201.15 Temperature Monitoring Flashcards

1
Q
  • 201.15 Temperature Monitoring*
    • *

Wide Range Temperature Instruments

A

Redundant loop temp during power operation

Monitor heatup / cooldown

WR Tc for eacr loop on Aux S/D Panel (ASP)

Input to Cold Overpressure Mitigation System (COMS)

While RCS < 350, RCS pressure is maintained < X by using the Pzr PORVs

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q
  • 201.15 Temperature Monitoring*
    • *

Narrow Range Temperature Instruments

A

Indication

Protection

(Excessive Cooldown Protection gives FW isolation on P-4 & low Tavg)

Rod Control

Pzr Level Control

Steam Dumps

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q
  • 201.15 Temperature Monitoring*
    • *

WR Temperature Instrument Locations

A

One RTD in cold leg and one in hot leg for each loop

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q
  • 201.15 Temperature Monitoring*
    • *

NR Temperature instrumentation Locations

A

1 RTD in each cold leg (3 fast respone spares)

3 fast response RTDs in each hot leg (120 degrees around pipe)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly