1
Q

The maximum horizontal length of a w.c fixture drain is?

A

10 ft (3m)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

A vent stack shall be installed to protect the base of every soil or waste stack that passes through more than:

A

4 storeys

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What is the hydraulic load of a 3” floor drain in a public washroom?

A

no load

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

The size of the portion of vent pipe that terminates through the roof shall not be less than:

A

3”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Any roof vent terminating into the open air shall be located at a distance of not less than:

A

3.5m away from any window, door or other opening

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

The min developed length of a trap arm shall not exceed:

A

2 x the pipe diameter

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Strap hangers shall not be used to support horizontal pipe greater than:

A

4”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Fixtures that drain into a vertical section of a relief or circuit vent shall not have a hydraulic load of?

A

1 1/2 FU

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

All fixtures shall have a trap w/ a water seal of?

A

not less than 1 1/2 “ (38mm)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

A trap used to carry acid waste shall have a water seal of:

A

not less than 2” (50mm)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

How many fixture units are permitted to drain into a soil or waste stack if the stack was to act as a relief vent?

A

6 FU each

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

The max number of a water closets allowed on a 3” soil stack is?

A

6 water closets

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

The rate of discharge through an 1 1/4” fixture outlet pipe is called a/an

A

fixture unit

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Where a building trap is installed, a fresh air inlet shall be installed on the building drain upstream of the trap:
2.5.5.4

A

as close as possible to the trap and w/in 1.2m of the trap

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

The trap weir is?

A

The highest part of the lower interior surface

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

A vertical pipe means:

A

45 degree from the vertical

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
17
Q

The max distance bn hangers on a horizontal run of ABS plastic pipe shall be:

A

1.2m (4’)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
18
Q

A building sewer begins outside a building at a point?

A

1m from the building wall

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
19
Q

The total fall of a fixture drain from the trap weir to the vent fitting shall not exceed:

A

two times the diameter of the pipe

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
20
Q

Any vent pipe shall extend vertically above the flood level rim of a fixture:

A

to adjust above the flood level rim before connecting to another vent

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
21
Q

The min size of a fresh air inlet for a 7 storey building is:

A

4”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
22
Q

A shower receptor for 2 or 3 heads is equal to a hydraulic load of:

A

3 fixture units

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
23
Q

A kitchen sink with a domestic type garbage disposal unit installed on it has a hydraulic load of?

A

1 1/2 FU

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
24
Q

A 2” trap not listed in table 2.4.9.3 has a hydraulic load of?

A

3 FU

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
25
The max number of FU that may be connected to a horizontal branch off a 2" stack that passes through 5 storeys is?
6 FU
26
The max number of FU that may be connected to a 3" stack of 60 meters in developed length is:
102 FU
27
The max number of FU that may be connected to a 4" building drain at uniform grade of 1 in 50 is?
240 FU
28
The size of a trap / waste opening for a potato peeler is?
2"
29
The size of a trap / waste opening for a beauty parlor basin is?
1 1/2"
30
The min size vent for a 2" trap is?
1 1/2"
31
The max cumulative change in direction of a trap arm serving a lavatory is?
135 degrees
32
A branch cannot be connected w/in 1.5m of the base of the stack:
- receives a discharge of 30 of more FUs - receives a discharge from fixtures located on 2 or more storeys
33
A common cause of trap seal loss in a properly vented system is?
evaporation
34
An ABS stack 15m in length, when subjected to a temp change of 50 C, would have a linear expansion of about?
70 mm A-2.3.3.9
35
The trap seal refers to the vertical distance measured from?
the trap weir to the trap dip
36
In testing a 5 storey (15m) stack with water, the pressure at the base of the stack on the gauge would read?
147 kPa
37
If 8 water closets are required in a washroom, how many urinals could be substituted for w.c's?
5 (2/3)
38
The max length of an offset on a 4" soil / waste stack serving as a wet vent is?
max 2.5 m
39
You must connect a sanitary building drain w/ a combined building sewer. If an open air restaurant is located on the roof of the building, and the roof drain has to be located w/in 1 m of the patio, what must you do to ensure that your rough-in passes inspection?
Place a running trap / clean-out on the storm building drain prior to its connection w/ the building sewer
40
What is the min length of a trap arm serving a lavatory?
2 1/2"
41
Which arrangement may allow a fixture to self-siphon?
Trap too far below fixture
42
If you have a 4" building drain connected to a 3" soil stack, what would the size of the c/o at the base of the stack be?
4" 2.4.7.2
43
What is the min grade on a building drain?
1% 1/8
44
What is the primary function of a p-trap?
Keep sewer gases from entering the building
45
Trap arm size are based on?
The size of the fixture outlet pipe
46
What would be the size of a trap that serves two lavatories that are in the same room?
1 1/2"
47
What size of vent terminal would be required for a 1 1/2" vent?
1 1/2" x 3" 2.5.6.5
48
What is the max size of a trap arm that may drain into a wet vent?
2 w/ the exception of an emergency floor drain
49
What is the min size of c/o for a 4" pipe?
4"
50
Flat vent is a trade name for a vent that?
requires a c/o fitting to be placed
51
The main stack / vent located in a single - family dwelling:
Should be chosen to allow as many fixture as possible to connect to the main stack.
52
The min drainage pipe size for a lavatory is?
1 1/4"
53
What is the max degree change of direction on a water closet trap arm?
225 degrees
54
On a ferrous c/o fitting, all nuts, bolts, caps and plugs shall be?
non-ferrous
55
Which of the following traps is prohibited from use in a plumbing system?
bell-trap
56
______ is a vent pipe that serves one fixture?
individual vent
57
A branch vent:
is two or more dry vents connecting together
58
the positive or negative pressure in a drainage will never exceed ____ of water column at the trap seal serving the fixture:
1"
59
What is the max length of a continuous waste serving a kitchen sink?
1200mm
60
On a fixture drain serving a kitchen you cannot exceed ____ degrees bn c/o:
90 degrees
61
A 3" (80mm) stack vent is required in a residence because of:
the national plumbing code of Canada
62
What kind of trap is allowed to be used on an interceptor?
drum trap
63
The min pipe size for a building sewer that is to be connected to public sewer is:
4 "
64
A pipe positioned at a 45 degree from the horizontal, is considered to be?
vertical
65
The continuous waste / vent principle connection is considered as the best arrangement for venting because:
waste water does not enter the vent pipe
66
A vent connection fitting placed on a trap arm:
must have the vent opening arranged above horizontal centreline of the trap
67
The min slope to which a trap arm must be installed is?
2% grade
68
What is the min distance that a vent can terminate above a door?
1m
69
The waste pipe of dual-vented fixtures must connect at?
same level
70
What is the min trap seal depth for all traps except those that drain acid wastes?
1 1/2" --> 38mm
71
When applying a water test to a part of the drainage system:
a 10 ft head must be created
72
Where does a fixture drain start?
at the trap weir
73
A building sewer which conducts both sewage / storm water is called a?
combined building sewer
74
A wet vent pipe acts as a/an ___ pipe and also a/an ____ pipe:
waste / vent
75
What is the largest size pipe that can be hung w/ perforate steel strap?
4"
76
What is the min size of a wet vent that serves a water closet?
2" (50mm)
77
An individual vent becomes a stack vent when:
a fixture drain extends through at least one complete storey
78
What would happen is the fall on a trap arm was more than one pipe diameter?
the trap may self-siphon
79
What is the min distance that a vent can terminate above a balcony?
2m 6 ft
80
What is the portion of the fixture drain bn the trap weir and the vent pipe fitting?
Trap arm
81
A properly piped wet vented group of fixtures that includes a water closet:
Must have the water closet piped as the lowest vented fixture
82
What is the max allowable change of direction bn a c/o and the pipe that it serves?
135 degrees
83
On a building drain you cannot exceed ____ degrees bn c/o?
45 degrees
84
When sizing the vertical portion of the wet vent, do not include the fixture unit load of the connected fixture?
Lowest (most downstream)
85
What connects the waste opening of a fixture to the trap serving the fixture?
fixture outlet pipe
86
Which vent pipe that is an extension of the soil or waste stack above the highest horizontal drain connected to the stack?
stack vent
87
The combined wastes from a lavatory / a single compartment sink are used to wet vent a 3" water closet. The wet vent size should be?
2"
88
A fixture drain piped to a drain through one complete storey min is called a:
soil or waste stack
89
Rain water leader sizing is based on rainfall volume in ____ over a period of 15 min:
mm
90
What is the min size for a circular rainwater leader?
2"
91
For conversion of a fixture unit loads to litres for pipe sizing purposes, 260 FU or less is equal to ____ L?
2360
92
When the number of FU exceeds 260 FU, the load is ____ litres from each fixture unit
9.1
93
A pump rated at 10 gallons per min would add a load to the combined sewer ____ liters
681 45 x 15 min = 681L
94
How many fixture units are allowed to connect to the vent stack?
8
95
How high must a building be before a vent stack is required? 2.5.4.2 (1)
5 storeys "More than 4 storeys"
96
How is a bathroom group sized when tied in to the vent stack?
wet vent
97
How far above the floor level of the lowest storey of the section the yoke vent shall be connected to the vent stack?
1m
98
Yoke vents are required on buildings of what height?
12 storeys (more than 11 storeys)
99
What is the min size of a fresh air inlet?
4"
100
When circuit venting 3 drinking fountains, what would be the size of the fixture drain immediately downstream of the circuit vent connection?
2"
101
What are the NPC intended for?
- ensures the quality / functionality of plumbing installations - protects the health of the occupants / general public - Protects building structure from damage caused by improper piping installation.
102
What does AHJ mean?
Authority having Jurisdiction
103
When does testing + inspection need to be done?
Once piping rough-in has been completed (ground work or above grade) (piping needs to be under a test while being inspected)
104
What are the 4 main tests that may be performed on a DWV system?
- Water pressure tests - Air pressure tests - Final tests - Ball tests
105
How much water column must be applied to all joints?
3m (10')
106
How long does a test need to be done for?
15 min
107
How much pressure does a air pressure test need?
35 kPa (5 psig)
108
For final tests, what water column must be maintained for 15 min?
25 mm (1")
109
When a pipe is 3" or more, what size of ball is used for a ball test?
min 2" (50mm)
110
When a pipe is 3" or less, what size of ball is used for a ball test?
1" (25mm)
111
What is this?
A drop head auger
112
What is a drop head auger used for?
For cleaning the trap arms of fixtures mounted back-to-back
113
What is this?
A spade cutter
114
What is a spade cutter used for?
Following up after augers have been used / to open up floor drains
115
What is this?
A shark-tooth cutter
116
What is a shark-tooth cutter used for?
For cleaning pipes of general material clinging to pipe walls
117
What is this?
A grease C cutter
118
What does a grease C cutter used for?
For grease blockages in lines leading from garbage disposal units or waste pipes
119
What is the best tool to use when you suspect that a building sewer is frozen b/c it isn't buried deep enough?
A steam cleaning machine