Test In Flashcards
(32 cards)
How would you set the regulator for paralleling inside the feed point ?
Set regulator to neutral and off control.
In the first step of returning a voltage regulator to service, what is the position of the Power and Control switches?
Off
When bypassing a control regulator, the control is set to ______ and off control.
Neutral
What does it means when voltage regulators is set to Buck?
The voltage regulator provides a step down in voltage
The system is 6930/12000 WYE 4-wire and the transformer 12000 GRD WYE/6930. How would this transformer be connected?
Phase to Neutral
The system is 2400/4160 WYE 4-wire. The transformer is 2400/4160 WYE. How is the primary connected?
WYE
A customer wants 120/208 volts , three-face, four-wire service. The overhead transformers are 120/240 volts. What bushing would be the common?
X2
A customer wants 120/208 volts, three-face, four-wire service. Transformer are 120/240 volts. What is the secondary connection?
WYE
To build a WYE, we wire the three windings together by ______ of the connections.
Matching the polarity.
Which of the following rotations is the standard SCE face sequence?
BAC, CBA
A vector is define as a means of expressing the _______ and the _______ of a quantity.
Magnitude , Angle.
What are the three reasons that could cause an Automatic Recloser (AR) to open a ground relay target?
Select the three that apply.
•Bypass around AR
•Paralleling with another circuit
•Ground fault
Which of the following statements best describes how RARs operate during Red flag warning situations
RARs are Blocked to prevent reclosing in SOB 322 areas.
The function of the ground relay is to determine the circuit’s
Escaping current
What are the three primary reasons Edison installs Automatic Reclosers (AR’s)?
•sectionalizing
•protection
•changing mode operation
What is the primary function of a midpoint controlled switch?
To aid in sectionalizing the total circuit load to about 50%
What components are required for each PE gear installation?
Select the three that applied
•Control mechanism
•Voltage sensing units
•Transfer mechanism
An AC circuit has 120 volts and 10 ohms of impedance. What is the current on the circuit?
12 Amps
A circuit has 17KVA with a power factor of 82.3% what is the KVAR?
9.7 KVAR
Which of the following may occur if the secondary of a current transformer is opened while primary is in the current of the primary of the current transformer?
Select the two that applied
•High voltages across the opened secondary.
•Arcing could occur which could harm operator and cause equipment damage.
On a CT meter panel, solid color wires with the white stipe are used for what?
Current Input.
Which of the following transformers are needed for KWH meter to measure power?
Current and potential transformer
What is used to shunt the CT before removing the meter in a CT panel
Test Switches
What is the function of the Potential Transformer (PT)?
To provide a proportional output voltage for meter purposes