In accordance with the NEC what is required for emergency and standby electrical systems?
Kept completely separated from other electrical systems
Which of the following must comply with electrical safety standards and codes?
Cost
Manpower
Design
Design
Generators are not permitted to be closer than how many feet form the load?
25 feet (7.6 meters)
“Ratio of average to peak power” best describes which factor?
Annual load
Historically, all general purpose lighting power used in overseas United States bases in what voltage?
120
AC motors above 5 horsepower operate satisfactorily in what voltage systems?
208 or 240
The combination of power and light circuits will be accomplished by the use of which of the following voltage systems?
208 to 240
Which of the following is not a unit of measurement associated with electrical loads?
Inductance
Kilowatts
Amperes
Kilovoltamperes
Inductance
The ratio between the actual maximum demand and the connected load is called what?
Demand factor
Which NEC article provides the requirements for determine demand factors?
Article 220
What is the first step when deleting a suitable site for a generator?
Study plot plan of area
If a level dry area can not be found, what should be done?
Place generator on planks or logs for suitable base foundation
If exhaust piping installation required loops in the system, what must be done?
Install drain cock at lowest point of the system
Exhaust piping insulation located inside A structure must be capable to withstand what maximum amount of temperature?
1500 F
What is the minimum AWG size utilized with the ground terminal wire?
6
What is the primary reason for the voltage changeover board?
Permits reconnection of generators phase windings
What is the output of the voltage changeover board of connected in series?
240/416
What is the prefers material used for ground in an underground metallic water piping systems?
A metal driven rod
What is the minimum diameter of a ground rod if manufactured out of piping?
3/4 inch
What is the minimum depth that a ground rod must be driven into the ground?
8
The ground lead utilized with the ground rod is manufactured out of what type of material?
Copper
The resistance of the soil used to implant a ground rod is dependent upon which of the following factors?
Chemical composition of soil
Depth of ground rod
Moisture content
Acidity of soil
Moisture content
What is one of the best means of reducing the resistance to ground?
Use of additional rods
Load cables are connected in which order? ;
L0, L3, L2, and L1