Flame rectification is a process by which:
An electrical current passes through a flame
What commonly causes the problem of having to relight the pilot and condensation on windows?
A cracked heat exchanger
How would you correct the short cycling problem in a furnace without a heat anticipator?
Adjust the thermostat cycle rate per the furnace manufacturer’s instructions
What instrument do we use to measure gas pressure with?
Manometer
Name 3 types of igniters used in gas furnaces.
Spark igniter, hot surface igniter, intermittent pilot
What could cause a furnace to stay on too long and create cold drafts?
No humidifier installed
True or False? When venting a Category I furnace, best results can be obtained if Type B, double wall pipe is used for the vent and vent connector.
True
What precaution must be taken during the installation of Category IV (condensing) furnaces?
Make sure the vent pipe slopes back toward the furnace
What must be done if manifold pressure cannot be adjusted to fire the burners at the correct input?
Replace orifices with ones a size larger or smaller
What should you do if the pilot flame is yellow and soot has accumulated around the pilot assembly?
Disassemble and clean the pilot assembly
What is the first major event in the ignition sequence of an induced combustion furnace?
The energizing of the spark ignition module
True or False? For correct natural gas system operation, burner manifold pressure must be set at 3.5 inches w.c.
True
Which troubleshooting step for spark re-ignition is incorrect?
Check for spark with screwdriver
Can a glow coil remain energized continuously without risk of burning out?
False
Most glow coils require an adjustable resistor in series to:
Increase glow coil temperature
Put these steps in the proper sequence for direct burner ignition:
Purge combustion chamber with inducer fan for 15 seconds
Energize hot surface igniter for 17 seconds
Energize gas valve for 5 seconds
Check flame sensor for next 2 seconds
In an atmospheric gas burner, the presence of a yellow or orange flame indicates:
Not enough primary air
What does the equation [CFM = Btuh / (1.08 × Temp rise)] determine?
System airflow
Where is manifold pressure on a gas furnace measured?
Between the gas valve outlet and the orifice
What is the most likely problem if the pilot is lit but the main gas valve will not open?
The limit switch contacts are closed
What would a heat anticipator set to ‘longer’ most likely cause?
Short blower ‘on’ cycles
One cubic foot of LP gas (propane) contains _____ BTU’s of heat energy than one cubic foot of natural gas.
More
Where is the secondary or auxiliary limit switch located?
In the blower compartment of a downflow furnace
Almost all burner problems are caused by improper ___________.
Primary air