Steam/Water Flashcards

(34 cards)

1
Q

What is the delay time prior to a low drum level trip

A

One minute delay timer

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Does the feedwater ESP block valve close during boiler trips

A

It only close when boiler has been ESPed or if valve is in manually activated at ESP panel

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What is the purpose of the feed water area isolating valve and when is it used

A

The feed water isolating valve isolates the boiler drain system from the mud drum blowdown tank
It is used whenever the boiler is hydroed, filled, or isolated for a major outage.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

In what order will safty valves operate

A

Superheater first followed by the steam drum vents

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What devices protect the boiler from over pressure

A

Superheater and steam drum saftey valves

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What is the #2 recovery design pressure

A

700 psi

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

How many trs violations does the state allow

A

Zero

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

How many TRS excursions does the state allow

A

Two (2) excursions per calendar quarter

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What is the differance between a TRS excursion and a violation

A

Excursion - TRS 12hr average finishes above permit

Violation - when the 3rd excursion occurs within a calendar quarter

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What can happen if the steam trap is not operating correctly

A

Stuck closed - condensate can fill the header leading to possible smelt water reaction inside the furnace
Stuck open - steam is continually wasted, High cost

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What is included in the sootblower system that purges the water from the steam supply

A

Steam trap is mounted at the bottom of each sootblower steam supply header

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

How is the ID fan steam lance operated

A

Steam lance is operated one minute of every 20 minutes

Local timer

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

What does the ID fan steam lance do

A

Cleans the buildups from the ID fan rotor

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

How is the ID fan driven

A

Fan is driven by a 3200 hp steam Turbine using 600 psi

Steam exhausting to 50 psi

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

What is the centerline for O2 on the boiler

A

1.5 - 2.5

2 is the target

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

What is the differance between operating sootblowers in modicon mode versus computer mode

A

Modicon - blow in numerical order

Computer - by recipe ( normal)

17
Q

If the secondary windbox pressure needs to be raised or lowered, how should it be done

A

Change the splits (%)
Or
Increase the total air

18
Q

What happens if the air flow is allowed to get too low while burning oil or liquor

A

Boiler will trip on low air flow

Will flame out

19
Q

Describe the procedures for putting the steam coil air heater(SCAH) in and out of service

20
Q

What is normal economizer exit flue gas temperature

A

675 - 650 (IN)

400 (out)

21
Q

Why not operate the furnace draft higher or lower than target

A

Low - trip ID fan out on speed

High - cause boiler to blow back

22
Q

What is target for furnace draft

23
Q

Where is the furnace draft reading taken

A

Furnace draft tap is located in the upper furnace on the north boiler wall opposite the screen and sends its signal to TDC group 1

24
Q

How is furnace draft controlled

A
  • 0.3

Controls ID fan speed

25
What is furnace draft
Suction on the boiler
26
Explain the shutdown procedures for the ID fan
``` Put auxiliary oil pump in manual Slow fan down to 350 rpm Hand trip fan Close and lock inlet steam valve Close outlet steam valve Open condensate drains Cut off steam lance to rotor Close and lock header valve on 600 psi header deck Make sure equalizing valve is also closed ```
27
Explain the startup procedures for the ID fan
``` Open equalizing valve Startup auxiliary oil pump Open outlet steam valve at ID fan Back warm turbine or 1.5 hours Open the 600psi header valve Close equalizing valve Close condensate drains at ID fan ```
28
During maintenance mode why is the air to liquor put in auto
It will be to low of air flow to keep it burning right
29
What is the minimum black liquor flow required to burn black liquor without fuel oil ( oil burners )
105 mpph | Which is about 30 mcr
30
What is the process for washing the liquor system
....
31
What should you check if burner pressure goes high on one liquor gun but is normal in the other
Plugged nozzle or hose | Bad pressure transmitter
32
What does "high drum" mean
Steam drum has more water than steam
33
What does "low drum" mean
Steam drum is low on water
34
Which water level indicating device initiates the high drum trip
The main water column 2 min delay timer