PEC Flashcards
(135 cards)
Conductors and equipment for delivering energy from the serving utility to the wiring system of the premises served.
- Service Line
- service drop
- service conductor
- service
Service
How many service should be in building or other structure?
One
A structure that stands alone or the is cut off from adjoining structures by fire walls
Building
Service conductors made up in the form of cable
Service Cable
the underground service conductors between the street main
Service Lateral
Minimum size of underground conductor
8mm^2
The overhead service conductors from the last pole or other aerial support
Service Drop
the conductors from the service point to the service disconnecting means
Service Conductors
the point of connection between facilities of the serving utility and the premises wiring
Service Point
the service conductors between the terminals of the service equipment and a point usually outside the building
SEC as Overhead System
The service conductors between the terminals of the service equipment and the point of connection to the service lateral
SEC as Underground System
Service drop conductors not in excess of 600 volts shall have a minimum clearance of _____ feet over residential property and driveways and those commercial areas not subject to truck traffic.
12
Each service drop or service lateral shall supply one how many set of servuce entrance conductors
One
The raceway that encloses the service entrance conductors
Service Raceway
the necessary equipment usually consisting of circuit breakers, or switches and fuses
Service Equipment
When re-routing conduit, ut may be necessary to increase the wire size, if the distance is greater in order to _________
compensate for voltage drop
The minimum size service lateral to a bramch circuit limited load is ________ copper.
8
Of the two to six service disconnecting means in a panel only a disconnect used for ____________ permitted to be remote from other disconnects.
a water pump intended for fire protection
Give the minimum vertical clearance from finished grade of a service drop conductor installed between buildings on residential properties and driveways.
3000 mm
When the voltage between service conductors does not exceed 300 v and the roof has a slope of not less than 100mm, the clearance can be reduced to
900mm
the maximum clearance for service drops over buildings
9 feet
service conductors passing over roofs must have a clearance over the roof which they pass of:
2400 mm
A ________ refers to the circuit conductor between the service equipment and the branch circuit over current device.
feeder
Service using copper conductors shall have sufficient capacity and shall NOT smaller than
8.0 sq. mm.