Electrical Installation Design Flashcards
What key factors must be considered in assessing supply details for an electrical installation design?
Live conductors, current, prospective fault current, and earthing arrangement
In a typical single-phase 230 V supply in the UK, how many live conductors are there?
Two
In the UK, what is the voltage for three-phase supplies without a neutral conductor?
400 V
Why are three-phase supplies preferred for larger installations requiring more than 100 A of power?
They are more energy-efficient.
What does the term “nominal voltage” refer to in electrical installations?
The voltage measured between live and earth in the UK
How does the real voltage in an installation relate to the nominal voltage?
The real voltage is always lower than the nominal voltage.
Which type of conductor arrangement is common in larger retail outlets and larger commercial or industrial buildings in the UK?
Three-phase with a neutral
What is the maximum current rating typically associated with small domestic-type installations in the UK?
100 A
In a three-phase and neutral supply in the UK, what are the voltages for line-to-neutral (L-N) and line-to-line (L-L)?
L-N: 230 V, L-L: 400 V
Which type of conductor arrangement is not very common in the UK due to the requirement for all circuits to be three-phase balanced loads?
Three-phase 400 V
According to UK regulations (BS 7671), where can you find diagrams of various conductor arrangements?
Chapter 31
What does the term “external impedance” refer to in the context of earthing arrangements?
Resistance between the installation and the substation transformer
why is it essential to know the supply details before designing an electrical installation?
To ensure the safety of the installation
In the UK, what is the primary difference between a single-phase 230 V supply and a three-phase 400 V supply?
The number of live conductors
What is the purpose of a neutral conductor in a three-phase and neutral supply (L-N : 400 V L-L) in the UK?
To balance the phases and carry unbalanced current
In an electrical installation located far from the substation transformer, how does the distance impact the real voltage compared to the nominal voltage?
The real voltage is lower as distance increases.
What is the purpose of using nominal (normal) values in electrical calculations?
To account for voltage variations due to demand and distance
Which of the following is NOT a common type of conductor arrangement in the UK?
Four-phase
What is the primary reason for using a three-phase supply for larger installations?
It provides better voltage regulation.
What is the maximum demand typically associated with most average-sized houses in the UK?
Less than 100 A
In larger installations with a maximum demand over 100 A, what is often used to distribute the load in the supply?
Three-phase supply
When a building needs a supply over 400 A per phase, what may be installed on-site to provide the required capacity?
A substation transformer
What factors govern the maximum demand for an electrical installation?
The size of the incoming supply cables
Why is it essential to check the supply capacity when adding to an existing electrical installation?
To prevent overload and ensure safety