In terms of the HART digital communication signal, which value represents a
logical “1”
1200Hz
The maximum cable length for Foundation Fieldbus is H1 network, using type “A”
cable is
1900 meters
Which of the 7 OSI layers is NOT used in both wireless and wired HART?
Session Layer and Presentation Layer
Which method of communication arbitration does HART utilize?
Master/Slave with token passing between primary and secondary masters
In terms of HART digital communications, what is it’s Baud rate?
✓ 1200bps
These are the 2 framing methods of serial Modbus
ascii and rtu,
What is the value of the Foundation Fieldbus Terminator resistor/capacitor in
Ohms/Farads respectively?
100 ohms and 1 micro farad ✗ (100/1)
What is the IEC# or standard of manchester encoding that the Profibus-PA, and
Foundation Fieldbus H1 Physical layers are based on?
IEC-61158-2
Between the start and the end of a Modbus ASCII message, what field order is
the data framed?
Address > Function > Data > CRC
The data transfer rate of Foundation Fieldbus HSE is:
10/100 Mbps
The communications relationship in Foundation Fieldbus used for device
alarming/broadcasting is:
Report Distribution
Modulation technique of Foundation Fieldbus HSE?
Manchester Encoding
What is the 2 fundamental differences between Foundation Fieldbus and other
protocols?
peer to peer communications, devices execute the control algorithm,
devices run the programs
What is the physical layer of Profibus-DP Physical layer based on? Think 2 wire
version.
RS-485
Which layers of the OSI stack does serial MODBUS protocol use?
Physical, Data Link, Application
What Coil/Register number range do Analog Input registers use?
30001 – 39999
What is the maximum segment length for Profibus PA, utilizing type A cable?
1900 m
What does HART stand for?
Highway Addressable Remote Transducer
What media access method does MODBUS TCP utilize on an Ethernet network?
Master/Slave with CSMA/CD
This layer 7, data concentrator is used for wireless HART networks
GATEWAY, WIRELESS GATEWAY
What is the MINIMUM circuit impedance required in the physical signal line to
ensure the HART protocol, physically communicates properly?
230 Ω
What type of protocol is used for the upper 3 layers in Ethernet IP?
Common Industrial Protocol
This “8th layer” is how the host platform formats the digital data being received
from the device at physical layer
PROFILE
This error checking method of MODBUS, utilizes a 17 variable polynomial
cyclic redundancy check