FINAL TEST Flashcards
(116 cards)
What is the minimum diameter sheave (pulley) that is required for a 900 pair cable, 2.75” in diameter, if the bend radius for a multipair in 10 x OD?
Select one:
A.
27.5 inches
B.
13.75 inches
C.
55 inches
D.
43.2 inches
The correct answer is: C
55 inches
What does this OTDR trace indicate?
Select one:
A. Non-reflective fiber break
B. Reflective end with negative loss
C. Reflective fiber break
D. Reflective end with positive loss
The correct answer is: A
Non-reflective fiber break
In a patch cord, what is the alternate colour of pair #1?
Select one:
A. Green-red
B. Blue-orange
C. Brown-slate
D. Black-yellow
The correct answer is: A
Green-red
What value of dB represents a doubling of power?
Select one:
A.
2 dB
B.
4 dB
C.
6 dB
D.
3 dB
The correct answer is: D
3 dB
A 1900 m link of singlemode outdoor fiber operating at 1310 nm has 2 mechanical splices and 2 mated connectors. The component losses are as follows:
Fiber loss = 0.5 dB/km
Splice loss = 0.3 dB
Mated pair connector loss = 0.75 dB
What is the total loss of this link?
Select one:
A.
2.30 dB
B.
3.65 dB
C.
3.05 dB
D.
4.55 dB
The correct answer is: C
3.05 dB
What will happen to channel attenuation when a 62.5 µm fiber patch cord is connected to a 50 µm fiber?
Select one:
A.
Attenuation will be higher when the source is connected to the 62.5 µm fiber
B.
Attenuation will be higher when the source is connected to the 50 µm fiber
C.
Attenuation will be higher only when operating at 850 nm
D.
Attenuation will be higher only when operating at 1300 nm
The correct answer is: A
Attenuation will be higher when the source is connected to the 62.5 µm fiber
According to ANSI-568-C.2 standard, which of the following is a required certification field-test parameter?
Select one:
A.
Resistance
B.
Impedance
C.
ACR
D.
Return Loss
The correct answer is: D
Return Loss
Installed on a CEA-310-E compliant 19” rack is the following equipment:
3(three) - Horizontal cable management panels, 19” x 1-3/4”
2(two) - Switch, 19” x 5-1/4”
2(two) - Modular pacth panels, 19” x 3-1/2”
How many rack units does all this equipment occupy?
Select one:
A.
17 rack units
B.
13 rack units
C.
7 rack units
D.
11 rack units
The correct answer is: B
13 rack units
How much shorter will the maximum permanent link length be when using 28 AWG ‘small conductor” cords with a derating factor of 92%?
Select one:
A.
82.8 meters
B.
92.0 meters
C.
99.2 meters
D.
82.5 meters
The correct answer is: A
82.8 meters
an OSP cable connecting two buildings has the following colours identifying the last pair.
Black superbinder
Violet-brown binders
Violet-slate pair
What is the minimum number of 250-pair terminal blocks and the minimum number of 25-pair connector blocks required to terminate both ends of this cable?
Select one:
A.
6 terminal blocks and 48 connector blocks
B.
15 terminal blocks and 144 connector blocks
C.
16 terminal blocks and 144 connector blocks
D.
5 terminal blocks and 48 connector blocks
The correct answer is: C
16 terminal blocks and 144 connector blocks
Which statement regarding NEXT is true?
Select one:
A.
Crosstalk is greatest at the near end (at the sender end)
B.
NEXT is only measured near the center of the link-under-test
C.
Length is a factor of NEXT
D.
NEXT measures the crosstalk on the link-under-test as the signal is measured at the receiving end
The correct answer is: A
Crosstalk is greatest at the near end (at the sender end)
According to the TIA-568.0-D standard, what is the maximum amount of conductor untwist for a Cat.3 cable?
Select one:
A.
0.5 inches
B.
0.3 inches
C.
3 inches
D.
1 inch
The correct answer is: C
3 inches
According to ANSI-568.0-D standard, what is the maximum installation pull/tensile load for a 4-pair cable?
Select one:
A.
25 lbf.
B.
100 lbf.
C.
50 lbf.
D.
75 lbf.
The correct answer is: A
25 lbf.
According to the ANSI-568.3-D standard, what is the identifying colour of a laser optimized optical fiber SC connector?
Select one:
A.
Beige
B.
Blue
C.
Aqua
D.
Green
The correct answer is: C
Aqua
According to the TIA-569-D standard, what is the maximum allowable distance between non-continuous cable supports such as “J” hooks?
Select one:
A.
4 ft
B.
5 ft
C.
3 ft
D.
2 ft.
The correct answer is: B
5 ft
What size of mechanical splice devices are required to splice a loose tube cable to a breakout cable?
Select one:
A.
125 µm - 250 µm
B.
125 µm - 900 µm
C.
250 µm - 900 µm
D.
250 µm - 250 µm
The correct answer is: C
250 µm - 900 µm
What equipment is needed to find the length of copper cable on a reel?
Select one:
A.
Wire map tester
B.
Interferometer
C.
Impedance tester
D.
Time domain reflectometer
The correct answer is: D
Time domain reflectometer
What is the minimum number of BBC’s (a.k.a., ground equalizer [GE]) required in a ten story building with two TRs per floor?
Select one:
A.
3
B.
4
C.
7
D.
10
The correct answer is: B
4
What does this OTDR trace indicate?
Select one:
A.
Reflective end with positive loss
B.
Non-reflective fiber break
C.
Reflective end with negative loss
D.
Reflective fiber break
The correct answer is: D
Reflective fiber break
An EF is located 20 meters from the exterior edge of a building. How many meters of non-FT rated outdoor fiber cable be installed into the EF?
Select one:
A.
In 5 meters of EMT
B.
In 17 meters of rigid conduit
C.
In a cable tray
D.
On J hooks
The correct answer is: B
In 17 meters of rigid conduit
When viewed from the front of the patch panel, how are the WA cables routed on a two row 48-port hinged patch panel, that hinges towards the left?
Select one:
A.
All 48 cables are routed to the right side of the patch panel
B.
All 48 cables are routed to the left side of the patch panel
C.
Cables 1 to 12 and cables 25 to 36 are routed to the left side of the patch panel. Cables 13 to 24 and cables 37 to 48 are routed to the right side of the patch panel
D.
Cables 1 to 24 are routed to the right side of the patch panel and cables 25 to 48 are routed to the left side of the patch panel
The correct answer is: B
All 48 cables are routed to the left side of the patch panel
According to ANSI/TIA-568.3-D, which is correct duplex fiber patch cord configuration?
Select one:
The correct answer is: A
What size is the PBB (TMGB)?
Select one:
A.
0.25” x 2” x 19”
B.
0.25” x 2” x variable length
C.
0.25” x 4” x variable length
D.
0.25” x 4” x 24”
The correct answer is: C
0.25” x 4” x variable length
According to the ANSI-568.3-D standard, how is a MM SC connector differentiated from a SM SC connector?
Select one:
A.
The MM connector is colour-coded orange and the SM connector is colour-coded yellow
B.
The MM connector is colour-coded grey and the SM connector is colour-coded yellow
C.
The MM connector is colour-coded beige and the SM connector is colour-coded blue
D.
The MM connector is colour-coded beige and the SM connector is colour-coded yellow
The correct answer is: C
The MM connector is colour-coded beige and the SM connector is colour-coded blue