Pre-course ILT CV Flashcards
(32 cards)
When does the LD relief to the PRT lift?
600 psig
When does the LD relief to the VCT lift?
255 psig
What is the normal flow rate through the LD system and how is it divided amongst the 8149 valves?
120 gpm total
The 45 gpm valve is open and one 75 gpm valve is open
What will cause CV129 to divert away from the LD Demins?
Upstream temperature >= 133 degF
What are the five general services provided to RCS by CVCS?
C-REPS
Chemistry
RCS filling and draining
ECCS high head
Pressurizer level control
Seal water for RCPs
What are the interlocks and coincidences associated with CV mini flow valves 8114 and 8116?
Auto-close on SI 2/4 <1448 psig
Auto open on SI 2/4 >1643 psig
Reset by resetting SI and pressing the reset buttons above each valve
What are the interlocks and setpoints associated with valves 8110 and 8111?
Auto close on SI with 2/4 Lo-2 RWST level 46.7%
Reset by resetting SI and SI recirc pump
What is the normal flow rate of mini flow for CV pump recirc?
60 gpm per pump
What is the normal flow rate through the Charging portion of CV?
100 gpm with one pump running
What is the normal flow rate for Seal Return?
12 gpm
What is the normal flow rate for Seal Injection?
8 gpm per seal
What is the interlock associated with LD isolation valves 459 and 460?
Auto close on PZR level <17%
LD Orifice isolation valves 8149s must be closed in order to Open or Close
What is the interlock associated with orifice isolation valves 8149 A/B/C?
Auto close on PZR level 17%
Phase A isolation
CV459 or CV460 close
What is the interlock associated with Regen HX isolation valves 8389A/B?
Auto close if 8324 closes
What is the interlock associated with Regen HX isolation valves 8389A/B?
Auto close if 8324 closes
How is water hammer prevented in the Letdown system in the event of a low pressurizer level <17%?
CV459 and CV460 have bleed vent valve in vent line to ensure they close at a slower rate than orifice valves
What is the design flow rate of the CV pumps?
150 gpm at 2500 psig
What is the runout flow rate of the CV pumps?
550 gpm at 600 psig
What is the shutoff head of the CV pumps?
2600 psig
What happens if either VCT LT 112 or 185 reach 95%?
Hi 2 alarm will cause CV-112A to full divert to HUT
What happens if LT-112 reaches 73%?
CV-112A will begin to modulate to the HUT
What happens if either LT 112 or 185 reach 70%?
A Boron Dilution Alert Alarm will occur but it can be bypassed in Modes 1 and 2
What happens if LT 112 reaches 55%?
Auto make up turns off
What happens if LT-112 reaches 37%?
Auto make up on, low level alarm