remote shutdown Flashcards

1
Q

What is RCS Press WR PI-963 considered as per T.S. 4.1-4?

A

Post Accident Instrument

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What is Remote Shutdown required for?

A

Only required to get and maintain HOT SHUTDOWN

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What must be done to start EF-P-1?

A

Must manually OPEN MS-V-13A/B

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What must be done to start EF-P-2A/B?

A

Must manually start and breakers on 1D and 1E 4160V Bus

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Where must DC-V-2B/65B be controlled to control RCS C/D during EOP-030?

A

Locally in “B” DH vault

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Which NI is the only NI at RSD?

A

NI-12

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

How is AH-C-4B controlled?

A

Controlled locally at control panel with 69 switch (no key)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

How is AH-P-3B controlled?

A

Controlled at 1B ES MCC with 69 switch

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Where is MU-V-16C/D controlled?

A

At RSD (“B” side HPI valves)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Is high temp isolation of Letdown rupture (HELB) bypassed for MU-V-2A/B on RSD?

A

No, but HELB (145F) AND process temp (135F) IS bypassed for MU-V-3

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

How do you get control of AH-E-1 in SLOW at MCC if running in FAST?

A

OPEN the breaker at the MCC and then re-close and take switch to SLOW

How well did you know this?
1
Not at all
2
3
4
5
Perfectly