CC UPS Flashcards

(78 cards)

1
Q

Q1 Breaker

A

Input isolation circuit breaker, used to isolate the UPS from the main AC input (mains 1) and provide input current protection.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

QF1 Breaker

A

Battery disconnect circuit breaker, external to the UPS, used to disconnect the battery from the UPS.
QF1 provides isolation and protection between the UPS and its battery system.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Q4S Breaker

A

Bypass input circuit breaker; it is used to isolate the UPS from the bypass input (mains 2) source and provide back-feed protection

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Q3BP

A

Maintenance bypass circuit breaker, used to supply the attached load via the bypass source while the UPS is being serviced.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Power Flow

Normal Operation

A

During normal operation, power flows from the main AC input source (mains 1) into the UPS rectifier/battery charger section. The rectifier/battery charger converts the AC voltage to DC, maintains the charge of the battery, and feeds the DC power to the inverter. The inverter regenerates AC voltage, and supplies the attached load.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Power Flow

On Battery Operation

A

If the main AC input source (mains 1) fails or goes out of tolerance, the charger stops. Power flows from the battery to the UPS inverter, which in turn supplies the attached load. When the main AC input source (mains 1) returns, the charger restarts automatically and the UPS resumes its normal operation. .
If the battery becomes depleted before the main AC input source (mains 1) returns, the inverter stops and the attached load is transferred to the bypass AC input source (mains 2) if it is available.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Front Panel

EPO Button

A

On the left side of the front panel, an emergency power off (EPO) pushbutton is
provided, with a protective cover to guard against inadvertent operation. This
pushbutton, when activated, disconnects the main AC input (mains 1), bypass AC
input (mains 2), and battery power to the UPS, and disconnects output power to the
attached load.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Front Panel

1

A

(item 1) The audible alarm provides an audible warning to the operator by sounding
a pulsed “beep” when any of the following conditions occur:
◗ Load transferred to bypass (mains 2)
◗ Load supplied via battery
◗ Operating problem
During minor alarm conditions, the alarm sounds at a slow rate and a low sound
level. When the battery approaches the low-voltage shutdown level, the alarm
sounds louder and at an increased rate. If the inverter shuts down, the alarm
sounds loudly and continuously.
An audible alarm reset is located on the hidden panel. See Figure 1-7. Pressing it
will silence the alarm. Should a higher-level alarm condition occur after the reset
has been activated, the audible alarm will sound the new alarm condition.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Front Panel

2

A

(item 2 ) This red LED turns on when any of these conditions occur:
◗ The load is no longer protected following an inverter shutdown,
or the opening of the isolation circuit breaker (Q5N).
◗ The battery circuit breaker QF1 is open, making battery power
unavailable.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Front Panel

3

A

(item 3) This orange LED turns on when an operating problem exists, such as fan
failure; static switch power supply fault; battery temperature fault;
overload fault; or bypass AC input (mains 2) out of tolerance. The UPS
continues to protect the attached load.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Front Panel

4

A

(item 4) This orange LED turns on to indicate that the attached load is
being partially or completely supplied by the battery. When the main AC
input (mains 1) fails or is outside tolerance, stored battery energy is
supplied to the inverter, which in turn supplies the load.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Front Panel

5

A

(item 5) This green LED indicates that the attached load is supplied by
the inverter and protected by the battery. During normal operation, this
LED is the only one that is on.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Front Panel

6

A

(item 6) This green pushbutton is used to start the inverter. When it is pushed, the
green “load protected” LED flashes for three seconds, indicating that the start
command has been received. When the inverter has synchronized with the bypass
AC input (mains 2) source, the static switch transfers the load to the inverter output.
If the inverter cannot synchronize to the bypass AC input (mains 2) source, the load
must be forced to transfer using the hidden panel (see section 2.11, Forced
Transfers).

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Front Panel

7

A

(item 7) This gray pushbutton is used to stop the inverter. When it is pressed for 3
seconds, the inverter stops and the load is transferred to the bypass AC input (mains
2) source. If the uninterrupted transfer conditions are not met, this pushbutton has
no effect and the inverter can be stopped only from the hidden panel (see Section
2.12, Forced Transfers).

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

What is this?

A

Alphanumeric Display and Controls

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

Settings Button

A

This pushbutton is used to select the display language and adjust the LCD screen
contrast for optimal viewing.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
17
Q

Selection Button

A

Depending on the displayed message, the “˘” key may serve to indicate selection,
negative response, and other functions.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
18
Q

Voltage Button

A

This pushbutton provides access to voltage measurements, including:
◗ Main AC input (mains 1) phase-to-phase voltage
◗ Bypass AC input (mains 2) phase-to-neutral and phase-to-phase voltage
◗ Inverter output phase-to-neutral and phase-to-phase voltage
◗ Load phase-to-neutral and phase-to-phase voltage

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
19
Q

Current Button

A

This pushbutton provides access to current measurements, including:
◗ Main AC input (mains 1) current
◗ Bypass AC input (mains 2) current
◗ Inverter output current
◗ Load current
◗ Percent current drawn by the load relative to UPS rating
◗ Crest factor per phase

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
20
Q

Power/Freq. Button

A

This pushbutton provides access to power and frequency measurements, including:
◗ Main AC input (mains 1) frequency
◗ Bypass AC input (mains 2) frequency
◗ Inverter frequency
◗ Power drawn by the load (in kW and kVA)
◗ Load power factor

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
21
Q

Battery Button

A

This pushbutton provides access to battery measurements, including:
◗ Battery voltage
◗ Battery current
◗ Battery ambient temperature
◗ Battery time available
◗ Battery time remaining

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
22
Q

Alarm Button

A

This pushbutton is used to display current alarms, or to display stored alarms.
If the alarm key is pressed repeatedly, the display will scroll through the stored alarm
record, returning to the latest after the oldest is shown.
If a blinking character (!) appears in the display, the user may press the Alarm
pushbutton again to scroll through additional useful information.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
23
Q

Hidden Panel Indicators

A

There are 14 led indicators and additional status pushbottons.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
24
Q

A

A

Emergency Shutdown

This red LED indicates that the emergency power off (EPO) or remote emergency power off (REPO) has been activated.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
25
B
Rectifier / Charger is On ## Footnote This green LED indicates that the rectifier/battery charger is on.
26
C
Rectifier / Charger Fault ## Footnote This red LED indicates an alarm condition within the rectifier/battery charger. it indicates the presence of one of the following fault conditions: ◗ Input circuit breaker Q1 open ◗ Input power protection fuse blown ◗ Rectifier/battery charger over-temperature ◗ Battery charge overcurrent ◗ Battery overvoltage ◗ Rectifier/battery charger control board fault ◗ Power supply board fault
27
D
Main AC input (mains 1) outside tolerance This orange LED indicates that the main AC input (mains 1) source is outside tolerance (voltage and/or frequency too high or too low).
28
E
Reserved for future use.
29
F
Battery Temperature Outside Tolorence ## Footnote This orange LED indicates that the ambient temperature of the battery is too high or too low.
30
G
Battery Charging ## Footnote This orange LED indicates that the battery is being recharged. This LED functions only when the connected battery is of the vented lead-acid type (sealed lead-acid batteries will not activate this signal).
31
H
Inverter Fault ## Footnote This red LED indicates an alarm condition in the inverter, which may be one or more of the following conditions: ◗ Inverter shutdown due to output voltage out of tolerance ◗ Inverter output protection fuse blown ◗ Inverter leg fault ◗ Inverter output transformer over-temperature ◗ Inverter leg over-temperature ◗ Internal clock fault ◗ Inverter control board fault ◗ Power supply board fault
32
I
Battery Discharged ## Footnote This orange LED indicates that the battery has reached the end of its autonomy, shutting down the inverter.
33
J
Inverter Desynchronized ## Footnote This orange LED indicates that the inverter is not synchronized with the bypass AC input (mains 2).
34
K
Transfer Fault ## Footnote This red LED indicates a transfer fault, which may be one or more of the following conditions: ◗ Inverter output static switch fault ◗ Static switch over-temperature ◗ Static switch power supply fault ◗ Transfer control board fault ◗ Power supply board fault
35
L
Overload ## Footnote This orange LED indicates an alarm condition resulting from one or more of the following conditions: ◗ Inverter current above rating ◗ Output current above rating ◗ Inverter and/or static switch shutdown due to excessive load current
36
M
Bypass AC input (mains 2) outside tolerance ## Footnote This orange LED indicates that the bypass AC input (mains 2) voltage and/or frequency are too high or too low.
37
N
Maintenance Position ## Footnote This orange LED indicates that circuit breakers QF1, Q4S, Q5N, or Q3BP are set to the maintenance position. The UPS is not available for load protection.
38
Test Connector
(port) This 9-pin connector is reserved for service. It is used to connect the cabinet to a computer, allowing system calibration, personalization, and computer-aided diagnostics
39
Clear Fault Log
Pressing this pushbutton clears the alarms stored in memory, allowing the unit to restart. Memorized alarms cannot be cleared until the condition causing the alarm has been corrected
40
Audible Alarm Reset
Pressing this pushbutton stops the audible alarm. Should a new fault condition at a higher alarm level occur, the alarm will sound again.
41
Battery Charge Cycle Button 1
(pushbutton #1) Pressing this pushbutton begins a battery charging cycle. After the cycle is complete, the rectifier/battery charger returns to float charge levels on the battery. The battery charge cycle is not applicable to sealed lead-acid battery installations
42
Return to Float Voltage Button 2
pushbutton #2) This pushbutton can be used during a battery charge cycle to force the rectifier/battery charger back to the float voltage level.
43
LOW LEVEL ALARM UPS OK !
This message indicates that a problem requiring action has occurred. The load is still supplied by the inverter. The problem is listed in the secondary alarm message (see below), as indicated by the flashing exclamation mark (!). The alarm message may be viewed by pressing the “alarm” pushbutton (!)
44
UPS INPUT FAILURE LOAD ON BATTERY !
This message indicates that the main AC input (mains 1) has failed or is outside of tolerance, and power to the inverter is being supplied from the UPS battery system. The load is still supplied via the inverter.
45
REMAINING BAT. TIME \_\_ MN %KW LOAD = \_\_
This message is automatically displayed every five seconds when the UPS is on battery. It alternates with the previous message. The message provides an estimate of the available remaining time on battery, based on the percentage of full rated load being supplied, the type of battery, the battery temperature, and the battery age.
46
UPS LOW BATTERY SHUTDOWN IMMINENT !
This message indicates that the batteries have reached the “low battery shutdown” warning level. The user must take steps to prepare the load for shutdown (load shedding, file saving and computer shutdown, etc.). This message replaces the previous two messages when the batteries are nearly depleted. When this message appears, there are only a few minutes of battery back-up time remaining.
47
UPS ALARM CALL SERVICE !
This indicates that the battery disconnect circuit breaker QF1 has been open or the inverter has stopped and that service is required. The problem is listed in the secondary alarm message (see below), as indicated by the flashing exclamation mark (!). The secondary alarm message may be viewed by pressing the “alarm” pushbutton (!).
48
EMERGENCY SHUTDOWN REPO ON !
This message indicates that the UPS has been shut down because a remote emergency power off (REPO) pushbutton has been pressed and is still closed.
49
LOAD ON BYPASS !
This message indicates that the load has been transferred to the bypass AC input (mains 2) source. The load is no longer protected.
50
BYPASS PROBLEM CHECK FREQUENCY !
This message indicates that the bypass AC input (mains 2) source is out of frequency tolerance. The inverter has switched to free-running mode. Transfer of the load from the inverter output to the bypass AC input source requires an interruption of power to the load.
51
BYPASS PROBLEM CHECK VOLTAGE !
This message indicates that the bypass AC input (mains 2) source is out of voltage tolerance. The inverter has switched to free-running mode. Transfer of the load from the inverter output to the bypass AC input source requires an interruption of power to the load.
52
INDEPENDENT INVERTER FREQ. COMMAND ON !
This message indicates that the inverter has been set to free-running mode. The inverter is not synchronized to the bypass AC input (mains 2) power source. Transfer of the load from the inverter output to the bypass AC input source requires an interruption of power to the load.
53
BYPASS TRANSFER LOCKOUT COMMAND ON !
This message indicates that the UPS has been set not to transfer from the inverter to the bypass AC input (mains 2) source. In the event of an inverter shutdown, the load will be disconnected.
54
BATTERY CABINET OVERTEMP. !
This message indicates that the ambient temperature of the battery is out of tolerance.
55
UPS INPUT PROBLEM CHECK FREQUENCY !
This message indicates that the main AC input (mains 1) frequency is out of tolerance. The rectifier/battery charger has shut down and the inverter is operating from its battery source.
56
UPS INPUT PROBLEM CHECK VOLTAGE !
This message indicates that the main AC input (mains 1) voltage is out of tolerance. the rectifier/battery charger has shut down and the inverter is operating from its battery source.
57
CHARGER SHUTDOWN COMMAND ON !
This message indicates that the rectifier/battery charger has been instructed to shut down, for example during progressive (stepped) transfer to a motor-generator set.
58
INPUT KVA LIMITED COMMAND ON !
This message indicates that the rectifier/battery charger has been instructed to limit the power drawn from the main AC input (mains 1) source. This condition occurs, for example, when the load is being supplied by an undersized motor-generator set; the UPS battery source is called upon to make up the difference
59
BATTERY CURRENT LIMIT COMMAND ON !
This message indicates that the rectifier/battery charger has been instructed to limit the charge current to the battery. Normal charge current to the battery will be supplied when the command is released. This condition occurs, for example, when the load is being supplied by an undersized motor-generator set.
60
QF1 BATTERY BREAKER OPEN !
This message indicates that the battery circuit breaker QF1 has been opened or has tripped. the load is no longer protected, since battery power is unavailable.
61
LOW BATTERY . . . !
This message indicates that the inverter has shut down, due to depletion of the batterys' stored energy.
62
CHARGER OFF . . . !
This message indicates that the rectifier/battery charger has shut down.
63
CHARGER FAULT CALL SERVICE !
This message indicates that a fault has occurred in the rectifier/battery charger, and that service is required.
64
Q1 UPS INPUT CB OPEN !
This message indicates that the input isolation circuit breaker is open or has tripped. It must be closed for rectifier/battery charger start-up.
65
INVERTER OVERLOAD CHECK P.F. AND KW
This message indicates that the inverter is in an overload condition, usually due to excessive real power (kW) being drawn by the load. The flashing “KW” indicates that the operator should check the load real power. The inverter will keep supplying the load for a certain amount of time depending on the overload level.
66
INVERTER FAULT CALL SERVICE !
This message indicates that a fault has occurred in the inverter, and that service is required.
67
INVERTER SHUTDOWN OVERLOAD \> I MAX!
This message indicates that an overload greater than 1.5 times the full power rating of the inverter has occurred, and that the inverter has shut down.
68
INVERTER SHUTDOWN THERMAL OVERLOAD A
This message indicates that an overload below 1.5 times the full power rating of the inverter has occurred and that the inverter has shut down. The flashing “A” indicates that the operator should check the load current.
69
I LOAD \> IN CHECK LOAD A
This message indicates that the load power being drawn is greater than the UPS full load rating. The flashing “A” indicates that the operator should check the load current. The inverter or static switch will keep supplying the load for a certain amount of time depending on the overload level.
70
TRANSFER FAULT CALL SERVICE !
This message indicates that a fault has occurred that affects the transfer of the load between the inverter and the bypass source. Service is required.
71
PH OUT OF TOLERANCE !
This message indicates that there is an out of tolerance condition between the inverter and bypass AC input (mains 2) sources. Transfer of the load between the inverter and bypass AC input will result in an interruption of load power.
72
Q4S BYPASS SWITCH OPEN !
This message indicates that the circuit breaker Q4S is open. Transfer of the load from the inverter to the bypass source is not possible.
73
Q5N UPS OUTPUT ISOL. SWITCH OPEN !
This message indicates that the optional UPS isolation circuit breaker Q5N is open. The load is not supplied unless the maintenance bypass circuit breaker Q3BP is closed.
74
Q3BP MAINT. BYPASS SWITCH CLOSED !
This message indicates that the optional maintenance bypass circuit breaker Q3BP is closed. The system is set to maintenance bypass, and the load is supplied by the bypass AC input source (mains 2).
75
STATIC SWITCH O.L. EMERGENCY OFF !
This message indicates that the static switch has shut down following an overload condition, disconnecting the load.
76
DISPLAY NUMBER 1 UNAVAILABLE
This message indicates that the alphanumeric display is not operating properly. The status of the UPS is still correctly indicated by the LEDs of the visible panel and the hidden panel, see section 1.5 Single Module Indicators and Controls.
77
HARMONIC FILTER FUSE FAILED
This message indicates that the fuse(s) protecting the input harmonic filter has opened and that service is required. The status of the UPS is still correctly indicated by the LEDs of the visible panel. Refer to section 1.5 Single Module Indicators and Controls for front and hidden panel indicators and controls.
78