Pre-Test Review (No RQ-C-KNOW) Flashcards
(186 cards)
What are the safety related functions of the Reactor Protection System
- Keep fuel within DNBR
- Limit RCS Pressure w/in design
What are the non-safety related functions of the Reactor Protection System
- Initiate Turbine trip from a Reactor Trip
- Status and Alarm Conditions
What is the function of OTDT & what are the inputs
- Protects from DNB
- Inputs from dT, Tave, AFD, and Pressurizer Pressure
What is the function of OPDT & what are the inputs
- Protects from kW/ft
- Inputs from dT and Tave
What are the Safety Limits
- WRB-1 DNBR >= 1.17
- W-3 BNDR >= 1.30
- Centerline Fuel Temperature < 5080 deg F (decreasing by 58 deg F per 10K MWD/MTU)
- RCS Pressure < 2735 psig
Loss of 4kV Bus Voltage MDAFP start signal:
- Setpoint
- Coincidence
- Interlock
- 94 (93) V
- 2/3 on EITHER T11A/T11D bus
- None
Loss of 4kV Bus Voltage MDAFP Valve repositioning signal:
- Setpoint
- Coincidence
- Interlock
- 94 (93) V
- 2/3 on BOTH T busses in the same train
- None
AMSAC MDAFP start signal:
- Setpoint
- Coincidence
- Interlock
- Feedwater Flow <25%
- 3/4 flow channels
- C20
Low Low Steam Generator Water Level MDAFP start signal:
- Setpoint
- Coincidence
- Interlock
- 5 (22) % Level
- 2/3 level channels on 1 Steam Generator
- None
Loss of Both Main Feedpumps MDAFP start signal:
- Setpoint
- Coincidence
- Interlock
- Feedpump Turbine Stop Valves Closed
- 2/2 limit switches madeup (1 from each MFP)
- Only Available w/ switch in AUTO
RCP Bus Undervoltage TDAFP start signal:
- Setpoint
- Coincidence
- Interlock
- 88 V
- 1/2 on 2 RCP busses
- On time delay
SG Water Level Low Low TDAFP start signal:
- Setpoint
- Coincidence
- Interlock
- 5 (22) % Level
- 2/3 level channels on 2 Steam Generators)
- None
AMSAC TDAFP start signal:
- Setpoint
- Coincidence
- Interlock
- Feedwater Flow <25%
- 3/4 flow channels
- C20
Loss of Voltage Load Shed signal:
- Setpoint
- Coincidence
- Interlock
- 94 (93) V
- 2/3 on ANY T bus
- 2 sec Delay
Degraded Bus Voltage signal:
- Setpoint
- Coincidence
- Interlock
- 113 V
- 2/3 on EITHER T11A/T11D
- 2 min Delay
RWST Sequence signal:
- Setpoint
- Coincidence
- Interlock
- VCT Level < 2.5%
- 2/2 Level Channels (QLC-451/2)
- Either IMO-910/911 full open before QMO-451/452 closes
Which Pressurizer Pressure Channels are used for SI
- Channels 1-3
Which Containment Pressure Channels are used for SI
- Channels 2-4
Which Containment Pressure Channels are used for CTS
- Channels 1-4
What is the input into Pressurizer Level Program Control
- Auctioneered high Tave
How many gallons per % Level in the Pressurizer
- 75 gallons per % level
What happens at 17% Pressurizer Level and lowering
- All heaters are de-energized AND Letdown Orifice valves close to protect heaters
Why is NLI-151 (Pressurizer Level Cold Cal) used during cooldown
- Because actual level is lower than indicated on the hot cal channels and doesn’t provide heater protection
What instrument inputs to LTOP Protection for NRV-152
- NPS-122 (Loop 1 WR)
- Even, Even, Odd