Your water supplier may interrupt water service to a customer when

A

Provisions in the cross connection, control, ordinance, or regulations are not met

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Backflow in a public water supply can be caused by

A

back pressure or backsiphonage

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

An atmospheric vacuum breaker may have a downstream shut off valve

A

Under no circumstances

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

The 1996 Federal safe drinking water act places, a primary responsibility for the quality of the public water supply on which of the following

A

Water purveyor

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

An airgap must have

A

Two times the pipe diameter with the minimum of 1 inch separation

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

An unprotected bypass around a reduced pressure principle backflow prevention assembly is

A

Not permissible

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

The major concern of the water purveyor where an auxiliary water supply is utilized or maintained is to ensure that

A

Backflow protection is provided at the water service connection

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

A pressure vacuum breaker may be installed with a

A

Shut off valve downstream

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Two types of cross connections are

A

Direct and indirect

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

When nontoxic antifreeze chemicals are added to a fire suppression system, which of the following is required to protect the potable water supply

A

Reduced pressure principle backflow prevention assembly

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Internal protection refers to

A

Backflow protection at each point of use

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Lye is back siphoned from an open vat, without a cover over the top by a direct cross connection this constitutes a

A

Health hazard

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

In responding to a suspected backflow incident, the water purveyor should

A

Implement emergency response plan

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

The loading of the first and second check valves and reduced pressure principle backflow prevention assemblies are always

A

Different

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

Undersized water, service, and distribution piping carrying water at high velocity

A

May cause back siphonage due to aspirator effect

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

A perfect vacuum at sea level will raise water in a pipe a maximum of

A

33.9 feet

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
17
Q

The water supplier may require more frequent field testing of backflow prevention assemblies due to

A

High incident of field test failures of the assembly

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
18
Q

A differential pressure gauge is used to field test

A

Reduced pressure principle backflow assemblies

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
19
Q

The relief valve opening point of a reduced pressure principle backflow prevention assembly must open at or above

A

2.0 PSID

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
20
Q

When field testing a reduced pressure principle backflow prevention assembly, the number two testcock should be flushed

A

With caution to prevent premature opening of relief valve

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
21
Q

During a field test, the air inlet valve on a pressure vacuum breaker must open at or

A

Above 1.0 PSID

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
22
Q

Hose bib vacuum breakers should be located

A

On hose bibs as required by code

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
23
Q

The probable cause of an intermittent discharge of the relief valve on a reduced pressure principle backflow prevention assembly is

A

Fluctuations and supply line pressure

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
24
Q

When entering a vault containing a backflow prevention assembly does tester should

A

Check quality of the atmosphere prior to entry

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
25
A service or containment protection, backflow prevention assembly is meant to protect
Public water supply system
26
A vacuum breaker is used to protect against
Back siphonage
27
A tester required to report backflow prevention field test information to the
Administrative authority
28
Backflow prevention assembly shall be field tested
When required by local administrative authority
29
Backflow prevention assemblies should be repaired
When field test results indicate failure
30
Check valves of double check valve backflow prevention assemblies must be
Internally loaded
31
A vacuum relief valve should be installed
Never as a backflow prevention assembly
32
When repairing double check valve assemblies the tester should not
Modify internal components
33
A backflow prevention assembly should make an abnormal humming noise during operation under which of the following conditions
Never
34
The accuracy of fuel test gauges should be checked
At least annually
35
The air gap drain funnel for the relief valve of a reduced pressure principle backflow prevention assembly
May not be sufficient to handle the full relief valve discharge
36
How many tests are there on a pressure vacuum breaker
Two
37
An atmospheric vacuum breaker must be installed
6 inches above highest outlet and all downstream piping
38
A double check valve assembly is field tested with a
Differential gauge
39
The type of backflows are
Back pressure and back siphonage conditions
40
A Watermain break will most likely cause what condition
Back siphonage
41
A reduced pressure principle backflow prevention assembly shall be installed
Readily accessible above grade
42
Which component of a pressure vacuum breaker must be field tested first
Air inlet valve
43
Each of the check valves in a double check valve assembly is designed to hold in the direction of flow a minimum static pressure of
1.0 psi
44
An absolute pressure of 25 PSIA at sea level is equal to approximately what value engage pressure PSIG
10 PSIG
45
Results of a field test on a backflow prevention assembly should not include, which of the following information on the report form
Date of manufacture
46
To properly field test, a reduced pressure principle backflow prevention assembly
The inlet shut off valve must be open
47
A pressure vacuum breaker may be used for backflow protection for which of the following conditions
Back siphonage health hazards
48
The relief valve of reduced pressure principle backflow prevention assembly discharges in a static, no flow condition and stops discharging during the flow condition. The most likely cause is.
Fouled check valve number one
49
A 2 inch atmospheric vacuum breaker when used on irrigation systems shall be installed at least _______ inches above the downstream piping outlets
Six
50
When field testing a double check valve assembly and check valve number one leaks the tester
May test check valve number two before repairing check valve number one
51
A backflow prevention assembly consisting of two independently operating internally loaded check valves located between two tightly closed shut off valves with four approximately located test cocks is a
Double check valve assembly
52
A reduced pressure principle backflow prevention assembly must be installed at least
12 inches above grade
53
Edible syrup in a cannery was forced into a drinking water line through a direct cross connection. This could’ve been prevented by the installation of a.
Double check valve assembly
54
To properly solve a cross connection, contamination incident a qualified person should
Identify an isolate, the source of contamination, the affected area, and notify customers and the health department and take water samples
55
To convert feet of head to pounds per square inch multiply by
0.4333
56
The physical operation of a hose bib vacuum breaker is classified as a type of
Atmospheric vacuum breaker
57
A contaminated auxiliary water supply is utilized to maintain high pressure of a fire sprinkler system to protect the potable water supply. What protection should be installed at the service connection.
Reduced pressure principle backflow prevention assembly
58
When restoring service to the customer after testing a double check valve assembly the shut off valves are opened
Slowly number one shut off valve first
59
It is possible to compensate for a leaking number to shut off valve during the field test of a reduced pressure principle backflow prevention assembly by attaching a temporary bypass hose from
Number one test cock, to number four test cock
60
When field testing a pressure vacuum breaker near a ceiling, the gauge should
Be placed at the same elevation as the assembly
61
Which of the following could create a closed water system if installed in the service supply line
Backflow prevention assembly
62
A total cross connection control program should be coordinated with
Plumbing inspector, local health department, water purveyor
63
The temperature increases in a closed plumbing system. This is an example of.
Thermal expansion
64
The maximum head loss across a double check valve from zero to rated flow is
10.0 psi
65
Which of the following conditions would not be a hazard to a public water supply?
A reduced pressure principle backflow prevention assembly installed on a cooling tower feed line that is tested twice a year
66
During the held test of a leaking check valve number two on a reduced pressure principle backflow prevention assembly pressure is bypassed through the gauge from test cock number two to test cock number four this procedure will
Cause the differential pressure reading to drop and cause the relief valve to open
67
During the field test of a check valve in a pressure vacuum breaker, the high bleed needle valve is left open this procedure will
Reduce the pressure between the check valve and the number one shut off valve
68
When field testing a double check valve assembly check valve number one is found to be leaking. The next step is to.
Test check valve number two
69
The differential pressure gauges used for field testing backflow prevention assemblies read in minimum increments of
.1 PSID
70
After the installation of a reduced pressure principle backflow prevention assembly, the number one shut off valve is turned on to establish water pressure within the assembly. Upon opening the number one shut off valve. The relief valve discharge is continuously this discharge may be an indication of.
A foul check valve number one
71
The spring and the relief valve of a reduced pressure principle backflow prevention assembly is designed to
Open the relief valve
72
During the test of a check valve on a pressure vacuum breaker water continues to flow from the test cock number two. This is an indication of.
Leaky number one shut off valve
73
Any pressure less than that exerted by the atmosphere is defined as a
Vacuum
74
Performance design specifications of reduced principle backflow prevention assemblies, require that the differential pressure check valve number 1 be ______ PSID greater than the opening point of the relief valve
3.0
75
How many tests are required on a reduced pressure principle backflow prevention assembly
Four
76
The relief valve of a reduced pressure, principle backflow prevention assembly discharges, continuously during both flow and no flow conditions. The most probable cause is.
Foul relief valve
77
To exert a pressure of one PSI at the base of a column of water, the column would have to be
27.75 inches high
78