Departmental training committee: all________ of the department
Assistant fire chief’s
Captains shall: if assigned to a fire station conduct a______ hour drill each shift and______ wet apparatus drills each month
TWO
TWO
Scope of training: there are five general areas of training which comprises the department training plan
1) chief/Company officer
2) tower/In-service
3) firestation
4) recruit
5) technical
Tower/In-service training is mandatory and each company shall drill as a unit at a departmental approved training site a minimum of_____hours per year______ three hour sessions (I SO requirement)
18
6
At least one safety drill shall be conducted each month and last a minimum of_____hour
1
_________ Shall maintain a stock of library material published by other organizations or agencies for distribution
Training services section
Arial supply line:___Inch hose with____ inch couplings. 100 foot length
3
2 1/2
Water shall be run through all hose once every____ unless the hose has been otherwise wet in-service
Three months
All rubber hose must be reloaded following the annual hose test and then__________ thereafter
Quarterly
_______ shall assign new hose numbers
The property inventory unit of the administrative bureau located at Pacoima warehouse
Hard suction hose shall be marked with the______ number, And engine______ number
Vehicle identification
Company
Standard loads of 4 inch hose and compliment for standard engine
800 load and 900, complement
Standard load of 2 1/2 inch hose and complement for a standard engine
800 and 900
Standard load of 1 3/4 inch hose and compliment for a standard engine
750 and 1000
Standard load of 2 1/2 inch hose and complement for a quint
400 and 600
The total length of any holes line in the test layout shall not exceed______
300 feet
When testing hose all personnel so clear the area at minimum distance of______ feet, other than those required to perform the remainder of the procedure. The pressure shall be increased slowly to the service test pressure and held within plus or minus_____ PSI
15 feet
5 PSI
Annual test pressure: The standard hose test pressure is_____ PSI for all hose except otherwise specified
300 psi
All bypass and soft suction and rubber nitrile hose shall be tested a_______
250 psi
All hard suction hose shall be tested at_____ PSI
100 psi
For 50’ sections,_____ is the minimum allowable length for use in the field
35 feet
For 100 foot sections_______ is the minimal allowable late for use in the field
70 feet
For 20 foot bypass and soft suctions______ feat is the minimum allowable length
12 feet
Whenever the hose length falls below the minimum allowable length, initiate a
Survey request form 41