors can be reduced to 1-hour.
What is the fire rating for hotel bedrooms?
Each hotel bedroom shall be compartmented from adjoining rooms and other parts of the same building by construction having fire resistance rating of at least 1 hour.
What is the fire rating for labor accommodation bedroom?
Each labor accommodation bedroom shall be compartmented from adjoining rooms and other parts of the same building by construction having fire resistance rating of at least 1- hour.
What are the kitchen fire rating requirements for a labor accommodation?
Kitchens are only allowed on the ground floor and shall be enclosed with minimum 1-hour fire rated compartment wall, including 1⁄2-hour fire rated door. Kitchen shall be separated by 1 hour fire rating and a protected corridor away from the dormitory sleeping area on the ground floor.
What is the fire rating required for motor vehicle workshop?
A motor vehicle workshop shall be separated from any other part of the same building by compartment walls and floors having fire resistance of not less than 2 hours.
What is the fire rating and ventilation requirement for a spray painting booth or for any spray painting process?
Areas in which spray painting or other allied processes are performed or carried out, shall be separated from other parts of the same building by compartment walls and floors having fire resistance of not less than 2 hours. Spray painting booths shall have built in vapor extraction system.
What is the size requirement for cold room and the fire rating of the construction?
Where a cold room has a floor area exceeding 20 m2, a separate outer layer of non- combustible construction, including the door, having minimum 1-hour fire resistance rating (with sprinkler), shall be provided to compartmentalize the cold room enclosure from other areas. Provision of the fire resisting outer layer enclosure, including the fire door to the cold room would not be required if the cold room has a floor area not exceeding 20 m2 and is sprinkler protected. The storage materials shall not include highly flammable chemicals. Cold room lesser than 20 m2 provided with at least one hour fire rating compartment, need not be provided with sprinklers provided that the storage shall not include flammable materials.
What shall the maximum allowable area of a mezzanine floor?
The aggregate area of mezzanines within a room, other than those located in special-purpose industrial occupancies, shall not exceed one-third the open area of the room in which the mezzanines are located.
What is a breeching inlet?
A connection through which the Civil Defence fire department can pump supplemental water into the sprinkler system, standpipe, or other system, furnishing water for fire extinguishment to supplement existing water supplies.
What is the definition of fire access level?
Level where Civil Defence Fire Appliances (Fire Truck/Engine) are deployed and where fire fighters have direct access into the building.
What is the definition of fire engine access road?
The road to the building or structure to allow access for Civil Defence fire-fighting and rescue apparatus.
What is the definition of fire engine access way?
The path adjacent to the building or structure to allow operational setup for Civil Defence fire-fighting and rescue apparatus such as Aerial Appliances.
What is a landing valve?
A 65 mm diameter water outlet normally located inside or near the staircase landing for trained or Civil Defence fire fighters to use during fire.