Chapter 10 Flashcards
Chapter 10
The driver operator must first made the pump operational and then prepare to use?
At least one of the three sources of water to supply the pumping operation (335)
When making a fire pump operational begins?
After the Apparatus is properly position and the parking brake has been set
how to prevent pump from over heating
circulator bypass or booster cooling valve to recirculate water back in the tank (337-38)
During drafting operations, the amount of friction loss is____to the amount of water moving through the hose or appliance
Proportional
pumping at a low residual pressure while being supplied by another apparatus is____ dangerous. This may cause the ____ to____,interrupting the supply of water. it may also lead to______of the pump
equally/hose /collapse,/cavitation
Transfer valve must be in parallel (volume)position when priming:(358)
Two-stage pumps
A pump in series (pressure) position may(358)
Trap air that will need to be removed
To create an effective fire stream during drafting operations,a lift of no greater than____ is recommended
20 feet for 60% capacity of the pump
As air is evacuated from the pump the compound gauge on the intake will register a vacuum reading
1 inch of mercury for 1 foot of lift required
Priming typically take 10 to 15 seconds but not to exceed
30 seconds (45 seconds in pump larger than 1250 GPM)
Vacuum is measured from the surface of the water
To the eye of the pump’s impeller
When opening the discharge (using a draft)if the pressure dropped below____pause a moment to allow it to stabilize before opening it further
50psi
Water temperature below 35°F or above 90°F may adversely impact The ability of the pump to reach (356)
Capacity
Driver engineer should maintain the residual pressure of at least ____ on their master gauge intake during pumping operation (340)
20 PSI
When using 2 1/2 or 3 inch to supply the pumper off the hydrant the lines should be(344)
Kept as short as possible to avoid excess friction loss
When pumping in relay the supplying pumper should supply
20 psi plus friction loss and engine pressure should not exceed 250 psi
If a circular tank is 12 feet in diameter 15 feet high is 3/4 full and water is being removed from the tank at a rate of 500 GPM, approximately how many minutes will it takes before the tank is empty
x
Class AA hydrant
Light blue at 1500 gallons per minute
Class A hydrant
Green at 1000 to 1499 gallons per minute
Class B hydrant
Orange at 500 to 999 gallons per minute
Class C hydrant
Red at less than 500 gallons per minute
The water supply from an onboard water tank is(336)
The sole source of supply for many incidents
The two basic pressurized water supply sources are a fire hydrant and(339)
Supply hose from another pumper.
In order to partially open the tank fill valve and not create the potential for pump cavitation, some driver open the valve the distance of their thump to the pump panel with their hand on the valve control.(338)
True.