Week 7 Flashcards

(51 cards)

1
Q

Hydrostatic test is?

A

200 psi/ 2hours

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Systems normally subject to system working pressure over 150 psi shall be tested at?

A

50 psi in excess of system pressure

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

How can you test if there is a major drop in temperature anticipated?

A

An interim air test is permitted at 40psi for 24h. The hydrostatic test is still required at a better time.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

When conducting a hydrostatic test where shall the test gauge be located?

A

Lowest elevation point because it’s under the most pressure

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Initial installation of an FDC test is conducted at?

A

200psi or 50 psi in excess of maximum static pressure.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Dry pipe and double interlock preaction systems must be tested with?

A

Air and water. 200 psi/ 2h water, 40 psi/ 24h air 1 1/2 psi allowable leakage

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

An audible alarm is required in?

A

5 minutes

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Main drain tests are to be performed?

A

Annually

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Where can a wet system be installed?

A

Sprinkler systems shall be wet systems unless areas are subject to freezing or other special conditions.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

State two advantages of a wet system?

A

Most reliable, cost effective, easy to maintain.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Where shall the inspectors test of a wet system be located?

A

Installed downstream of the water flow alarm, furthest point is preferred.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

State two items which must be present in all wet system valve rooms?

A

Lighted, and heated.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

What are two alarm devices that a wet system may contain?

A

Flow paddle switch, low pressure alarm switch ps120, alarm valve ps10

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

State how many sprinkler heads must operate in order to initiate an alarm?

A

Just one

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

Identify the amount of pitch required on the piping of a wet system.

A

Shall be permitted to be installed level

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

What device must be installed on an antifreeze system which is connected to a potable water supply to protect the water

A

Backflow prevention device

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
17
Q

State some possible areas that an antifreeze system would be installed to protect

A

Often used to protect smaller portions of a wet system from freezing.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
18
Q

State the maximum size of an antifreeze system?

A

40 gal

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
19
Q

State the device added to allow for expansion when a reduced pressure backflow preventer is installed.

A

Expansion chamber to compensate for thermal expansion.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
20
Q

State the minimum drop of an antifreeze loop when using a non potable water supply

A

5 ft

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
21
Q

State the purpose of the 1/32” hole in the check valve of the antifreeze loop

A

To allow for expansion

22
Q

State the frequency antifreeze solutions shall be tested

23
Q

Where are dry systems normally installed.

A

Areas subject to freezing.

24
Q

What’s the maximum number of gallons which may be trapped before a dry system auxiliary drain is installed?

25
What is the size of a light or ordinary wet system.
52,000 ft2
26
What clearance must a valve room have from all panels or system valves?
36”
27
Valve room enclosure must have drainage twice the size of the drain true / false
True
28
What size pressure gauge must be used?
Rated for twice rated pressure
29
Where must pressure gauges be installed?
Below alarm valve or riser check, Above Alarm valve or riser check valve
30
Where is a relief valve required in wet systems?
Downstream of any check valve
31
Minimum relief valve size?
1/2”
32
Where is an air vent required?
On all wet systems, installed at highest point.
33
Where is the main drain located?
Downstream of the control valve
34
5 - 50 gal of trapped water must have an auxiliary drain valve of what size
3/4
35
When’s are auxiliary drains tested
Annually, and quarterly to confirm and exercise internal components. Or whenever a control valve has been closed and re opened
36
What are two system audible alarms
Water motor gong, electric bell
37
When shall system alarms be tested
Inspect quarterly, test quarterly
38
Where do you test system alarms?
From the inspectors test connection
39
Anti freeze solutions?
Glycerin (plastic), and propylene glycol
40
How long shall an air compressor take to fill a system?
30 minutes, 60 minutes in a refrigerated space maintained below 5* F ( -15* C)
41
Air supply connections shall be sized at
Min 1/2” above priming level of the valve
42
What’s the drain size of an exhauster
2”
43
How soon shall water be at an ITV in a dwelling unit
15 seconds
44
Not greater than 500gal shall be permitted without a Q.O.D true/false
True
45
750gal or more shall have a Q.O.D true/ false
True
46
What is the pitch for areas subject to freezing?
1/2” per 10’ for branch lines and 1/4” for mains
47
What is the pitch required for refrigerated areas?
1/2” per 10’ for branch lines and mains
48
Where shall a dry pipe FDC be installed?
Between system control valve and the dry pipe valve
49
Describe two tail end systems which may be connected to a wet system
Antifreeze loop, pre action system, deluge system, dry system
50
State two antifreeze solutions permitted to be used with potable water supply
Glycerin, propylene glycol
51
State the type of control valve that must be used on a reduced pressure back flow preventer
Supervised, indicating control valve.