Systems Test 3 Flashcards

(88 cards)

1
Q
  • LOT 201.14 PZR Pressure & Level*
    • *

At what pressure will the PORV (PCV-655A) lift when COMS is armed?

A
  • 70 - 200 ˚F:*
  • *515 psig**
  • 220 - 380 ˚F:*
  • *730 psig**

Uses Auct Low WR TH / PT-403

  • Note:*
  • Normal PORV setpoint is ≈ 2335 psig. (Master pressure controller 87.5%)*
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q
  • LOT 202.36 Essential Chilled Water*
    • *

When will the running and standby essential chillers start on a LOOP / SI? (ESF DG Sequencer)

A
  • Standby:*
  • *35 sec**
  • (Chilled Water Pump / Chiller Oil Pump)*
  • *65 sec (30 sec prelube cycle)**
  • Essential Chiller*
  • Running:*
  • *240 sec**
  • (Chilled Water Pump / Chiller Oil Pump)*
  • *270 sec (30 sec prelube cycle)**
  • Essential Chiller*

Running essential chiller must complete 135 sec post lube cycle before it can be restarted on ESF DG sequencer.

Note:
ESF sequencer bypasses the 30 min anti-recycle timer permissive

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q
  • LOT 201.27 Containment Combustible Gas*
    • *

What are the sources of H2 during a LOCA?

A
  • Major Source:*
  • *Radiolytic decomposition of water ****

Other Sources:
Zirc water reaction **
H2 from the RCS
Max is 1190 scf
Corrosion of metals and paint in containment
Zinc-based paints & galvanized steel
Aluminum
Less of a source than zinc

  • Note:*
  • Radiolytic decomposition of water and Zirc water reaction are variable and will increase with fuel damage*
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q
  • LOT 201.18 Rod Control*
    • *

What does the Rod Control Startup Switch reset?

A
  • POSSUM:*
  • *P/A Converter**
  • *Bank Overlap Unit**
  • *Step Counters**
  • *Slave Cyclers**
  • *Urgent Failures**
  • *Master Cycler**

Located on CP005.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q
  • LOT 201.18 Rod Control*
    • *

How is the Terror signal generated in the Rx Control Unit?

A
  • Terror = (Tref - Tave) + (Turb Load - NI power)*
  • *Tref → Turbine Impulse Pressure (PT-505)**
  • *Tave → Auctioneered High Tave (T-412A/422A/432A/442A)**
  • *Turb Load → Turbine Impulse Pressure (PT-505)**
  • *NI Power → Auctioneered High PR NIs (NI-41/42/43/44)**
  • Turbine Load - NI Power Portion:*
  • *Used for fast response during transients / load stability**
  • *Passes through Rate comparator**
  • Rate of change produces error output*
  • Steady state results in no output*

Note:
Terror meter on CP005

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q
  • LOT 201.13 ECW*
    • *

What will auto start/stop the ECW pumps?

A
  • Auto Start:*
  • *ESF DG Sequencer (25 Sec)**
  • MODES I, II, III*
  • *CCW Header Pressure - Low (76 psig) [15 sec TD]**
  • *ECW Header Pressure - Low (30 psig) [2/3] [15 sec TD]**
  • Low Pressure on other two trains*
  • Auto Stop:*
  • *Discharge Valve not 95% open after 25 sec**
  • N/A for SI*
  • Note:*
  • 15 Sec TD is to prevent inadvertant train S/U during transient conditions.
  • Discharge valve must be open after 25 sec b/c ECW pump does not have a recirc line to protect the pump
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q
  • LOT 202.36 Essential Chilled Water*
    • *

What ECW pond temperature would make the Essential Chilled Water system inoperable?

A

< 41 ˚F

Per POP02, declare inoperable in MODES 1 - 4.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q
  • LOT 201.18 Rod Control*
    • *

What provides an accurate indication of control rod bank step count positions by counting the up down pulses from the Rx Control Unit?

A

Pulse to Analog Converter

Located in back of DC hold cabinet.

  • Note:*
  • During Rx S/U, resets when operators reset the S/U Switch.
  • During Dropped rod, have to use manual mode to reset bank to height of dropped rod
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q
  • LOT 201.12 CCW*
    • *

What are the important levels in the CCW Surge Tank?

A
  • 83.3%:*
  • *High Alarm**
  • 74%:*
  • *Makeup Valve Closes**
  • 68.75%:*
  • *Makeup Valve Opens**
  • 66.7%:*
  • *Low Alarm**
  • 64.6%:*
  • *1st Low Level Isolation**
  • 61.5%:*
  • *2nd Low Level Isolation**
  • 56%:*
  • *Baffles Begin**
  • 49%:*
  • *Compartment Level - Low Alarm**
  • 8.3%:*
  • *Compartment Level - Low 2 Alarm**
  • Demin water normally fills CCW Surge Tank. (Auto)
  • RMWST can fill the CCW Surge Tank. (Manual)
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q
  • LOT 201.14 PZR Pressure & Level*
    • *

What is the basis for the size of the PZR?

A
  • Enough Water:*
  • *Keep Heaters covered during step load increase of 10%**
  • Enough Steam:*
  • *Accomodate 50% load reduction w/o reaching PZR LVL - High (92%)**
  • w/ Rods and Steam Dumps*
  • *After PZR LVL - High (92%) Rx trip, will not lift safety valves**
  • After Rx Trip AND Turbine Trip:*
  • *No SI**
  • *PZR will not empty**
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q
  • LOT 201.07 Rx Makeup System*
    • *

What will make the makeup stop valves (FCV-0110B/FCV-0111B) auto close?

A
  • Total Makeup Flow Deviation:*
  • *± 15 gpm [15 sec TC]**
  • BA Flow to Blender Deviation:*
  • *± 2 gpm [15 sec TC]**
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q
  • LOT 201.09 RHR*
    • *

What happens in the RHR system during a SI?

A

RHR HX Bypass Closes

RHR HX TCV Valve Full Open

RHR Pumps Trip

  • *CCW from RHR HX opens**
  • CCW pump mini-flow concerns*
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q
  • LOT 201.12 CCW*
    • *

What will cause the thermal barrier isolation valve to shut?

A

CCW Flow - High (60 gpm)

CCW Temp - High (187 ˚F)

Protects CCW piping from thermal barrier HX leak.

Switches located on CP004.

Two in-line backpressure sensing valves provide backup

  • Start to close at 120 psig
  • Full close at 150 psig
  • Note:*
  • Backpressure sensing valves auto-reset when pressure drops below setpoint*
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q
  • LOT 201.10 ECCS*
    • *

What is the system lineup during hot leg recirc?

A

2 ECCS trains injecting into Hot Legs

1 ECCS train injecting into Cold Leg

LHSI and HHSI mini-flow valves closed

Taking Suction from Emergency Sumps

HHSI and LHSI are operated together. Never align HHSI to Hot leg and LHSI to Cold leg or vice versa.

  • Note:*
  • Cold Leg Recirc is the exact same except all 3 ECCS trains injecting into cold legs.*
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q
  • LOT 202.38 FHB HVAC*
    • *

What cools the components in the FHB HVAC System?

A
  • MAB Chill Water:*
  • *FHB HVAC Supply**
  • *Temporary FHB Supplemental Cooling AHU**
  • Only used to reduce heat during cask loading*
  • Essential Chill Water:*
  • *ECCS Pump Room**
  • *Recirc Valve Room**
  • *SF Pump Room**
  • TSC Chill Water:*
  • *PASS Station**
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q
  • LOT 201.09 RHR*
    • *

Which RHR trains are used to transfer refueling water from the refueling cavity to the RWST at the end of a refueling operation?

A

RHR Train “B”

RHR Train “C”

Flow is controlled by throttling the respective train IRC or ORC isolation valve to the RWST

Note:
Do not use train that is selected for shutdown cooling.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
17
Q
  • LOT 201.10 ECCS*
    • *

What are the four phases of a DBA LOCA?

A
  • *Blowdown**
  • Begins with LOCA and ends with RCS pressure = CTMT pressure*
  • *Refill**
  • Water at bottom of the reactor vessel and reaches the bottom of the fuel rods via addition of ECCS (Accumulators and SI pumps).*
  • *Reflood**
  • Rx vessel filled with water*
  • Core temperature rise has terminated*
  • Core temperatures have been reduced to their long term steady state level.*
  • *Long Term Recirculation**
  • Cold Leg Recirc (1st Phase)*
  • Hot Leg Recirc (2nd Phase)*
  • Hot Leg Recirc starts 5.5 hrs (Operator Action) after start of LOCA and cools upper head and prevents boron precipitation.*
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
18
Q
  • LOT 201.14 PZR Pressure & Level*
    • *

How many PZR heaters are there and what is the KW rating / heater?

A

117 Heaters

  • *17.95 KW / Heater**
  • 2101 KW Total*

LCO 3.4.3 PZR

Applicable MODES 1-3

  • Requires 2 groups (A/B) w/ 175 KW each
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
19
Q
  • LOT 201.09 RHR*
    • *

What trips the RHR pumps?

A

SI

RHR Flow - Low (925 gpm [5 sec TC])

CP001 Indications:

  • Amps
  • Flow
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
20
Q
  • LOT 201.10 ECCS*
    • *

What are the Emergency Core Cooling System (ECCS) acceptance criteria?

A

Coolable Geometry

Long-Term cooling

Cladding Oxidation
≤ 17% the total cladding thickness before oxidation.

  • *Peak Cladding Temperature**
  • ≤ 2200 ˚F*
  • *H2 Generation**
  • ≤ 1% the total amount of H2 produced from all metal surrounding the fuel reacting*
  • (excludes metal around plenum volume)*

DBAs:

  • LOCA
  • SLB
  • Fuel Handling Accident
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
21
Q
  • LOT 201.07 Rx Makeup System*
    • *

What will auto close the RMW non-essential service isolation valves? (FV-7663/FV-7659)

A
  • *SI**
  • SI Train “B” (FV-7663)*
  • SI Train “C” (FV-7659)*

RMWST Level (54%)

RMWST Level (54%) will also isolate the RMWST sample line (FV-7664). (SI will not)

  • Note:*
  • Makeup to CCW surge tank and SFP will NOT be secured.*
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
22
Q
  • LOT 201.13 ECW*
    • *

What is the minimum level and max temperature of the ECW pond as required by LCO 3.7.5 Ultimate Heat Sink?

A
  • Level:*
  • *≥ 25.5 ft**
  • Max Level 26 ft (FSAR)*
  • Temperature:*
  • *≤ 99 ˚F**

Pond sized to have a 30 day cooling water supply to safely shutdown and cooldown both Units while maintaining a heat sink for heat removal

  • Note:*
  • ECW Bay LVL indication and alarms located on CP002
  • ECW Bay LVL - Low 2 (14.96 ft) for LCO 3.7.5 entry.
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
23
Q
  • LOT 202.37 EAB/CR HVAC*
    • *

During a DBA, what must control room personnel dose be limited to IAW 10CFR50?

A

≤ 5 Rem Whole Body

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
24
Q
  • LOT 201.10 ECCS*
    • *

What valves in the ECCS have a power lockout feature?

A
  • *HHSI/LHSI Hot leg injection valves (MOV-008/MOV-019)**
  • 100% Power: Closed w/ power locked out*
  • CP-001*
  • *Accumulator outlet valves (MOV-039)**
  • 100% Power: Open w/ power locked out*
  • CP-001 / ASP*

No accumulator pressure / level indicators exist on ASP!!

  • Note:*
  • 2 transfer switches for accumulator outlet valves. 1 transfers control and VPI and the other transfers power lockout feature.*
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
25
* LOT 201.12 CCW* * * * What will happen in the CCW system during a SI?
* *All 3 CCW pumps start** * 20 Sec on ESF DG Sequencer* * Will start even if switches on CP001/CP002 are in off* * *Opens CCW HX outlet and closes bypass valves** * Full flow through HX* **Isolates non-ESF loads** * *Aligns CCW to RCFCs** * Secures RCB Chill Water* * *Opens RHR HX outlet valves** * CCW Min Flow requirements* * * * * Note:* * Must re-align cooling to SFP HXs in 2.5 hrs.*
26
* LOT 201.08 BTRS* * * * What is the limiting temperature and component for the BTRS?
**130 ˚F** **RCP Seals** * * * Limit temperature to 115 ˚F to allow CCPs to add 15 ˚F.
27
* LOT 201.12 CCW* * * * What will happen in the CCW system when the CCW Surge tank reaches 61.5%? (2nd Low Level Isolation)
* *Isolates CCW Header** * Isolates RCP Upper/Lower Bearing Coolers, Thermal Barrier, RCP Motor Air Coolers, SFP HX, PASS Coolers* **CCW Train "B" → CCP "B" and Seal Water HX** **CCW Train "C" → CCP "A" and PDP** * *Opens RHR Outlet Valves for running CCW Pumps _ONLY_** * Min flow requirements* * * * * Note:* * As soon as CCW common header isolated, standby CCW pump will start on CCW Header Pressure - Low (76 psig)*
28
* LOT 201.10 ECCS* * * * What will cause an SI auto recirculation signal?
**SI Signal** **_AND_** * *RWST Level - Low 2 (≤ 75,000 gal) [1/1]** * Each lvl switch provides signal for it's train only* * * * Closes HHSI AND LHSI pump mini-flow valves. When ≥ 1 valve for each pump closed: * Opens containment sump → SI suction header Isolation valve. RWST → SI suction header isolation valve must be manually closed by operator. (CP001) * * * * Note:* * Reset and RWST lvl indication are located on CP001*
29
* LOT 201.13 ECW* * * * What will happen in the ECW system once a ECW pump is started?
**Starts self cleaning strainer motor** * *Starts to Open Discharge Valve after 10 sec** * If not open after 25 sec, pump trips (N/A for SI)* **Opens chemical injection valve for associated bay** * *Opens Blowdown Valves (N/A for train 2A)** * Maintain CP002 switches in CLOSE so doesn't really happen* * *Starts ventilation fans** * Must be manually secured* * * * * Discharge Valve MCC switch in local prevents discharge valve opening when ECW pump starts. * Self Cleaning strainer does not have switch in MCR. * * * * Note:* * Discharge valve will shut 2 mins after ECW pump secures to prevent draining ECW piping to ECW pond and thus preventing water hammer on pump S/U.*
30
* LOT 201.13 ECW* * * * What will cause a CCW standby train not selected alarm on CP002?
**2 ECW/CCW train selector switches in "OFF"**
31
* LOT 201.18 Rod Control* * * * What causes a rod control power cabinet urgent failure?
* *Logic Error** * 0 Current sent to stationary and movable grippers at same time* * *Regulation Error** * Current doesn't match order or Full current for too long* * *Phase Failure** * Excessive voltage ripple* * *Multiplex Error** * Wrong rod getting current* * *Rod Holdout switches out of position** * *Loose Circuit Card** * * * * Stops Auto/Manual rod motion * Individual Bank rod motion will still work * Sends reduced current signal to affected group movable/stationary grippers * * * * Note:* * Non-Urgent is a loss of 1 of the 4 power supplies and will not affect system operation.*
32
* LOT 201.14 PZR Pressure & Level* * * * What Tavg is used to calculate PZR program level?
**Auctioneered High Tavg** ## Footnote * * * Compares selected controlling channel level (LT-465 or LT-467) to program level to determine demand to FCV-0205.
33
* LOT 202.38 FHB HVAC* * * * How many FHB HVAC exhaust trains must be OPERABLE during movement of irradiated fuel?
* *One Train** * *_OR_** * *One Train Capable of being OPERABLE in 2 hrs** ## Footnote * * * TRM 3.9.12 FHB Exhaust Air System
34
* LOT 201.14 PZR Pressure & Level* * * * What is the effect of indicated PZR level for the following conditions? * Reference Leg Break * Diaphragm Failure * Reference Leg Heating
* _Reference Leg Break:_* * *Less Mass → D/P ↓ → Lind↑** * _Diaphragm Failure:_* * *D/P ↓ → Lind↑** * _Reference Leg Heating:_* * *Less Mass → D/P ↓ → Lind↑** * w/o compensation*
35
* LOT 201.14 PZR Pressure & Level* * * * What are the important PZR Master pressure controller setpoints?
* _PCV-655A:_* * *87.5%: Opens** * *75%: Closes** * _Spray Valves:_* * *72%: Full Open** * *40.5%: Start to Open** * _Control Heaters:_* * *34.5%: Zero Power** * 22%: NOP* * *15.5%: Full Power** * _B/U Heaters:_* * *14.5%: Turn Off** * *9.5%: Turn On**
36
* LOT 202.38 FHB HVAC* * * * What will cause a FHB HVAC Emergency Operating Actuation Signal?
**SI** * *High Radiation (5x10-4 µCi/cc)** * RT-8035 _OR_ RT-8036* * * * High Radiation Signal will drop out after 100 sec (Regardless if High Rad clear) to allow reset on CP-022.
37
* LOT 201.14 PZR Pressure & Level* * * * While operating in MODE 1, what is your PZR Pressure DNB limit?
**2200 psig** ## Footnote * * * LCO 3.2.5 DNB Parameters Applicable: MODE 1
38
* LOT 201.10 ECCS* * * * In order for the RWST to be OPERABLE in MODES 1 - 4, what must water volume and boron concentration be?
**≥ 458,000 gallons** **2800 ppm - 3000 ppm** * * * LCO 3.5.5 RWST Applicable: MODES 1 - 4
39
* LOT 201.09 RHR* * * * When is RHR placed in service?
**≤ 350 ˚F** * *≤ 332 psig** * Interlock to open MOV-060/MOV-061* * * * No auto close features for MOV-060/MOV-061.
40
* LOT 201.14 PZR Pressure & Level* * * * At what PZR level will the heaters trip off?
* *17% [1/2]** * LT-465/467 _OR_ LT-466/467* ## Footnote * * * Backup heaters will turn back on if in auto once PZR LVL \> 17%. [2/2] * * * * Note:* * For LOOP / SI, B/U heaters control switch must be cycled to turn back on.*
41
* LOT 201.10 ECCS* * * * At what RCS pressures will the ECCS Accumulators, HHSI pumps, and LHSI pumps inject into the RCS Cold Legs?
* _HHSI:_* * *\< 1600 psig** * _Accumulators:_* * *590 - 670 psig** * _LHSI:_* * *\< 300 psig** * * * Receive water from RWST. * * * * Note:* * During DBA, Accumulators will inject 1st.*
42
* LOT 201.07 Rx Makeup System* * * * What powers the RMW pumps, BAT pumps, and CCPs?
* _RMW Pump A:_* * *MCC E1C2** * _RMW Pump B:_* * *MCC E1B4** * _BAT Pump A:_* * *MCC E1C4** * _BAT Pump B:_* * *MCC E1A4** * _CCP A:_* * *E1C** * _CCP B:_* * *E1A** * * * C-B-C-A-C-A (2444)
43
* LOT 201.18 Rod Control* * * * What is the purpose of using bank overlap?
**Gives more uniform reactivity rate** * * * * Used for the control banks _ONLY_. * S/D banks not overlapped b/c they will not be used while critical. * * * * Note:* * The bank selector switch must be in Auto or manual to maintain bank overlaps during rod movement.*
44
* LOT 201.13 ECW* * * * What will auto start/stop the ECW traveling screens?
* _Auto Start:_* * *SI** * *High Screen D/P (5.5") w/ Screen Wash Pressure ≥ 63 psig** * Resets at 4.5" (Will run for 4 mins after reset)* * _Auto Stop:_* * *Sreen Wash Pressure \< 63 psig** * N/A for SI* * *∆Level \< Setpoint**
45
* LOT 201.14 PZR Pressure & Level* * * * What is the PZR Program Level for 0% RTP and 100% RTP?
* _0% RTP (567 ˚F):_* * *25%** * _100% RTP (593 ˚F):_* * *57%** * * * At actual 100% RTP (592 ˚F) PZR Level will be 55.7%.
46
* LOT 201.09 RHR* * * * Which pressure transmitters provide the open permissive for the RHR Suction Valves? (MOV-060/MOV-061)
* _RHR Train "A":_* * *MOV-060A: PT-405** * *MOV-061A: PT-406** * _RHR Train "B":_* * *MOV-060B: PT-406** * *MOV-061B: PT-407** * _RHR Train "C":_* * *MOV-060C: PT-407** * *MOV-061C: PT-405** * * * Power Supplies: * PT-405: Train "A" * PT-406: Train "B" * PT-407: Train "C"
47
* LOT 201.12 CCW* * * * What systems operate at a higher pressure than CCW?
* *RHR HX** * *RCP Thermal Barrier** * *Letdown HX** * *Excess Letdown HX** * *RCDT HX** * *Primary Sample Coolers** * *SFP HX**
48
* LOT 201.27 Containment Combustible Gas* * * * What are the sample points for the H2 monitors?
**Top of Containment Dome** **Above S/Gs (S/G C/D)** **Inside S/G Compartment (S/G C/D)** **Inside Primary Shield (S/G A/B)** * * * Controlled from CP002 * * * * Note:* * H2 monitor "B" penetrations used by PASS*
49
* LOT 201.10 ECCS* * * * In order for the accumulators to be OPERABLE in MODES 1 - 3 w/ PZR pressure \> 1000 psig, what must water volume and boron concentration be?
* _Water Volume:_* * *8800 gal - 9100 gal** * _Boron Concentration:_* * *2700 ppm - 3000 ppm** * * * LCO 3.5.1 Accumulators Applicable: MODES 1 - 3
50
* LOT 201.07 Rx Makeup System* * * * What are the different ways an operator can inject boron into the RCS?
* _BAT:_* * *Charging Line** * Normal / Alt. Immediate: Flow limited by FCV-0110A (0-100 gpm)* * Emergency: BAT pump flowrate (125 gpm)* * *RCP Seal Injection** * 5 gal/min per pump* * *Gravity Feed** * CV-0333 / CV-0226* * _RWST:_* * *Charging Line** * MOV-112C / MOV-113B* * _BTRS:_* * *Demins** * * * The emergency boration path through the charging line, the gravity feed path, and the RWST path are all considered "Emergency Boration." * * * * Note:* * VCT Level - Low 2 (3%) will close MOV-112B/MOV-113A and prevent normal boration.*
51
* LOT 201.07 Rx Makeup System* * * * What will auto start/ stop the BAT pumps?
* _Auto Start:_* * *VCT Level (28%)** * 200 gpm blend flow (RMWST/BAT)* * *Manual / Borate Initiated** * Manual: 200 gpm blend flow (RMWST/BAT)* * Borate: Flowrate (User Defined 0-100 gpm)* * _Auto Stop:_* * *VCT Level (48%)** * _Trip:_* * *Overload** * * * Can be controlled from ASP. * * * * Note:* * Unlike RMW pumps that trip on low level, the BAT pumps have no low level trip.*
52
* LOT 201.12 CCW* * * * What CCW loads isolate when the CCW Surge tank reaches 64.6%? (1st Low Level Isolation)
* _HXs:_* * *Letdown HX** * *Excess Letdown HX** * *RCDT HX** * _Evaporators:_* * *Boron Recycle Evaporator** * *LWPS Evaporator** * _Sample Coolers:_* * *Boric Acid Sample Cooler** * *Primary Sample Coolers** * _Radiation Monitors:_* * *S/G Blowdown Rad Monitor** * *BRS Rad Monitor**
53
* LOT 202.37 EAB/CR HVAC* * * * What is the required D/P across the CR HVAC Makeup and Cleanup filters?
* _Cleanup:_* * *\< 6.0" H2O** * _Makeup:_* * *\< 6.1" H2O** * * * *Note: Located on CP022*
54
* LOT 202.37 EAB/CR HVAC* * * * What is the CR HVAC system response following an SI or High Rad?
* *Makeup Supply Damper Opens** * *Makeup Fan Starts** * *Makeup Discharge Damper Modulates to maintain 1000 cfm** * FCV-9584/9585/9586* * *Cleanup Fan Starts** * *Supply Fan Starts​** * *Return Fan Starts** * *Return Damper Opens** * FV-9675/9676/9677* * *Kitchen / Toilet exhaust fan Stops** * * * For an SI: * EAB AHUs Start * Battery Room Exhaust Fan Starts * MAB HVAC Emergency AHU Starts * * * * Note:* * Can be done manually on CP022*
55
* LOT 202.37 EAB/CR HVAC* * * * How much air flow is present in the following sections of the CR HVAC system? * Supply Fan Discharge * Recirculation Flow * Cleanup Flow * Makeup Flow
* _Supply Fan Discharge:_* * *17400 cfm** * _Recirculation Flow:_* * *16400 cfm** * _Cleanup Flow:_* * *6000 cfm** * 1000 cfm (Fan) + 5000 cfm (Recirc Flow)* * _Makeup Flow:_* * *1000 cfm** * Maintained by discharge damper*
56
* LOT 201.07 Rx Makeup System* * * * What will auto start/stop the RMW pumps?
*_Auto Start:_* **VCT Level (28%)** *200 gpm blend flow (RMWST/BAT)* **Manual / Dilute / Alt Dilute Initiated** *Manual: 200 gpm blend flow (RMWST/BAT) Dilute / Alt Dilute: Flowrate (User Defined 0-300 gpm)* * _Trip:_* * *RMWST Level (5.6%)** * * * Makeup will secure at VCT Level (48%) but operator must secure RMW pump.
57
* LOT 201.10 ECCS* * * * When must all HHSI pumps be inoperable per tech specs?
* *MODE 5** * *MODE 6 w/ Rx Vessel Head on** ## Footnote * * * LCO 3.5.3.2 ECCS Subsytems - Tavg ≤ 200 ˚F
58
* LOT 202.38 FHB HVAC* * * * What will happen on a FHB HVAC Emergency Operating Actuation Signal?
* _Opens:_* * *Relief Supply Dampers (D-001/D-037)** * Relief Damper off closed seat → Main Supply Fans to Trip → D/P Damper (D-138) to Close* * *Exhaust Filter Inlet Dampers (D-033/D-034)** * *Exhaust Filter Outlet Dampers [Modulates] (D-146/D-147)** * _Shuts:_* * *Bypass Line Dampers (D-036/D-162)** * _Starts:_* * *ALL (3) Main Exhaust Fans** * *ALL (3) Exhaust Booster Fans**
59
* LOT 201.13 ECW* * * * What loads does ECW supply?
**Essential Chillers​** * _ESF DGs:_* * *Jacket Water HX** * *Turbo Charger Combustion Air Cooler** * *Lube Oil HX** * _CCW:_* * *CCW HX** * *CCW Pump Supplementary Cooler** * Cools area cooler and CCW pump motor*
60
* LOT 201.18 Rod Control* * * * What is the RDMG's output voltage and frequency?
**260 VAC** **59 Hz** * * * Prevents alternate power supply connection * * * * Note:* * Control switches to operate RDMGs are on local control panel only.*
61
* LOT 201.18 Rod Control* * * * When performing a Rx startup, how many steps until bank overlaps begin?
**137 steps** * * * * Control Bank A at 137 steps, Control Bank B will begin to lift. * Process repeated for control bank C and control bank D.
62
* LOT 201.14 PZR Pressure & Level* * * * How many RCPs are required for PZR Spray?
* *RCP 1A ONLY** * *_OR_** * *RCP 1D ONLY** * *_OR_** * *RCPs 1B _AND_ 1C**
63
* LOT 201.14 PZR Pressure & Level* * * * When is COMS required to be armed?
**≤ 350 ˚F** * * * * PCV-655A (Auct Low WR TH / PT-403) * PCV-656A (Auct Low WR TC / PT-404) * * * COMS controller completely independent of master pressure controller. * * * * Note:* * Manually armed on CP004*
64
* LOT 201.10 ECCS* * * * What will auto open the accumulator discharge valve? (MOV-039)
**SI** * *RCS Pressure ≥ P-11** * PZR Pressure ≥ 1985 psig [2/3]*
65
* LOT 203.11 LWPS* * * * For an unprotected outdoor tank, what is activity limited to? (LCO 3.11.1 Liquid Holdup Tanks)
* *≤ 10 Curies** * Excludes Tritium and entrained Noble Gases* ## Footnote * * * LCO N/A to WMT D/E/F b/c they have a berm. Used for temporary tanks.
66
* LOT 201.13 ECW* * * * Describe what happens to the ECW blowdown valves when a SI occurs?
* *Blowdown valves shut** * Once SI clears, must take valves to shut then back to auto on CP002* * * * CP002 switch in AUTO: * ECW Train 2A: Valve opens * ALL other ECW Trains: Cycles Open/Shut with ECW pump starting/securing Valve physically located on MAB 10' at ECW Sump. (No local switch) * * * *Note: By procedure, every blowdown valve with exception of train 2A is maintained in the CLOSE position on CP002*
67
* LOT 201.14 PZR Pressure & Level* * * * What PZR Level deviation will automatically turn on PZR B/U Heaters?
* *+ 5% Level Deviation** * Controlling Channel Level (LT-465/467) \> 5% above Program Level* * * * Done to preheat PZR insurge. * * * * Note:* * *Charging flow at +5% Level Deviation: 50 gpm* * *Charging flow at -5% Level Deviation: 300 gpm*
68
* LOT 201.13 ECW* * * * What provides makeup to the ECW pond?
* _Normal:_* * *Well Water** * _Alternate:_* * *Unit 2 ECW Sump via ECW 2A return line** * * * * Unit 1 Sump is normally aligned to Unit 1 CW Return. * Unit 2 Sump can be aligned to **Unit 1** CW Return. * * * * Note:* * ECW Sump located on MAB 10' in Essential Chiller Train C Room.*
69
* LOT 201.18 Rod Control* * * * What is the rod speed for each control rod during auto and manual control?
*_Control Banks:_* * *_Terror 1.5 ˚F - 3 ˚F:_** * *6 steps/min** * *_Terror 3 ˚F - 5 ˚F:_** * *Linear slope (6 - 72 steps/min)** * *_Terror ≥ 5 ˚F:_** * *72 steps/min** * *_Manual:_** * *68.5 steps/min** * * * * _S/D Banks:_* * *68.5 steps/min** * * * * + Terror results in outward rod movement * - Terrror results in inward rod movement * * * * Note:* * Once ± 1.5 Terror reached rods with continue to shim until ± 1 Terror reached.*
70
* LOT 201.12 CCW* * * * What is the temperature band CCW operates in during normal operations?
* *60 ˚F - 105 ˚F** * MAX DBA: 122.3 ˚F* * * * 60 ˚F Basis: * Prevents condensate in Lube Oil Coolers * Prevents thermal shock to RCP thermal barrier * * * * Note:* * During C/D CCW Temp may reach 120 ˚F for 4 hrs (RHR cooling req.)*
71
* LOT 201.07 Rx Makeup System* * * * What is the usable volume and the boric acid concentration of the BATs?
* _Usable Volume:_* * *33,500 gal/tank** * 2 tanks* * _Boron Concentration:_* * *7000 - 7700 ppm** * * * MODES 1 - 6: * ≥ 27,000 gal (MODES 1 - 4) * ≥ 3,200 gal (MODES 5 - 6) * ≥ 7000 ppm * ≥ 65 ˚F CP004: * Level and temperature indication
72
* LOT 201.14 PZR Pressure & Level* * * * At what pressure will the PZR PORV auto open signal blocked?
**2185 psig** * * * * PCV-655A (PT-458) * PCV-656A (PT-457) * * * Tailpipe temperature for PORVs and Safeties on CP004. (PORV: TI-676 / Safeties: TI-677 - 679)
73
* LOT 201.14 PZR Pressure & Level* * * * What controls the opening of the PORVS? (PCV-655A / PCV-656A)
* _PCV-655A:_* * *Master Pressure Controller** * 87.5% (≈ 2335 psig)* * _PCV-656A:_* * *Backup PZR Pressure Channel** * 2335 psig* * * * * Note:* * *Only odd numbered channels can be selected as the “controlling channel” to input to the master pressure controller. (455/457)* * *Only even numbered channels can be selected for backup control, and they only input to PCV-656A (456/458)* * *Switch on CP004*
74
* LOT 202.38 FHB HVAC* * * * What will happen to the FHB HVAC system during a LOOP?
* _Open:_* * *Supply Fan Inlet Dampers (D-002/D-003/D-004)** * _Shut:_* * *Exhaust Filter Outlet Dampers (D-146/D-147)** * _Trip:_* * *Supply Fans** * *Exhaust Booster Fans** * _Starts:_* * *All (3) Exhaust Fans** * Locks in start signal to re-start fans when power returns* * * * Supply fans will not start on exhaust fan start b/c power will strip and not return. **_Operator must open a relief damper (D-001/D-037)_**
75
* LOT 201.18 Rod Control* * * * How many control rods are in each bank?
* _Control Banks_* * *A: 8 (4/4)** * *B: 8 (4/4)** * *C: 8 (4/4)** * *D: 5 (2/3)** * _S/D Banks:_* * *A: 7 (4/3)** * Unit 2: 8 (4/4)* * *B: 8 (4/4)** * *C: 4** * *D: 4** * *E: 4** * * * Rod D-6 in SD Bank A Group 2 was removed for Unit 1
76
* LOT 201.10 ECCS* * * * How do you place ECCS in-service during a plant heatup from cold shutdown?
* _Mode 5:_* * *_ALL_ HHSI pumps inoperable** * *SI not blocked** * _Before Entering MODE 4:_* * *Open ALL HHSI CL injection valves** * *2 trains of LHSI OPERABLE** * _Within 4 hrs of going \> 200 ˚F and before exceeding 225 ˚F:_* * *1 HHSI OPERABLE and 1 HHSI in Standby** * _Before Entering MODE 3 (350 ˚F):_* * *_ALL_ LHSI OPERABLE** * _Within 4 hrs of going \> 350 ˚F and before exceeding 375 ˚F:_* * *_ALL_ HHSI OPERABLE** * _900 psig - 1000 psig:_* * *_ALL_ Acummulators OPERABLE**
77
* LOT 201.10 ECCS* * * * Which valves will not be able to be manually opened if the respective train's Emergency Sump Outlet Valve (MOV-016) is open?
**HHSI Mini-Flow Valves (MOV-011/MOV-012)** **LHSI Mini-Flow Valves (MOV-013/MOV-014)** **RWST Outlet Valves (MOV-001)** * * * To manually open Emergency Sump Outlet Valve: * RWST Outlet Valve closed (Manual Only) * HHSI Mini-Flow Valve closed [1/2] * LHSI Mini-Flow Valve closed [1/2]
78
* LOT 201.07 Rx Makeup System* * * * How do you calculate the boron blender potentiometer setting?
*_FK-0110 Setpoint_* **20 x Boron Concentration of RCS/Boric Concentration of BAT** * * * Controller set up for 0-10 setting. Correlates to 0-100 gpm. (5 setting is 50 gpm)
79
* LOT 201.18 Rod Control* * * * What causes a rod control logic cabinet urgent failure?
* *Pulser Failure** * *Slave Cycle Input Failure** * Slave receive "Go" signal before last step done* * *Loose circuit card** * * * * Stops Auto/Manual rod motion * Individual Bank rod motion will still work * Sends reduced current signal to affected group movable/stationary grippers * * * * Note:* * Non-Urgent is a loss of 1 of the 6 power supplies and will not affect system operation.*
80
* LOT 201.07 Rx Makeup System* * * * What plant conditions require emergency boration?
**Loss of SDM** **Reactivity excursion that normal means cannot handle** **CRDM below insertion limits** **\> 1 Control Rod not inserting on Rx Trip** **Loss of DRPI after Rx Trip** **ATWAS** **QDPS S/D Monitor Alarm**
81
* LOT 202.37 EAB/CR HVAC* * * * What is the CR HVAC system response for a LOOP on Train C?
* *Makeup Supply Damper Opens** * *Supply Fan Starts** * *Return Fan Starts** * *Cleanup Fan Starts** * *Return Damper Opens** * FV-9677* ## Footnote * * * Kitchen/Toilet Exhaust fan stays running because dampers powered by A/B. * * * * Note:* * LOOP on A/B looks the same except Kitchen/Toilet fan secures b/c fan inlet dampers shut.*
82
* LOT 201.13 ECW* * * * What will auto start the screen wash booster pump?
* _Auto Start:_* * *SI** * *Traveling Screens Start** ## Footnote * * * Must be manually secured. MCC switch in LOCAL eliminates _ALL_ Auto Functions. * * * * Note:* * Starting screen wash booster pump will auto open screen wash valve unless MCR switch in close.*
83
* LOT 201.09 RHR* * * * Where in the CVCS does RHR enter and exit?
* _Supply:_* * *Downstream of Regen HX (IRC)** * RHR Train "A" _AND_ Train "B"* * _Return:_* * *Upstream of VCT** * RHR Train "A" ONLY* * * * Low Pressure Letdown: * All letdown orifices open * RHR pump not required to be running * PCV-135 able to maintain ≈ 380 psig
84
* LOT 201.07 Rx Makeup System* * * * What will auto close the boric acid purification loop isolation valves? (FV-8400A/B)
**BAT Tank Level - Low (29,584 gal) [1/1 on 1/2]** ## Footnote * * * Level Recorder located on CP018. Control switches for FV-8400A/B located on CP004. * * * * Note:* * This is the only BAT tank level actuation. The BAT pumps will _NOT_ trip on a low level actuation.*
85
* LOT 201.14 PZR Pressure & Level* * * * Which PZR Pressure instrument does not tie into P-11?
**PT-458** ## Footnote * * * P-11: PZR Pressure ≥ 1985 psig [2/3]
86
* LOT 201.07 Rx Makeup System* * * * What are the Boration thumb rules?
**DBW = 10 pcm/ppm** **10 gals of boron/ppm**
87
* LOT 201.14 PZR Pressure & Level* * * * At what pressure will the PORV (PCV-656A) lift when COMS is armed?
* _70 - 200 ˚F:_* * *475 psig** * _220 - 380 ˚F:_* * *660 psig** * * * Uses Auct Low WR TC / PT-404 * * * * Note:* * Normal PORV setpoint is 2335 psig. (B/U pressure channel)*
88
* LOT 201.10 ECCS* * * * When does the accumulator relief lift?
**700 psig** * * * Relieves to Containment Atmosphere * * * * HHSI Discharge Relief (1750 psig) → PRT * LHSI Discharge Relief (600 psig) → PRT