State the setpoint, actuation, and instrument for the following:
Variable Over Power Trip
State the setpoint, actuation, and instrument for the following:
Hi Log Power
State the setpoint, actuation, and instrument for the following:
Hi Local Power Density
State the setpoint, actuation, and instrument for the following:
Low Departure from Nucleate Boiling Ration (DNBR)
State the setpoint, actuation, and instrument for the following:
Hi Presssurizer Pressure
State the setpoint, actuation, and instrument for the following:
Low Pressurizer Pressure
State the setpoint, actuation, and instrument for the following:
Low Steam Generator Pressure
State the setpoint, actuation, and instrument for the following:
Low Steam Generator Water Level
State the setpoint, actuation, and instrument for the following:
Hi Steam Generator Water Level
State the setpoint, actuation, and instrument for the following:
High Containment Pressure
State the setpoint, actuation, and instrument for the following:
High-High Containment Pressure
State the setpoint, actuation, and instrument for the following:
Low Reactor Coolant Flow
State the setpoint, actuation, and instrument for the following:
Low Refueling Water Level
State the setpoint, actuation, and instrument for the following:
Supplementary Protection System
High-High Pressurizer Pressure
2409 psia
Reactor Trip
PT-199 A, B, C, & D, four additional narrow range (1500 - 2500 psia)
How does PPS respond to a loss of 1 logic matrix relay?
1 RTSG opens
How does PPS respond to a loss of PNB?
2 RTSG breakers open
Loss of PN:
Loss of power to one leg of 3 matrices.
Loss of power (1/2) to one leg of each ARC
No auto actuations
How does PPS respond to a loss of PKC?
1 RTSG breaker opens
RTSG (Reactor trip breakers / RTBs / TCBs)
* UV relay / Shunt trip coils actuate concurrently from auto or manual signal.
* Separate manual trip buttons for each RTB on B05. (A&C or B&D only will NOT trip the reactor)
* Trip path status indications (1-3 and 2-4 lights) (White lights on PPS and ROM C/D)
* Breaker indication on PPS cabinets.
* Control power: 125Vdc PK (RTB1-PKA / RTB2-PKB / RTB3-PKC / RTB4-PKD)
Are PPS setpoints more or less conservative than Tech Spec limits?
more conservative i.e. you will trip before exceeding the Tech Spec limit
How does placing a parameter in bypass affect PPS?
Trip/actuation logic becomes 2/3
RPS Trip Channel bypass interlock
* Electrical interlock prevents bypassing more than one trip channel (i.e. two low PZR pressure trip bistables).
* If second channel is bypassed, only the highest priority channel will be bypassed. (A highest, D lowest)
What are the logic matrix power supplies?
How far does the Pressurizer Pressure variable setpoint lower when the “LO PZR PRESS SETPOINT RESET” button is pushed?
Low PZR pressure variable setpoint (Trip, SIAS/CIAS)
* Setpoint Reset Push-button on ROMs
* ↓ setpoints 400 psia below current PPZR per PB push
* 100 psia is the lowest setpoint possible
* 10 second TD between PB adjustments
* Setpoint ↑ if PPZR ↑ (lags by 400 psia) until 1837 psia.
How far does the Steam Generator Pressure variable setpoint lower when the “LO SG PRESS SETPOINT RESET” button is pushed?
Lo SG Pressure variable setpoint (Trip, MSIS)
* Setpoint Reset Push-button on ROMs
* ↓ setpoints 200 psia below existing SG Pressure
* 10 second TD between PB adjustments
* Setpoint ↑ if PSG ↑ (lags by 200 psia)
How would an RCP sheared shaft be diagnosed?
Rx trip on Low RCS Flow
RCP sheared shaft protection. (not seen by CPCs)
Limits fuel failure and maintains 10CFR100 limits.
What BOP-ESFAS actuation is not initiated on trend?
RAS
Recirculation Actuation Signal