CC UPS Flashcards
(78 cards)
Q1 Breaker
Input isolation circuit breaker, used to isolate the UPS from the main AC input (mains 1) and provide input current protection.
QF1 Breaker
Battery disconnect circuit breaker, external to the UPS, used to disconnect the battery from the UPS.
QF1 provides isolation and protection between the UPS and its battery system.
Q4S Breaker
Bypass input circuit breaker; it is used to isolate the UPS from the bypass input (mains 2) source and provide back-feed protection
Q3BP
Maintenance bypass circuit breaker, used to supply the attached load via the bypass source while the UPS is being serviced.
Power Flow
Normal Operation
During normal operation, power flows from the main AC input source (mains 1) into the UPS rectifier/battery charger section. The rectifier/battery charger converts the AC voltage to DC, maintains the charge of the battery, and feeds the DC power to the inverter. The inverter regenerates AC voltage, and supplies the attached load.
Power Flow
On Battery Operation
If the main AC input source (mains 1) fails or goes out of tolerance, the charger stops. Power flows from the battery to the UPS inverter, which in turn supplies the attached load. When the main AC input source (mains 1) returns, the charger restarts automatically and the UPS resumes its normal operation. .
If the battery becomes depleted before the main AC input source (mains 1) returns, the inverter stops and the attached load is transferred to the bypass AC input source (mains 2) if it is available.
Front Panel
EPO Button
On the left side of the front panel, an emergency power off (EPO) pushbutton is
provided, with a protective cover to guard against inadvertent operation. This
pushbutton, when activated, disconnects the main AC input (mains 1), bypass AC
input (mains 2), and battery power to the UPS, and disconnects output power to the
attached load.
Front Panel
1
(item 1) The audible alarm provides an audible warning to the operator by sounding
a pulsed “beep” when any of the following conditions occur:
◗ Load transferred to bypass (mains 2)
◗ Load supplied via battery
◗ Operating problem
During minor alarm conditions, the alarm sounds at a slow rate and a low sound
level. When the battery approaches the low-voltage shutdown level, the alarm
sounds louder and at an increased rate. If the inverter shuts down, the alarm
sounds loudly and continuously.
An audible alarm reset is located on the hidden panel. See Figure 1-7. Pressing it
will silence the alarm. Should a higher-level alarm condition occur after the reset
has been activated, the audible alarm will sound the new alarm condition.
Front Panel
2
(item 2 ) This red LED turns on when any of these conditions occur:
◗ The load is no longer protected following an inverter shutdown,
or the opening of the isolation circuit breaker (Q5N).
◗ The battery circuit breaker QF1 is open, making battery power
unavailable.
Front Panel
3
(item 3) This orange LED turns on when an operating problem exists, such as fan
failure; static switch power supply fault; battery temperature fault;
overload fault; or bypass AC input (mains 2) out of tolerance. The UPS
continues to protect the attached load.
Front Panel
4
(item 4) This orange LED turns on to indicate that the attached load is
being partially or completely supplied by the battery. When the main AC
input (mains 1) fails or is outside tolerance, stored battery energy is
supplied to the inverter, which in turn supplies the load.
Front Panel
5
(item 5) This green LED indicates that the attached load is supplied by
the inverter and protected by the battery. During normal operation, this
LED is the only one that is on.
Front Panel
6
(item 6) This green pushbutton is used to start the inverter. When it is pushed, the
green “load protected” LED flashes for three seconds, indicating that the start
command has been received. When the inverter has synchronized with the bypass
AC input (mains 2) source, the static switch transfers the load to the inverter output.
If the inverter cannot synchronize to the bypass AC input (mains 2) source, the load
must be forced to transfer using the hidden panel (see section 2.11, Forced
Transfers).
Front Panel
7
(item 7) This gray pushbutton is used to stop the inverter. When it is pressed for 3
seconds, the inverter stops and the load is transferred to the bypass AC input (mains
2) source. If the uninterrupted transfer conditions are not met, this pushbutton has
no effect and the inverter can be stopped only from the hidden panel (see Section
2.12, Forced Transfers).
What is this?
Alphanumeric Display and Controls
Settings Button
This pushbutton is used to select the display language and adjust the LCD screen
contrast for optimal viewing.
Selection Button
Depending on the displayed message, the “˘” key may serve to indicate selection,
negative response, and other functions.
Voltage Button
This pushbutton provides access to voltage measurements, including:
◗ Main AC input (mains 1) phase-to-phase voltage
◗ Bypass AC input (mains 2) phase-to-neutral and phase-to-phase voltage
◗ Inverter output phase-to-neutral and phase-to-phase voltage
◗ Load phase-to-neutral and phase-to-phase voltage
Current Button
This pushbutton provides access to current measurements, including:
◗ Main AC input (mains 1) current
◗ Bypass AC input (mains 2) current
◗ Inverter output current
◗ Load current
◗ Percent current drawn by the load relative to UPS rating
◗ Crest factor per phase
Power/Freq. Button
This pushbutton provides access to power and frequency measurements, including:
◗ Main AC input (mains 1) frequency
◗ Bypass AC input (mains 2) frequency
◗ Inverter frequency
◗ Power drawn by the load (in kW and kVA)
◗ Load power factor
Battery Button
This pushbutton provides access to battery measurements, including:
◗ Battery voltage
◗ Battery current
◗ Battery ambient temperature
◗ Battery time available
◗ Battery time remaining
Alarm Button
This pushbutton is used to display current alarms, or to display stored alarms.
If the alarm key is pressed repeatedly, the display will scroll through the stored alarm
record, returning to the latest after the oldest is shown.
If a blinking character (!) appears in the display, the user may press the Alarm
pushbutton again to scroll through additional useful information.
Hidden Panel Indicators
There are 14 led indicators and additional status pushbottons.
A
Emergency Shutdown
This red LED indicates that the emergency power off (EPO) or remote emergency power off (REPO) has been activated.