Gas line sizing Flashcards
NPS stands for?
(Nominal pipe size) As the pipe gets stronger the wall thickness increases and the inner diameter decreases
Consideration when sizing a gas line?
- Type of fuel
- Length of piping (longest run)
- Individual branch loads
- Maximum flow capacity
- Type of materials to deliver the gas
- Within allowable maximum pressure drop
Where is the gas load for the appliance determined from?
Gas load for the appliance will be determined from the rating plate
Maximum pressure drop Natural gas?
1 inch WC
Maximum pressure drop Propane?
1 inch WC
If pressure drop exceeds the maximum?
The gas line is probably undersized and a larger line may need to be installed
What type of gas piping materials can be used?
Steel
Cooper
Polyethylene (plastic)
What schedule of black iron pipe is most commonly used for gas connections?
Pipe-schedule 40 steel.
For residential it is threaded and rated for a maximum of 125 psi
What is the minimum diameter for threaded pipe used for natural gas, unless it is schedule 80?
Threaded pipe for natural gas must not be smaller than 1/2 inch diameter unless it is schedule 80
When can pipe used for propane be smaller than 3/8 inch?
Pipe used on propane may be smaller then 3/8 inch if it is used for a branch line to a single appliance no longer than 25 feet.
What type of fittings are to be used with steel pipe?
Steel or malleable iron fittings are to be used with steel pipe
What is the maximum size of steel pipe that can be threaded in a gas piping system?
Maximum size steel pipe that can be threaded in a gas piping system is 2”
What materials can tubing be made of?
Tubing can be cooper or steel
How can copper be joined, and what must it be pressure rated for?
Cooper can be joined by flaring, brazing or compression fittings and must be pressure rated for 125 psi
Types of cooper:
Type K used for?
Underground gas, oil and water lines as well as plumbing and HVAC above ground, very thick wall
Types of cooper:
Type L used for?
Plumbing and heating systems, medium wall thickness
Types of cooper:
Type M used for?
Water distribution systems, heating and sprinkler system, thin wall
Types of cooper:
Type G used for?
All above ground and indoor natural gas and propane installations
Plastic pipes used for?
Outdoors, underground. Is joined using thermal fusion or compression. Tracer wire required. Does’t work with liquid propane.
Hose minimum rated working pressure for hose and hose fittings?
350 psi
Maximum length of hose on a permanent installation?
10’
Minimum length of hose on a construction heater?
15’
Maximum length of hose on a portable appliance (BBQ)?
30’
How must CSST be protected if run inside a wall?
CSST (corrugated stainless steel tubing) if run inside a wall must be protected from damage using protection plates