What are the three main insulation classes for dry type?
150 Celsius, 185 Celsius, 220 Celsius
What is the 150 C insulation class dry type made out of?
- Interlayer insulation may be mylar or nomex.
- Conductor insulation may be varnish
What is the 185 C insulation class dry type made out of?
-Interlayer insulation may be mylar or nomex
-Conductor insulation may be HPTZ
What is the 220 C insulation class dry type made out of?
-Interlayer insulation may be Nomex
-Conductor insulation may be HML or nomex
When does the equilibrium point occur in a transformer with a load?
When heat dissipated = the heat generated
If the temp is above the equilibrium point, will the insulation start degrading?
Yes or No?
Yes
Every 10 Celsius over, the temperature rating will be reduced by___?
1/2
What is the average winding rise?
80 Celsius, 115 Celsius, 150 Celsius.
What is the standard hotspot rise?
30 Celsius
What is the average ambient temp over 24 hours? What is the maximum?
30 Celsius, 40 Celsius
What is the insulation class of most dry types above 5kVa?
220 Celsius
Advantages of 80 Celsius Average Winding Temp Rise?
- More capacity
- Lower Losses
- Increases the trx efficiency
Disadvantages of 80 Celsius Average Winding Temp Rise?
-Higher Cost
-Uses larger conductors
- Larger physical size of trx
Advantages of 150 Celsius Average Winding Temp Rise?
- Uses smaller conductors
- Lower Cost
- Smaller physical size of trx
Disadvantages of 150 Celsius Average Winding Temp Rise?
- No increased capacity
- Higher losses
- Decreases the trx effiency
What is the insulation class of an Oil Filled trx?
120
What makes up the insulation class of an Oil Filled trx (Temps wise)?
65 Celsius average winding temp rise
15 Celsius hot spot rise
40 Celsius maximum ambient
When is no load loss present?
It is always present as long as voltage is applied to the primary
When is load loss present?
- Only when load is connect
- As long as current flows to the load
What are other words for Load Loss?
Winding losses or copper (aluminum) losses
Where does load loss come from?
I^2R and Eddies in both HV and LV windings
+
Stray losses which are due to the stray fluxes in structural steel parts
Load losses are specified at rated current and corrected to a temperature.
True or false?
True
No load losses are specified at rated current only, temperature is negligible.
True or false?
False
No load losses are specified at rated voltage only, temperature is negligable.
What does resistance depend on (one word answer) ?
Material