Sprinkler Installation Flashcards

(50 cards)

1
Q

Standard spray sprinklers heads were approved in ___, listed in ___

A

Approved in 53’ and listed in 58’

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

The available ___ and the amount of ___ discharged will determine the spray pattern

A

pressure and amount of water

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Deflectors do what?

A

Break up the water to form a specific pattern.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

When ___ are located more than ___inches below the sprinkler deflector, an adequate spray pattern develops and obstructions up to and including ___ ft would not require additional protection underneath.

A

When obstructions are located more than 18 inches inches below the sprinkler deflector, an adequate spray pattern develops and obstructions up to and including 4 ft would not require additional protection underneath.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

A standard spray sidewall sprinkler forms what kind of spray pattern? What two ways can they be orientated?

A

A quarter of a sphere

There are vertical and horizontal sidewall sprinklers

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What is the profile?

A

Profile is the distribution discharge pattern of a sprinkler

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What is the throw?

A

Throw is the distance that the water spray(discharge) travels from a sprinkler in one direction.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

How to identify a sprinkler?

A
1-2 uppercase letters to identify manufacturer
k-factor
deflector characteristic
pressure rating
thermal sensitivity
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

k factors are all based on the ___ k factor.

A
  1. 6 k factor

11. 2 k factor would discharge 200% of a 5.6k factor

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

If corrugated metal deck roofs are deeper than >3 inches you must from the ___ point. If they’re <3 inches you can measure from the ___ lowest point

A

> 3 inches - highest point

< 3 inches - lowest point

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

if the deflection or sag in the insulation exceeds ___ inches. The deflector distance shall be measured to the high point of the insulation.

A

6 inches

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Sprinklers shall be installed under fixed obstructions over __ ft

A

4 ft in width regardless of how low they’re to the sprinkler.

  • sprinkler cannot be further than 3 inches away from the edge under the obstruction
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

If obstructions are less than __ inches from the floor you do not need to put a sprinkler head under it.

A

24 inches from the floor

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

If the room is less than ___ sqft a single sprinkler at the highest ceiling level shall be sufficient without regard to obstructions or minimum distance to the wall.

A

400 sq ft

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

Quick response heads are not allowed in which hazard occupation classification.

A

extra hazard occupancies

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

Panel construction - formed by beams/girders/trusses

max area of 300 sq ft
penetrations are filled to trap hot gases.

A

Heads can be lowered where their is panel construction.

Ex. between web joists

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
17
Q

Bar joists with fireproofing >30%

A

If water can’t pass it obstructed construction

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
18
Q

Small room rule

A

A compartment of light hazard occupancy classification having unobstructed construction and a floor area not exceeding 800 sq ft

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
19
Q

Small room rule

A

A compartment of light hazard occupancy classification having unobstructed construction and a floor area not exceeding 800 sq ft

Sprinklers shall not be more than 9 ft from any single wall

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
20
Q

Sprinklers must be a minimum of __ inches from any wall

A

4”

heat won’t collect right in the corner of the wall.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
21
Q

Sprinkler heads cannot be within __ ft of each other

A

6 ft or else baffles will be required.

22
Q

Baffles shall not be less than __ inches long and __ inches high

A

8 inches long and 6 inches high

pendent - baffle must come down to at least level with sprinkler head
upright - baffle must extend 2-3 above upright

23
Q

unobstructed construction sprinklers must be __ inch to __ inches down from the ceiling

A

1-2 inches from ceiling

24
Q

If a vertical change in the ceiling creates a distance of more than __ inches it becomes a wall.

25
Obstructed construction sprinklers can be a maximum distance of __ inches down from the ceiling but has to be installed 1-6 inches below the obstruction.
1-6 inches below the obstruction but to a maximum of 22inches
26
Sprinklers in sloped ceiling should all be ___ ____ sprinklers
quick response sprinklers
27
Sprinkler heads have to be parallel to ceilings even if they are sloped.
True
28
shadow areas of a sprinkler are permitted as long as the cumulative dry areas do not exceed ___ sq ft per sprinkler
15 sq ft per sprinkler
29
finished soffit < 8 inches | finished soffit >8 inches
If the finished soffit is >8 a sprinkler underneath is required.
30
* 1 head sidewall finished soffit < 8 inches finished soffit >8 inches 2* heads sidewalls on either side of finished soffit these numbers become ___
If the finished soffit is >8 a sprinkler underneath is required. 16 inches
31
Standard sidewall sprinklers minimum distances
4-6 from ceiling | 6-18 when listed
32
vertical sidewalls distances from walls
4-6 inches from wall | horizontal sidewalls can be right on the wall.
33
sidewall sprinklers should not be installed less than __ ft from light fixtures or similar obstructions.
4 ft
34
sidewall sprinklers | there cannot be an obstruction within __ ft of the deflector
4 ft
35
sidewall sprinkler | 3 times rule
the distance between the sprinkler and the obstruction has to be a minimum of 3x the largest dimension of the obstruction.
36
sidewall sprinklers | the clearance between the deflector and the top of storage shall be __ inch or greater
18 inches or greator
37
sidewall sprinklers | the clearance between the deflector and the top of storage shall be __ inch or greater
18 inches or greater
38
special sprinklers rules | maximum protection area should not exceed ___ sq ft
maximum protection area should not exceed 400 sq ft
39
``` the temperature rating for heads orange or red yellow or green blue purple black ```
``` orange or red 135-170 yellow or green 175-225 blue 25-300 purple 325-375 black 375+ ```
40
relation of maximum ceiling temperature to the temperature rating of heads
temperature rating of head is generally 25 higher than what you would expect for the maximum ceiling temperature
41
the high-temperature zone around a unit heater
7 feet radius 7 feet above 2 feet below requires high temperature heads
42
intermediate temperature zone around a unit heater
7 - 20 feet @ 30 degree angle | requires intermediate temperature head
43
steam main temperature zones(Non-insulated) ex. ducts
intermediate zone 2'6" above | 1' below
44
blow off valve temperature zone
high temperate zone 7' in front of blow off valve
45
maximum protection area of an extended coverage head is __ sq ft
400 sq ft
46
extended coverage sprinklers must be a minimum of __ ft apart
8 ft apart
47
Extended coverage sprinklers use the __ times rule instead of the 3 times rule
4 times rule
48
CMSA sprinklers are permitted in __, ___, or ___ systems
wet, dry, or preaction systems
49
CMSA sprinklers max spacing
12ft
50
where can sprinklers be omitted?
``` bathrooms in dwelling units less than 55 sq ft closets <= 24 sq ft in hotels and motels closets <= 6 sq ft in sleeping units of hospitals electrical rooms where: only electrical equipment 2hr fire rated walls no storage only k-class fluid electrical equipment ```