A fire safety officer is a sworn member of this department. While on such duty, said member shall be in uniform and, In effect, be acting under the orders of the_________
Fire chief
The________ Will be the department limited access system coordinator and shall be responsible for Limited access key distribution and maintenance
Battalion fire chief-fire prevention division
All plans shall include a completed fire flow( FORM_____) obtained within one year of the submittal date and verified by a signature of an official of the water company or department fire prevention division
Form 196
An appointment shall be made a minimum of______ working days in advance with the appropriate fire prevention division regional office for all inspections and test
2
System piping shall be hydrostaticlly tested at_____ psi for two hours or at_______ PSI above the maximum system operating pressure, which ever is greater
200
50
Automatic sprinkler systems shall be supervised by a listed/Approved central, Proprietary, Or remote station, or a local alarm when approved by the chief, which will give an audible signal at the constantly attended location when the number of sprinklers is______ or more
100
Exception:_______ or more in group 1, Division 1.1 and 1.2 occupancies
20
Sprinkler plans shall be added scale no smaller than
1/8
All sprinkler systems and private hydrant systems shall be designed and installed in accordance with the California building and fire codes, and______
NFPA 13
Hydrostatic test(minimum 200 psi for two hours, Or at 50 PSI above the system operating pressure, Whichever is greater) shall be conducted on all systems, new upgrades, or partials which involved the installation of over______ sprinkler heads
20
The FDC shall be installed on the address side of the building within_______ feet(via vehicle access) of an accessible public fire hydrant
150 feet
The FTC shall be visible, accessible and installed with inlets no less than 24 inches and no more than_____ inches above the level of grade, With the FDC facing the street
42
FDC’s shall be located a minimum of________ feet from the structure. When that distance cannot be achieved, A minimum 2 hour fire resistive wall shall be provided with no openings in the wall,______ see in either direction of the FDC
25
25
Systems designed for a total combined water demand exceeding 2000 GPM shall be equipped with a single, Clappered body FDC having_______ 2 1/2 inlets siamese into a minimum______inch pipe with a______ inch check valve
6
6 inch
6 inch
In multi story/level buildings over three levels, the following devices shall be provided at each floor level in a rated shaft or stairway
1) indicating control files
2) waterflow detector with an alarm bell
3) drain valve
4) inspectors test valve with sight gauge
Sectional control valves shall be required for each combination of_____ sprinkler risers and or hydrants
5
Single-family dwellings and detached condos(1-4 units)
1250 GPM 2 Hours HYD spacing 600 feet
Detached condo (five or more units)
1500 GPM 2 hours Hyd spacing 300 feet
Two family dwellings(duplexes)
1500 GPM 2 hours Hyd spacing 600 feet
Multiple family dwellings, hotels, high-rise, commercial industrial
5000 GPM 2 hours Hyd spacing 300 feet
When a cul-de-sac depth exceeds_____ residential or_____ commercial, hydrants shall be required at mid block
450 feet
200 feet
Single-family dwellings-fire hydrant for the spacing of_____
600 feet
Single-family dwellings-urban properties(more than one unit per acre)
No portion of lot frontage should be more than_____ via vehicle or access from a public hydrant
450 feet
Non-urban properties(less than one unit per acre)
No portion of a structure should be placed on a lot where it exceeds______ via vehicle or access from a properly spaced public hydrant that meets the required fire flow
750 feet