Chapter 6 Tightness testing and Purging Flashcards

(26 cards)

1
Q

What is the NPM (no perceptible movement on the gauge during a tightness test?

A

0.25mbar on a water gauge, 0.2mbar on a digital gauge

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What is the let-by test testing?

A

checks if the emergency control valve (ECV) or meter control valve is allowing gas to pass through even when it’s supposedly closed

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

As a domestic gas engineer what is the maximum installation volume you can work on?

A

0.035 meter cubed.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

As a domestic gas engineer what is the maximum pressure in the system you can work on?

A

Anything below 2 bars.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

When to test for Tightness test? (There are more than 3 answers)

A
  1. Completion of new pipework installations.
  2. After alteration of existing installations.
  3. New extensions to pipework.
  4. Prior to any work on existing pipework.
  5. Where there’s a known or suspected gas leak.
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

On a meter which is not zeroed, the 2 different reading shown on the U gauge is 21mbar and 18mbar, what is the correct pressure?

A

(21-18)/2 = 19.5mbar.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What is Maximum permissible pressure drop on a G4/U6 meter with pipework Diameter of 28mm?

A

4mbar
(2.5mbar for 35mm pipework)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What is the Maximum permissible pressure drop on a E6 Ultrasonic meter, or No meter with a pipework of 28mm?

A

8mbar
(4mbar for pipework 35mm)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

At what pressure do we do the let-by test, and how long is test for?

A

7-10mbar for 1 minute.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

During the let-by test, the pressure increased to 12mbar within the minute of the testing, what should you check?

A

The isolation valve, check by disconnecting the outlet union and apply LDF to the valve barrel or ball.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What is the maximum inlet pressure to medium pressure meter installation that our domestic gas engineers are allowed to work on?

A

2bar (medium pressure is up to 2 bar)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What is the maximum pipework diameter a domestic gas engineer is allowed to work on?

A

35mm (Anything above will be classified as commercial)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

What is the maximum rated capacity through the primary meter a domestic gas engineer is allowed to work on?

A

16 m3/h (a U16 meter)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

What is the maximum installation volume (IV) including any meter and its fittings a domestic gas engineer is allowed to work on?

A

0.035m3
Anything above this will be classified as commercial work.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

What is the testing pressure for a low-pressure tightness test?

A

20mbar-21mbar

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

What is the testing pressure for a medium-pressure tightness test?

A

18mbar-19mbar

17
Q

What is the equation for adding up total installation volume?

A

IVt = IVm + IVp + IVf
Installation volume Total = Meter IV + Pipe IV + Fitting IV

18
Q

The pipe installation volume is 0.004 meter cubed, what is the fitting installation volume?

A

IVf = IVp * 0.1
IVf = 0.004 * 0.1 = 0.0004 m3

19
Q

For medium pressure tightness test, how does the tightness test carried out when there is a meter inlet valve just before the meter inlet?

A

Same procedure as the low-pressure tightness testing process.

20
Q

What needs to be sprayed with LDF following a tightness test?

A

ECV, Anaconda, Testing point, pressure regulator, meter connections.

21
Q

What is the OFF-ON-ON-Spray process after a tightness test on a medium pressure system

A

Gauge off, ECV on, lever on. Spray.

22
Q

What is the purge volume for a G4/U6/E6 meter with pipe diameter of 28mm or below.

23
Q

What is the purge volume for a U6/G4/E6/U16/G10 meter with pipe diameter of 35mm?

A

1.5 times the IV (Installation volume)

24
Q

The label on a G4 meter reads: Q = 6m3/h … V 2dm3, what is this V? How does this relate to purge volume?

A

V is badge volume, which is the internal volume of the gas meter. Purge volume of this meter will be 5 times the badge volume - 5 * 2 dm3 = 10 dm3 = 0.01m3

25
What is the IV for a U6/G4 meter?
0.008 m3.