Star Exam 2.0 Flashcards
(364 cards)
- The evaporator in a refrigeration system:
Is the component where refrigerant boils and absorbs heat.
The evaporator absorbs heat into the system. When the refrigerant is boiled at a lower temperature than that of the substance to be cooled, it absorbs heat from the substance.
- The purpose of the compressor is to change ___________.
Low-pressure, low-temperature vapor to a high-pressure, high temperature vapor
The compressor can be considered a vapor pump. It reduces the pressure on the low-pressure side of the system, which includes the evaporator, and increases the pressure in the high-pressure side of the system. This creates refrigerant flow from the low-pressure side to the high-pressure side. All compressors in refrigeration systems perform this function by compressing the vapor refrigerant.
- A common refrigerant leak detection device is the:
Halide torch.
Two refrigerant detection devices are commonly used: the halide torch and the electronic leak detector.
The halide torch cannot be calibrated, but it can be checked to make sure that it will detect leaks. It must be maintained to be reliable. It will detect a leak rate of about 7 oz. per year. The halide torch uses the primary airport to draw air into the burner through a flexible tube. If there is any chlorine-containing (CFC or HCFC) refrigerant in this air sample, it passes over a copper element, and the color of the flame changes from the typical blue of a gas flame to a green color. A large leak will extinguish the flame of the halide torch. The halide torch cannot be used with HFC refrigerants.
- Copper-plating of compressor parts is:
Caused by contaminants in the system.
Copper Plating.
Copper plating is the depositing of a layer of metallic copper on interior parts of a compressor, especially bearings, the plate on which the compressor valves are mounted, and other parts that may be subjected to high temperature. In severe cases of copper-plating, the copper deposit may build up to a thickness sufficient to interfere with proper operation of the compressor, and in extreme conditions may be a primary cause of compressor failure. There are two phases to the copperplating process:
- Copper is first dissolved into the refrigerant oil mixture.
- Copper is then plated out on compressor parts.
- If not properly installed, a hot-gas muffler might trap:
Oil.
The muffler is installed in the discharge line as close as possible to the compressor. Due to their construction, mufflers usually form natural oil traps unless properly installed.
- Unit ventilators are usually equipped with outside air dampers to:
Both are correct
Partial Correct: Provide ventilation air during building occupancy
Partial Correct: Comply with most local or state codes
The unit ventilator has an outside air intake as well as a return air intake. One or more dampers in the outside air and return air passages are under automatic control to proportion the amount of each type of air admitted into the unit.
Although now available as a year-round air conditioner with cooling ability from mechanical refrigeration, the unit ventilator was originally intended to provide heating and ventilation. Its design is based on the principle that classrooms are rather densely populated areas and therefore:
1. Ventilation air is desirable at all times when the room is occupied and, in fact, may be required by state, local and provincial codes.
2. Heat generated by the occupants makes cooling desirable, even when outdoor temperature is fairly low, and at such times cooling can be accomplished by supplying an increased quantity of outdoor air.
- Face and bypass dampers should be adjusted to provide:
Tight shut off to reduce the possibility of overcooling or overheating When installing face and bypass dampers, it is most important to assure they are properly adjusted so they will close tightly.
Leakage of bypass dampers, when in closed position, can:
a. Seriously reduce the cooling capacity of the system.
b. Overheat the space if there is a heating coil in the bypass and it is in operation.
c. Cause overcooling, or a lack of heat during the heating season if the bypass contains a heating coil.
- With belt driven equipment, alignment of the motor and driven equipment pulleys
Is accomplished using a string or straight edge.
A straight edge or string can be used to run from one pulley to the other. Alignment is complete when the string or straight edge touches both pulleys in two places at once.
- To assist consumers in making an informed choice when purchasing unitary air conditioning equipment, the efficiency of such units is expressed as Energy Efficiency Ratio (EER or SEER) the units of which are:
Btuh/watt A way of expressing efficiency is by the energy efficiency ratio, (EER), which is defined as Btuh/watt or Btu/watt-hour, which is derived by dividing the cooling capacity in Btuh by the electric input in watts.
Thus, a unit or unitary system having 78,000 Btuh cooling capacity and 11.3 kW input has an EER of 78,000 divided 11,300 or 6.9.
- Firestats located in the air stream of air handling units:
All
A. Are required in both the supply and return air streams
B. Partially Correct: Should be the manual reset type
C. Partially Correct: Should be nonadjustable
Central systems using return air are usually required to have a means for stopping the supply fan in the event of fire in the conditioned space.
This may be provided in small and medium-size systems by a safety highlimit thermostat, referred to as a firestat, which is placed in the return air duct. Upon sensing high temperature, it will trip and open an electrical circuit which stops the fan and thus avoids spreading the fire by way of the duct system. When tripped, the firestat requires manual reset.
- A sleeve bearing would typically be used in a motor that:
Operates with a light load and where noise is a factor.
The sleeve bearing is used where the load is light and the noise must be low (e.g., a fan motor on a residential furnace).
- A bearing used on the bottom of a motor where the shaft is positioned vertically is called a ____________ bearing.
Thrust
The typical air-cooled condenser has a vertical motor shaft and is pushing the air out the top of the unit. This results in a downward thrust on the motor bearings. The vertical condenser fan is trying to fly downward into the unit to push air out the top. This puts a real load on the end of the bearing (called the thrust surface).
- To produce electromagnetism, relative motion is required between a magnetic field and a/an:
Conductor
To produce electromagnetism, either the conductor moves through the field or the field is moved across the conductor. All that is really required is relative motion between a conductor and a magnetic field.
- Materials which do not allow their electrons to spin out of orbit easily are called:
Insulators
To produce electromagnetism, either the conductor moves through the field or the field is moved across the conductor. All that is really required is relative motion between a conductor and a magnetic field.
- A battery is an example of a/an ____________ source.
Direct current
Direct current flows constantly in one direction. A battery is one source of direct current. It will always have two poles or terminals, one negative (-) and one positive (+). The electron flow is from positive to negative inside the battery. However, the external flow for the electrical circuits is always negative to positive. The electrons flow in only one direction. Direct current will continue to flow until the circuit is broken or the source of energy stops supplying electrons.
- “Current flowing through a conductor in one direction for a split second, then in the opposite direction for a split second” would be a good definition of:
Alternating current
Alternating current is defined as current flowing through a conductor in one direction for a split second, then in the opposite direction for a split second.
- If a pressure gauge reads five psig at sea level elevation, the corresponding absolute pressure is ___________ psia.
ANS: 19.7 5.0 psig + 14.7 = 19.7 psia.
- Solar ________ is the amount of solar thermal energy produced divided by the water heating energy demand of the building.
Fractional
- The portion of the electromagnetic spectrum to which solar collectors respond is _____ and near-infrared radiation.
Visible light
- During winter, ________.
Daylight is shorter and the Northern Hemisphere is angled away from the sun
- Unless equipped with OSHA or Canadian Standards Association (CSA) approved ground-fault circuit interrupters, portable electric lighting used in wet and-or other conductive locations as, for example, drums, tanks and vessels, shall be operated at ______ volts or less.
12
Unless equipped with approved ground-fault circuit interrupters, 120 volt lighting is not acceptable.
- Receivers are usually required in systems having:
Evaporative condensers
Evaporative condensers and air-cooled condensers, being constructed with coiled tubing, contain very little storage space for refrigerant, and therefore systems with such condensers will generally require a receiver. (Water-cooled condensers of shell-and-tube type normally have enough volume to serve as receivers, and a separate or auxiliary receiver in this case is not needed unless the system is unusually extensive.)
- An important feature of a refrigerant receiver, in the case where the liquid line to the evaporator comes out of the top of the receiver, is a:
Dip tube
Where liquid leaving the receiver flows vertically upward out of the receiver, an integral dip tube is an important feature of the receiver. The dip tube, connected to the receiver outlet, extends to about onehalf inch from the bottom of the receiver. Its purpose is to ensure that only liquid enters the line leaving the receiver, preventing any vapor from entering the liquid line. If replacing or re-installing a receiver, it is essential to determine which connection has the dip tube. A receiver may not contain an integral dip tube, and so it may have to be provided in the field. The bottom end of the dip tube should not be made with a square cut; it should be cut-off at an angle of approximately 45 degrees. For this purpose, a receiver valve, can be used. The above considerations of the dip tube apply only to receivers where the liquid outlet is on the top of the receiver. If a receiver outlet is on the bottom of the receiver so that refrigerant can flow out by gravity, no special provision is needed to assure the liquid line being free of vapor; in such case, the dip tube must of course be omitted or only vapor would enter the liquid line.
- A pressure regulator is constructed so that a rise in ____________ steam pressure reduces off the inlet flow of supply steam.
Downstream