V7-1-8 Flashcards

(49 cards)

0
Q

Three or more dwelling units attached

A

Multiple family dwellings

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
1
Q

Single detached dwelling units on land owned in common

A

Detached condominiums

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Reviews building plans and applies fire flow and hydrant spacing requirements according to this regulation

A

Fire prevention engineering section

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

SFD & DC’s 1-4 units <5000 sq. ft.

Fire flow_____
Duration_____
Hydrant Spacing_____

A

Fire flow- 1250gpm
Duration- 2 hrs
Spacing- 600’

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

DC’s 5+ units <5000 sq ft

Fire flow—–
Duration—–
Hydrant spacing——

A

FF- 1500gpm
D- 2hrs
HS- 300’

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Duplexes

Fire flow—–
Duration——
Hydrant Spacing——

A

FF- 1500gpm
D- 2 hrs
HS- 600’

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Due to undetermined building designs for new land development projects (undeveloped land) the required fire flow Shall be:

FF—–
D——
HS—-

A

FF- 5000gpm
D- 5 hours
HS- 300’

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Fire flows proceeding are measured at_________

A

20 psi RESIDUAL psi

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Single family dwelling < 5000 sq ft

On lot 1 acre or > _________

On lot < 1 acre ___________

FF, D, HS?

A

1 acre or >
FF- 1000gpm
D- 2 hrs
HS- 600’

< 1 acre
FF 1250, rest same as above

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Mobile Home Park

Fire flow —–
Duration——
Hydrant Spacing—–

A

FF-1250gpm
D- 2 hrs
HS- 600’

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Conditions requiring additional fire flow

Each story above ground level add _____ per story

A

500gpm

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Conditions requiring additional fire flow

Any exposure within 50 feet add a total of______

A

500gpm

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Any high-rise building as determined by jurisdictional building code the fire flow Shall be minimum of

A

3500gpm for 3 hrs at 20psi

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Any flow may be increased up to 1000 GPM for a _________

A

Hazardous occupancy

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Fire hydrants shall be required at ________ and along ________ as requirements dictate

A

Intersections

Access ways

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

When a cul-de-sac depth exceeds _______ residential or _____ commercial, hydrant shall be required at mid block. Additional hydrants required if Hydrant spacing exceeds specified distances

A

450’ res.

200’ comm.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

Urban properties greater than 1 acre

No portion of lot frontage should be more than _____ via vehicular access from public hydrant

A

450’

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
17
Q

Non-urban properties less than 1 acre
No portion of a structure should be placed on a lot where it exceeds ______via vehicular access from a properly spaced public hydrant that meets the required fire flow

A

750’

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
18
Q

ALL OCCUPANCIES, other than SFD’s such as commercial, industrial, multifamily dwellings, private schools, institutions, detached condominiums (5 or more units) etc.
Fire hydrant spacing Shall be:

A

300’

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
19
Q

ALL OCCUPANCIES, other than SFD’s such as commercial, industrial, multifamily dwellings, private schools, institutions, detached condominiums (5 or more units) etc.
No portion of lot frontage shall be more than _____via vehicular access from the public hydrant

20
Q

ALL OCCUPANCIES, other than SFD’s such as commercial, industrial, multifamily dwellings, private schools, institutions, detached condominiums (5 or more units) etc.
No portion of a building should exceed _____via vehicular access from a properly spaced hydrant

21
Q

Hydrants Shall be required on both sides of the street whenever:

A

Streets having raised median center dividers which make access to hydrants difficult, causes time delay, and/or creates undue hazard

22
Q

Other situations that may require hydrants on both sides of the street

A

Excessive traffic loads
Lack of adjacent parallel public streets
Possibility of future development
Accessibility of existing hydrants

23
Q

Spacing distance between on-site hydrants Shall be _____ commercial to _____residential. Design features shall assist in allowing distance modifications

A

300’

600’

24
Only _______ qualify for Max spacing of 600 feet
Sprinklered buildings
25
For non-sprinklered buildings consideration should be given to fire protection, access doors, outside storage, etc., shall be taken into consideration. Distance between Hydrants should not exceed _____
400'
26
All on-site hydrants shall flow a minimum of
1250gpm @20psi for 2 hrs
27
If more than one on site fire hydrant is required, the on-site fire flow Shall be at least________, flowing from _______ simultaneously
2500gpm @ 20psi 2 hydrants
28
All on-site hydrants shall be installed a minimum of ______from a structure or protected by a ________
25' 2 hour fire wall
29
All on-site hydrants Shall be equipped with a shut off (gate) valve which shall be located as follows: Minimum distance to hydrant______ Maximum distance from hydrant___
Min- 10' Max- 25'
30
All new on site hydrants and underground installations are subject to inspection of the following items by representative of the department
- Piping materials and the bracing in support thereof - hydrostatic test of 200 psi for two hours - adequate flushing of the installation - flow test to satisfy required fire flow - hydrants painted
31
On-site hydrants have a hydrostatic test of
200psi for 2 hours
32
On-site hydrants are painted with ______ and ________.
2 coats of red primer One coat of red paint
33
It's the responsibility of ______, the______, or the _____to maintain on-site hydrants
Property management company Homeowners association Property owner
34
No barricades, walls, fences, landscaping, etc., shall be installed or planted within _____ of a fire hydrant.
3 feet
35
Minimum acceptable flow from an existing public hydrant Shall be _____ unless required fire flow is less
1000gpm
36
If more than one hydrant is to be flowed in order to meet required fire flow, the following number of hydrants Shall be flowed: (in gpm)
1 hydrant= 1250gpm & below 2 hydrant= 1251-3500gpm simul. 3 hydrant= 3501-5000gpm simul.
37
Existing single outlet 2 1/2 inch hydrants Shall be upgraded to a ________hydrant when the required fire flow exceeds 1250 GPM
Double outlet 6"x4"x2 1/2"
38
An upgrade of the fire hydrant will not be required if the required fire flow is between the minimum requirement of ______up to and including ______, and the existing public water system will provide the required fire flow through an existing wharf fire hydrant
750gpm 1250gpm
39
All new required fire hydrant installation shall be approved _______
6"x4"x2 1/2" fire hydrants
40
Hydrants Shall be installed so that the centerline of the lowest outlet is between ___and ___ above finished grade
14" and 24"
41
Hydrants shall be installed so that the front of the riser is between _____ and _____ behind the curve face
12" & 24"
42
Double outlet hydrants shall be installed with outlet's facing the curbs and at a _____to the curb line.
45 degree angle
43
Fire hydrants shall be installed with ______ unobstructed clearance on all sides.
3'
44
When fire hydrants are installed they will have approved _______on them.
Plastic caps
45
Hydrants will be painted with two coats of _____ and one coat of ________ for public hydrants and one coat of ___ for on-site hydrants, with the exception of the stems and threads.
Red primer Traffic signal yellow Red
46
Underground shut off valves are to be located a minimum distance of ______ from the hydrant a maximum distance of ____ from the hydrant
10' to 25'
47
Locations for shut off valves can be less than 10 feet when the ________ is already installed and the minimum 10 foot distance cannot be satisfied
Water main
48
When sidewalks are contiguous with a curb and are 5 feet wide or less, hydrants placed immediately behind sidewalk. Under no circumstances shall hydrants be _____ from a curbline.
> 6 feet