Wk 3 Flashcards

(50 cards)

1
Q

According to Book 57 (The 2020 Los Angeles Fire Code - Chapter 10
Section 1004.6) The occupant load of seating booths shall be based on
one person for each _ inches of booth seat length measured at the
backrest of the seating booth.

A

24”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

According to Book 57 (The 2020 Los Angeles Fire Code - Chapter 10
Section 1005.7.1) Doors. Door when fully opened shall not reduce the
required width by more than _ inches

A

7”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

According to Book 57 (The 2020 Los Angeles Fire Code - Chapter 10
Section Table 1006.2.1) Maximum Common Path of Egress Travel
Distance in a Educational (Group E) Occupancy is_ feet

A

75ft

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

According to Book 57 (The 2020 Los Angeles Fire Code- Chapter 10
Section 1006.2.1.1) Three or more exist access doorways. An occupant
load of 500 requires how many exit access doorways?

A

2

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q
  1. According to Book 57 (The 2020 Los Angeles Fire Code - Chapter 10
    Section 1008.2.1) llumination under normal power. The means of egress
    illumination level shall be not less than___ footcandle(s) at the walking
    surface.
A

1 footcandle

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

According to Book 57 (The 2020 Los Angeles Fire Code- Chapter 10
Section 1008.3.4) Duration> The emergency power system shall provide
power for a duration not less than_ minutes and shall consist of
storage batteries, unit equipment or an on site generator.

A

90 minutes

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

According to Book 57 (The 2020 Los Angeles Fire Code - Chapter 10
Section 1008.3.3 ) Rooms and Spaces. In the event of power supply
failure, an emergency electrical system shall automatically illuminate all
of the following areas: Electrical Rooms, Fire Command Centers, Fire
Pump Rooms, Generator Rooms and Public Restrooms with an area
greater than_ square feet?

A

300 sq ft

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

According to Book 57 (The 2020 Los Angeles Fire Code - Chapter 10
Section 1009.3.2) Stairway Width for accessible egress. Stairways shall
have a clear width of _ inches minimum between handrails.

A

48”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

According to Book 57 (The 2020 Los Angeles Fire Code - Chapter 10
Section 1011.3 Headroom) Stairways shall have a minimum clearance of
not less than _ inches measured vertically from a line connecting the
edge of nosing.

A

80”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

According to Book 57 (The 2020 Los Angeles Fire Code - Chapter 10
Section 1010.1.10.1) Where panic or fire exit hardware is installed, the
maximum unlatching force shall not exceed _ pounds

A

15lbs

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

According to the Los Angeles Fire Department Library Book 1 Basic
Inspection Guide, Section 57.33.17) Stairway Identification Signs shall be
square with a minimum dimension of __ inches

A

12”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

According to the Los Angeles Fire Department Library Book 1 Basic
Inspection Guide, Section 57.22.04) Permit. A special permit is required
for storage, display, sale, or other use of Christmas Trees within buildings
where more than_ trees are located.

A

10

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

According to the Los Angeles Fire Department Library Book 1 Basic
Inspection Guide, Section 57.80.09) Spray Booths, A permit is required to
erect, install or relocate spray booths or spray tunnel with any dimension
greater than_ feet

A

3ft

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

According to the Los Angeles Fire Department Library Book 1 Basic
Inspection Guide, (Section 57.138.13 Fire Department Connection Signs )
Fire Hose Cabinets that contain a fire extinguisher shall also be identified
with a sign stating “‘Fire Extinguisher* with letter no less than__ inches
on contrasting background.

A

3 “

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

According to the Los Angeles Fire Department Library Book 1 Basic
Inspection Guide, (Section 57.30.05) Table 30-B Permits: A Permit is
required for Class IA Flammable liquid in quantities greater than
Gallons

A

60 gallons

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

According to the Los Angeles Fire Department Library, Training
Bulletin 42 Single Station Smoke Detectors: Six out of ten fatal home fires
start between the hours of_&?

A

9pm & 6am

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
17
Q

According to the Los Angeles Fire Department Library, Training
Bulletin 42 Single Station Smoke Detectors: Detectors are approved to
give an area coverage equivalent to a_ foot diameter.

A

25 ft

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
18
Q

According to the Los Angeles Fire Department Library, Training
Bulletin 42 Single Station Smoke Detectors: A Smoke Detector can be
moved __ feet from a bedroom door and still provide coverage.

A

12.5 ft

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
19
Q

According to the Los Angeles Fire Department Library, Training
Bulletin 42 Single Station Smoke Detectors: Only Smoke Detectors
Approve by
can be sold or installed in California

A

California State Fire Marshal’s Office

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
20
Q

According to the Los Angeles Fire Department Library, Training
Bulletin 42 Single Station Smoke Detectors: All Detectors must meet the
following listing to be approved for use in California?

A

UL 217

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
21
Q

According to the Los Angeles Fire Department Library, Departmental
Bulletin 11-14 (Automatic Alarm Reduction Program) According the
DB11-14 the Los Angeles Fire Department responds to over
Automatic Alarms per month.

22
Q

According to the Los Angeles Fire Department Library, Departmental
Bulletin 11-14 (Automatic Alarm Reduction Program) According to DB 11
-14 Automatic Alarm Data will be collected on a
basis and a
report of the worst offenders will be provided to the FPB.

23
Q

According to the Los Angeles Fire Department Library. Departmental
Bulletin 11-14 (Automatic Alarm Reduction Program) The duration of the
Autoratic Alarm Reduction Program was

24
Q

According to the Los Angeles Fire Department Library, Departmental
Bulletin 11-14 (Automatic Alarm Reduction Program) When the fire
department arrives to an Intrusion alarm with no additional activations
the responding Officer is required to provide
with specified
information via email

A

On Duty OCD Battalion Commander

25
According to the Los Angeles Fire Department Library, Departmental Bulletin 11-14 (Automatic Alarm Reduction Program) The Automatic Alarm Reduction consists of Elements.
3
26
ACCORDING TO TB 01 2- AUTOMATIC SPRINKLER SYSTEMS, Records * show that_ of all fires in sprinklered buildings are extinguished or satisfactorily held in check by the sprinkler system.
96%
27
ACCORDING TO TB 012- AUTOMATIC SPRINKLER SYSTEMS, NBFU Bulletin No. 270 suggests that one of the first fire alarm engine companies responding should lay. into the fire department connection.
Two 2 1/2" lines
28
ACCORDING TO TB 012- AUTOMATIC SPRINKLER SYSTEMS, it is suggested that companies maintain a list of sprinklered buildings in their district. This information can be obtained from the_, which are filed behind the_ in the company files.
F-316s, F-173s
29
ACCORDING TO TB 012- AUTOMATIC SPRINKLER SYSTEMS "Junior systems" may be encountered from time to time which are designed to provide simple, inexpensive protection for light hazard occupancies where not over_or__ sprinklers are likely to likely to operate.
3, 4
30
ACCORDING TO TB 012- AUTOMATIC SPRINKLER SYSTEMS, A "Junior System" is a loop of three- fourths of an inch or one inch of copper tubing fitted with small orifice (one-fourth of an inch or three-eighths of an inch) sprinklers. They will discharge about _as much water as the standard one-half inch sprinkler.
One-Half 1/2
31
TB #149-RESIDENTIAL SPRINKLER SYSTEMS, states As of January 1, 2011, the State of California is requiring the installation of residential fire sprinklers in all new one- and two-family dwellings and manufactured homes. This mandate uses the NFPA 13D standard that includes new construction of garages, patios extending_ from house and unattached structures greater than
4', 200 sq ft
32
ACCORDING TO TB #149- RESIDENTIAL SPRINKLER SYSTEMS, The International Association of Fire Chiefs (IAFC) report that approximately 3,000 civilians perish annually from fire, with nearly two- thirds of those deaths occurring at
Home
33
TB #149-RESIDENTIAL SPRINKLER SYSTEMS states sprinkler head temperatures range from. degrees and cover a minimum area of,
135 to 175; 12'x12
34
ACCORDING TO TB #149- RESIDENTIAL SPRINKLER SYSTEMS which entity plan checks and approves the installation of residential sprinklers?
Plumbing/Mechanical Engineering Division of LADBS
35
TB #149-RESIDENTIAL SPRINKLER SYSTEMS STATES LADBS requires a (minimum) water demand capable of flowing for a period of
Two Heads; ten minutes
36
According to Book 57 (The 2020 Los Angeles Fire Code-Chapter 10 section 1012.2) Ramps used as part of a means of egress shall have a running slope not steeper than vertical in 12 units horizontal (8-percent slope).
One unit
37
According to Book 57 (The 2020 Los Angeles Fire Code-Chapter 10 section 1013.1) Exit sign placement in an exit access corridor or exit passageway shall be within how many feet?
100 ft
38
According to Book 57 (The 2020 Los Angeles Fire Code-Chapter 10 section 1013.6.2) The face of an exit sign illuminated from an external source shall have an intensity of not less then how many foot-candles?
5 foot-candles (54 lux)
39
According to Book 57 (The 2020 Los Angeles Fire Code-Chapter 10 section 1013.6.3) Illuminated exit signs shall ensure continued illumination for a duration of not less than how many minutes in case of primary power loss?
90 mins
40
According to Book 57 (The 2020 Los Angeles Fire Code-Chapter 10 secion 1015.7 1oof access) guards shall be provided if the roof hatch is located within how many feet of a roof edge?
10 ft
41
According to Book 57 (The 2020 Los Angeles Fire Code-Chapter 10 Table 1017.2) Occupancies A, E, F-1, M, R, and S-1 without a sprinkler system require an exit access travel distance of 200 feet. The occupancies with a sprinkler system require a travel distance of how many feet?
250 ft
42
According to Book 57 (The 2020 Los Angeles Fire Code-Chapter 10 section 1020.4 Dead ends) Where more than one exit or exit access doorway is required, the exit access shall be arranged such that dead-end corridors do not exceed how many feet in length?
20 ft
43
According to Book 57 (The 2020 Los Angeles Fire Code-Chapter 10 section 1023.2) Interior exit stairway and ramp enclosures shall have a fire-resistance rating of not less than _ _ where connecting four stories or more.
2 hours
44
According to Book 57 (The 2020 Los Angeles Fire Code-Chapter 10 section 1023.2) Interior exit stairway and ramp enclosures shall have a fire-resistance rating o not less than _ _ where connecting less than four stories.
1 hour
45
According to Book 57 (The 2020 Los Angeles Fire Code-Chapter 10 section 1030.3) Emergency escape and rescue openings shall have the bottom of the clear opening not greater than_ inches measured from the floor.
44 inches
46
ACCORDING TO TITLE 19, CALIFORNIA CODE OF REGULATIONS, DIVISION 1, SECTION 3.07 () CLEARANCES, No combustible material shall be placed or stored within how many feet of any building or structure?
10 feet
47
ACCORDING TO TITLE 19, CALIFORNIA CODE OF REGULATIONS, DIVISION 1, SECTION 320, FIRE SAFETY PERSONNEL, the owners and operators of any tent used as a place of assemblage shall provide at least one fire life safety person in every tent having a capacity of_persons and one additional qualified person for each - additional persons or fraction thereof.
500, 1000
48
ACCORDING TO TITLE 19, CALIFORNIA CODE OF REGULATIONS, DIVISION 1, SEC 568, TABLE 2, extinguishers with a 2-A and 4-A rating for low, moderate, and high class A hazards shall have a maximum travel distance of how many feet?
75 ft
49
ACCORDING TO TITLE 19, CALIFORNIA CODE OF REGULATIONS, DIVISION 1, SEC 904.2(h) TESTING AND MAINTENANCE REQUIREMENTS, who shall be consulted to avoid unnecessary disturbance of normal building operation at time of testing and maintenance?
Building Management
50
ACCORDING TO TITLE 19, CALIFORNIA CODE OF REGULATIONS, DIVISION 1, SEC 904.2(c) TESTING AND MAINTENANCE REQUIREMENTS, records of all testing and maintenance shall be retained on the premises by the building or system owner for a period of how many years after the next required test or maintenance?
5 years