Ch 7 Flashcards
(35 cards)
In a building on fire with an automatic fire suppression system, the primary tactic is to
Support the system and let it do its job.
NFPA 13 R and NFPA 13 D reference installation for residential occupancies and Homes. The death rate and damage rate is how much lower in Homes protected by wet pipe sprinkler systems.
Death rate is 83% lower and damage is 69% lower than non-sprinkler protected residences
An important part of NFPA 25 is to tag…
To tag a sprinkler system to show that it is removed from service and not functional
The sprinkler system is most often encountered and is the most reliable fire suppression system is
The wet pipe sprinkler system
Sprinkler systems that are used in areas that may be subject to freezing temperatures are
Dry pipe sprinkler systems
The difference between a pre-action sprinkler system and a dry pipe sprinkler system is
They are both filled with air, but the pre-action system has a sensing device that opens the water valve.
In both dry pipe and pre-action systems, if the piping capacity exceeds 500 gallons, the system must have
Must be equipped with an accelerator or exhauster to rapidly remove air from the system
Deluge Systems protect areas with high fire potential, such as flammable liquids, aircraft hangers, and combustible commodities. A deluge system has these feature features.
Dry pipe system, all sprinklers are open, and a detector operated valve, which is normally closed. When this is opened, it allows water to fill the piping and discharge from all sprinklers.
A deluge system may also have a manually operated override valve
If a decision must be made between using hose lines and properly supplying the sprinkler system, is best to
Supply the sprinkler system first.
If the sprinkler system is not achieving the desired results because of problems, water may be redirected to support hose lines
The two most common types of main control valves used to open and close sprinkler systems
OS&Y outside stem and yoke
PIV post indicator valve
It is poor practice to rely on remote annunciated panels to determine whether or not the fire pumps are running. You should.
Have a firefighter or two do a physical check of the pumps, and manually start the pumps if needed or directed by the IC
According to the book, the minimum size hose line to connect to the FDC is
Two 2 1/2 inch or two 3 inch lines.
The book recommends when connecting to an FDC for sprinkler Support you should pump 150 psi. Many sprinkler systems have a max design and tested pressure of.
175 psi
The three options when connecting to a fire hydrant and supplying the building FDC are
Hand lay to the hydrant and to the FDC
Forward lay LDH and connect to the FDC
Relay pump with a supply pumper at the hydrant and an attack pumper
If you encounter male threads on what is appearing to be the FDC, you should recognize this as
Either a test header, or a wall hydrant. This is not an FDC.
When shutting down the sprinkler system, it is better to
Shut it down later than earlier, and have a firefighter prepared to turn it back on
Even after the spring system has been shut down and restored and sprinkler heads replaced, the property owner should
Contact a licensed sprinkler contractor to inspect the system.
NFPA 14 lists six major types of standpipe systems
Automatic dry
Automatic wet- the most common type
Semiautomatic dry
Manual dry
Manual wet
Combined system- contains both sprinklers and standpipes
Wet standpipe system
NFPA 14 also defines three types of standpipes
Class 1- 2 1/2 inch connections
Class 2 - 1 1/2 inch connections and hose stations
Class 3 - both 1 1/2 and 2 1/2 connections
Older codes specified 65 psi, modern codes require 100 psi
Two intakes at the FDC indicate a flow of
Greater than 500 gallons per minute
The difference between manual wet/dry and automatic wet/dry standpipe systems are
Manual systems require water to be supplied to the FDC. Automatic systems are connected to a water supply all the time.
According to the book, how much should you allow for friction loss in standpipe system?
10 to 15 psi friction loss is adequate for standpipe system piping
Book minimums for standpipe operations
150 feet of 2.5” hose
50 feet of 1.75” hose
100 GPM
1.25-1.125” smoothbore nozzle
7/8 or 15/16 smoothie bar in conjunction with 1.75” attack hose
Non-water based extinguishing systems include
Foam
Halon/clean agents
Carbon dioxide
Dry chemical
Other systems using inert gases