API-570 data sheets - Temperatures (26) Flashcards
UT - Calibration - calibration block must be within what temperature of the part to be examined
25 *F
577: 9.9.1
Corrosion- CUI affects carbon steel and low alloy (temperature range)
10-350 *F
574: 7.4.4.1.e
Welding- when B32.3 recommends Minimum Preheat Temps become required
< 32*F
B31.3: 330.1.1
NDE- Standard temperature range for a PT exam
40-125 *F
V: T-652/653
Testing- Min flash point of hydrocarbons used for leak testing
120*F
574: 5.8.1
Corrosion- CUI affects Austenitic Stain Steels (temperature range).
120-400 *F
574: 7.4.4.1.h
Corrosion- Typical dew point of hydrochloric acid
130 *F
571: 4.3.7.3.d
Corrosion- Temperature where chlorides stress corrosion cracking becomes a concern
> 140 *F (greater)
NDE- Special procedures needed for UT thickness readings
> (greater) 150 *F
570: 5.7.1
Corrosion- Temperatures swings that can cause thermal fatigue
+/- 200 *F
571: 4.2.9.3.c
Corrosion- Most aggressive CUI temperature range
212-250 *F
571: 4.3.3.3.d.
Corrosion- Typical dew point of sulfuric acid
280 *F
571: 4.3.7.3.c
Welding- Minimum pre-heat temperature, when preheat is substituted for PWHT
300 *F
570: 8.2.3.2
Welding- minimum pre-heat temperature, when a local PWHT is substituted for a full encirclement PWHT.
300 *F
570: 7.4.6.2
Corrosion- Starting temp for Sulfidation on Carbon Steel per API 574
450 *F
574: 7.4.6.2.j