lesson 3: electrical standards and codes Flashcards

(69 cards)

1
Q

documentation that is used to determine the proper method for electrical equipment installation in the field is categorized as what

A

standards and codes

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

what term indicates that an electrical equipment has been constructed and tested so that moisture will not enter the equipment

A

Watertight

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

who ensures that the electrical installation process is performed within proper safety and code requirements

A

AHJ (authority having jurisdiction)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

NEMA standards are typically used in installations for sizing what

A

Motor starters

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

what can result in a large magnitude current flow in the ground path

A

Ground fault

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

the width of working space in front of the electrical equipment must be either that of the equipment, or ___’, whichever is greater

A

2 1/2’

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

NETA is an acronym for what

A

InterNational electrical testing association

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

an ANSI approved standard is developed based on input from various experts from applicable ___?

A

Industries

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

energized components that operate at ___v or more must be guarded against accidental contact

A

50v

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

what are used throughout the NEC to explain information that is contained in the various articles

A

Fine print notes

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

a ___ installation is an installation that the AHJ has reviewed, including conductors, equipment, and installation, and concluded to be acceptable

a. approved
b. labeled
c. acceptable
d. listed

A

approved

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

the IEEE produces how many standards

A

1100

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

an official description for equipment that has been constructed, protected, or treated so that rain does not interfere with the successful operation of the equipment under specified test conditions

A

Rainproof

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

A ___ is an accepted reference or practice

a. standard
b. code
c. listing
d. method

A

Standard

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

for 151v to 600v equipment under a grounded condition, the minimum working space clearance requirement is how many feet

A

3 1/2’

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

In the NEC, exceptions are permitted instead of the main rule when____

A

all provisions of the exception are met

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
17
Q

to assist in the proper application of the NEC, terms that are used in two or more articles, are defined where

A

NEC article 100 (definitions)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
18
Q

If a location is normally dry but is temporarily subject to moisture, it can be classified as what type of location

A

dry

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
19
Q

the final approval for the conductors and equipment installed must be given by who

A

AHJ (authority having jurisdiction)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
20
Q

what is a sustained discharge for electricity across a gap in a circuit or between electrodes

A

an arc

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
21
Q

what is provided for an installation that protects electrical equipment

A

dedicated equipment space

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
22
Q

the minimum clearance depths range from ____ to ____ for systems operating above 75 kv

A

3’ to 12’

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
23
Q

as with labeling, ___of a product certifies that the equipment has been evaluated by a testing agency suitable for the AHJ

A

listing

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
24
Q

an excessive amount of current present as the result of little or no resistance between conductors, is called what

A

short circuit

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
25
the NEC requires that a minimum length of ___" of free conductor be provided at each outlet for splices and terminations
6"
26
defective equipment, overloaded equipment, or too many loads on one circuit can cause what
an overload
27
what is the case or housing that surrounds an apparatus/equipment called
an enclosure
28
motor starters are sized by the classification "___"
NEMA sized starter
29
overcurrents are caused by, overloads, short circuits and what else
ground fault
30
most jurisdictions adopt the ____ as the model building code for their jurisdiction
IBC (international building code)
31
This national organization focuses on the interpretation of the NEC and teaches safe installation and use of electricity
IAEI (international association of electrical inspectors)
32
___ is the organization, office, or individual who is responsible for approving the equipment and materials used for electrical wiring installations
AHJ ( authority having jurisdiction)
33
who's purpose is it to practice safeguarding persons and property from the hazards arising from the use of electricity
the NEC
34
this type of voltage has a value assigned to a circuit or system to designate its voltage class
nominal
35
what chapter of the NEC applies to communication systems
chapter 8
36
the ____ are standards developed by NECA in partnership with other industry organizations
NEIS (national electrical installation standards)
37
where in the NEC book would you look to find/determine the maximum number of conductors that can be installed in a raceway
Annex c: tables
38
measuring most voltages in commercial and industrial buildings requires the use of a category ____ test instrument as a minimum
CAT III (3)
39
in order to become an enforceable law, ____ must be adopted by a jurisdiction such as a local county, parish, or state authority
code
40
where it has been adopted, the ____ applies to all types of structures, EXCEPT for single and two family dwellings, which are covered by a different code
IBC (international building code)
41
the official description for equipment that has been constructed, protected, pr treated so that exposure will not allow the entrance of water during a beating rain under specified test conditions
Raintight
42
what is installed to prevent personnel from accidentally contacting energized parts or to protect equipment from physical harm
an enclosure
43
this type of equipment converts electrical energy, into a useful form of energy, such as motion, heat, or light
utilization equipment
44
T or F premises wiring is only installed in permanent systems
False premises wiring is installed in BOTH temporary and permanent systems note: premises wiring DOES NOT include internal wiring to equipment such as motors, motor control centers, and appliances
45
T or F rather than using the latest version, some municipalities require compliance with an earlier version of the NEC
True
46
T or F NEMA publishes over 800 standards for the electrical industry
False NEMA publishes 500 standards
47
T or F electrical codes can be amended by a particular jurisdiction such as a state or municipality
True
48
T or F OSHA is a suitable testing agency
False recognized testing agencies are as follows: UL(underwriters laboratories inc) - being the most recognized MET laboratories inc. Intertek FM GLobal (Factory Mutual) and CSA (Canadian Standards Association)
49
T or F ANSI develops electrical standards and oversees the standards writing and approval process
False ANSI does NOT develop electrical standards BUT does oversee the standard writing and approval process
50
T or F NEC requirements typically do not appear on the prints used for electrical installations
True
51
T or F The NFPA 5000 and I-codes are updated every 5 years
False they are updated every 3 years
52
T or F The higher the AWG value, the greater the cross sectional area and the heavier the conductor
False the SMALLER the number the greater cross sectional area and heavier the conductor is ex: a 10g wire cross section is 5.26mm squared VS a 14 gauge wire cross section is 2.08mm squared
53
T or F permises wiring does not include internal wiring to equipment such as motors, motor control centers, and appliances
True
54
T or F underground installations and those in direct contact with the earth are classified as damp locations
False such installations are classified as wet locations- wet locations are subject to water or other liquids damp locations are subject to moderate degrees of moisture(like basements indoors), generally out of the weather but can be outdoors if the location is partially covered
55
T or F per the AHJ, visual imperfections of an installation can result in failure of a final inspection and require rework
True main criteria that the AHJ reviews when making an approval are: 1. conformance to the requirements of the NEC and any other applicable local building codes and standards 2. quality and suitability of equipment installed (ex: no significant dents or damage that may affect the structure or function of equipment) 3. professionalism of electrical work performed , emphasizing on NEC's phrase "neat and workmanlike manner" (ex: are conduit runs straight, are openings in boxes plugged, conductors properly racked for future access etc.)
56
T or F Electrician licensing requirements for the NEC vary, depending on each states' governing body
True
57
T or F a standard is typically an enforceable law
False only when adopted can a code be an enforceable law
58
T or F because most standards are not readily accessible on a jobsite, working knowledge of applicable standards is necessary when performing installations
True working knowledge includes, knowledge of which standards are available, information they contain, and publisher information so that they can be obtained if necessary obtaining all applicable codes and standards for a particular installation is not necessary, but may need to be occasionally obtained for supplemental information
59
T or F a conductor with insulation rated for dry and damp locations cannot be placed in a wet location even if it is inside of a conduit listed for wet locations
True all conductors, raceways, supporting equipment etc. must all be listed for whichever location it is to be installed in
60
T or F The IBC (I-codes, International building code) is a code administered by the IEC (international electrotechnical commission)
False the IBC is maintained by the international code council (ICC). The ICC is a family of 15 related building codes (I-codes), such as the international plumbers code(IPC) and the international mechanical code(IMC) as examples
61
T or F plumbing or ventilation duct work is permitted in dedicated electrical spaces
False there can be NO foreign systems that are not associated with the electrical equipment, and cannot be violated by any other installations HOWEVER, there is one exception, suspended ceilings are allowed within the 6' above electrical equipment, and foreign systems(plumbing, ventilation etc.) are allowed above the 6' dedicated equipment space but they must have a leak protection apparatus to prevent leakage or moisture from dripping on electrical equipment.
62
T or F Disconnecting means identification is placed on equipment before the installation is completed
False identification is performed after the equipment installation is complete. identification MUST be durable enough to withstand the environment that the installation is exposed to.
63
what are at least 10 requirements AHJ looks for when inspecting a job site for "Neat and workmanlike manner"
1. conduit bends meet NEC requirements 2. conduit runs are plumb, level, true, and not kinked 3. conduit is supported within the specified distance from a box (within 3' from a box) 4. connectors are securely fastened 5. covers are properly secured 6. installation surfaces are free of paint, plaster, and other contaminates 7. conduit offset bends are made as required (Bends in a single run cannot exceed 360 degrees before a pull point is installed) 8. proper sized boxes are securely mounted and level 9. proper sized conduit and conductors are installed (conductor fill rate in conduit cannot exceed 40%) 10. Unused openings in boxes are plugged
64
what is the "flash hazard boundary" when referring to arc flash protection warning tags
it is the distance from arc required to limit skin temperature to a curable burn
65
what does it mean on an arc flash protection warning tag if you see "3 cal/cm(squared) flash hazard at 18""
3 cal/cm(2) is the heat energy at 18" from an arc
66
what does the "limited approach" mean on a arc flash protection warning tag. ex. 36 inch limited approach
the specified distance that an unqualified person can be to the arc flash hazard. the only exception to this is if the unqualified person has on the appropriate PPE and is also under the direct supervision of a qualified person.
67
as an example; what does "12 inch restricted approach- 500v class 00 gloves" mean on an arc flash protection warning tag
12 inches is the skin protection boundary, and the rated PPE required
68
what would "480 VAC shock hazard when door is open" mean on an arc flash protection warning label
it is the shock potential
69
where might the equipment name on an arc flash protection warning label, be
at the bottom