When making correction on Grid map for private or non county hydrants use what color ink?

A

Green

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What is a map depicting roads, hydrants, numbers and other landmarks either strip or grid?

A

Response Map

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Who shall conduct inspections or test of new hydrants

A

Regional Fire Prevention or Special Units

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q
  1. Hydrant is ____ behind curb line
A

12”-24”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q
  1. Center of lowest outlet is ___ above the curb
A

14” -24”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

____degrees to the curb for single hydrant

A

90

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

____degrees to the curb for double hydrant

A

45

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

___ coats of ___primer one ____traffic signal paint

A

Two; red

One; Yellow

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What should be used to note repairs or obstructions to hydrants

A

Form 410

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

A Damaged Fire Hydrant Notification Form 21 should be filled out for all hydrants except?

A

Private

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

When cul-de-sac depth exceeds what for commercial and residential mid block hydrants are required?

A

200’ commercial and 450’ residential

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

The available flow of hydrant is calculated by?

A

Testing the static pressure and residual pressure of the hydrant

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

The FDC shall be installed on the address side of the structure with vehicular access and how far from a
hydrant?

A

150’

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Fire hydrant spacing for single family dwellings?

A

600’

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

Hydrant spacing for single family dwellings with more than 1 home per acre hydrant spacing will be?

A

450’

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

Non urban properties no part of the structure will be more than what from a hydrant?

A

750’

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
17
Q

All occupancies other than single family dwelling shall be no less than?

A

300’ from a hydrant

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
18
Q

What buildings qualify for the maximum spacing of hydrants of 600’?

A

Sprinklered

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
19
Q

For non sprinklered buildings hydrant distance should be?

A

400’

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
20
Q

All hydrants shall flow what gpm at what psi for how long?

A

1250 gpms at 20 psi for 2 hours

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
21
Q

If there is more than 1 on site hydrant the only difference is there shall be

A

2500 gpms

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
22
Q

All hydrants shall be installed how far from a building?

A

25’ or have a 2 hour fire wall

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
23
Q

When the required fire flow exceeds what does a wharf hydrant need to be replaced with 4” x 2”?

A

1250gpm

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
24
Q

Unless the required fire flow is less the minimum flow from a hydrant shall be?

A

1000 gpm

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
25
No walls, barricades, fences, landscaping etc. shall be placed within?
3’ of hydrants
26
314. All on-site hydrants must have a shut-off valve located?
Minimum of 10’ maximum of 25’
27
What color are on site hydrants painted?
Red
28
Public underground hydrant shut off’s are located how far from the hydrant?
Min 10’ max 25’
29
Any building in excess of 150’ from a water supply shall
have an onsite hydrant
30
Credit for automatic sprinklers and other protective equipment should be limited to?
750 GPM
31
FDCs shall be located at least how many feet from a structure?
25
32
A sprinkle system shall be monitored either by panel or outside agency w/ alarm for how many sprinklers?
100 | Exception is 20 or more for Group 1, Division 1.1 and 1.2 occupancies
33
System piping shall be hydrostatic testes at what psi for how long on all systems with 20 or more heads?
200 psi or 50 psi over max operating Max operating pressure whichever is greater for 2 hours
34
Appointments for inspections or test shall be made with the Fire Prevention Division how many days ahead?
2
35
All sprinkler plans shall include a Fire Flow Form 196 obtained within 1 year of the submittal date and signed by whom?
Official of the Water Company or Department Fire Prevention Division
36
The minimum allowance for coverage of a sprinkler head is?
15 gpm and 15 – 25 gpm range
37
What is the minimum amount of pressure and lines to an automatic sprinkler?
1 2 ½ and maintain 150 psi
38
561. All FDC connections shall be used?
shall be connected to and charged
39
If an FDC can’t be at least 25’ from a structure what has to happen?
A 2 hour fire wall and no opening 25’ both | directions.
40
Systems that demand 2000 gpm or more require?
6-2 ½” Siamese into 6” pipe with 6” check
41
The FDC shall be installed on the address side of the structure with vehicular access and how far from a hydrant?
150’
42
In a multi story building (including basements) over three stories you must have? (4 things)
1. Indicating control valve 2. Water flow detector with an alarm bell 3. Drain Valve 4. Inspector test valve
43
What buildings qualify for the maximum spacing of hydrants of 600’?
Sprinklered
44
For non sprinklered buildings hydrant distance should be?
400’
45
330. When may sprinklers may be omitted from garages?
1 One hour fire resistant wall 2. Heat detector in garage is wired to sprinkler alarm device 3. Residence not located in the Very High Fire Hazard Severity Zone
46
Fire Sprinklers are required and shall be designed for all what type of occupancy
group 2 occupancies
47
When a maximum system pressure exceeds 125 a system shall have what on the system side of the riser check?
¼” relief valve set to 175 psi
48
Is a license required to maintain a sprinkler system
? No
49
How often are stand pipe and sprinkler systems serviced?
5 years
50
** Hydrostatic testing is conducted on all structure with haw many sprinklers?
20 or more
51
Class “A” foam shall not be added to fixed water systems such as Tanks, Standpipes, and Sprinklers T or F
T
52
What is a Class I system? standpipe
Dry standpipe with no water source and 2 ½” outlets for use by F.D
53
A combination system? standpipe
Has 2 ½” F.D. outlets and supplies the sprinkler systems
54
A class III system? standpipe
A system directly connected to a water supply with 2 ½” and 1 ½” outlets
55
A class II system? standpipe
A wet standpipe system with a water source and 1 ½” outlets for occupant use
56
When connecting to a vertical standpipe connect to what outlet first?
The lower
57
**On the metro blue line what type of standpipe system exists?
A dry system with a double 2 ½” outlet at ground level and 1 2 ½” outlet on the platform
58
A Class 1 standpipe is a standpipe with ___ outlets
2 ½”
59
Class II standpipes shall be located so that all potions of the building are within
30’ of a nozzle on 100’ of hose
60
Every building 4 stories or more shall provide 1 standpipe for use during
construction
61
Standpipe shall be installed when construction is over
35’ high
62
All occupancies will be sprinklered except
Group U and R Division 3
63
Storage shall be a minimum of ___ from the ceilings of non sprinklered buildings and ___ below sprinklers in sprinklered buildings
2’; 18”
64
A deluge system is normally equipped with system
open sprinkler and a deluge valve and separate detection
65
What are the 5 major types of sprinkler systems?
``` Wet pipe dry pipe pre-action deluge residential ```
66
When connecting to a sprinkler or standpipe system with inlets in a vertical position, connect to ______ inlets first.
Lower
67
**Private Hydrant within 25'
2 hr fire wall
68
**Standpipes should be inspected
6 months semi annually
69
**On the metro blue line what type of standpipe system exists ho wmany 2 1/2 connections?
2