What is RCS Press WR PI-963 considered as per T.S. 4.1-4?
Post Accident Instrument
What is Remote Shutdown required for?
Only required to get and maintain HOT SHUTDOWN
What must be done to start EF-P-1?
Must manually OPEN MS-V-13A/B
What must be done to start EF-P-2A/B?
Must manually start and breakers on 1D and 1E 4160V Bus
Where must DC-V-2B/65B be controlled to control RCS C/D during EOP-030?
Locally in “B” DH vault
Which NI is the only NI at RSD?
NI-12
How is AH-C-4B controlled?
Controlled locally at control panel with 69 switch (no key)
How is AH-P-3B controlled?
Controlled at 1B ES MCC with 69 switch
Where is MU-V-16C/D controlled?
At RSD (“B” side HPI valves)
Is high temp isolation of Letdown rupture (HELB) bypassed for MU-V-2A/B on RSD?
No, but HELB (145F) AND process temp (135F) IS bypassed for MU-V-3
How do you get control of AH-E-1 in SLOW at MCC if running in FAST?
OPEN the breaker at the MCC and then re-close and take switch to SLOW