Quiz Flashcards

(61 cards)

1
Q

Boiler fittings are components directly attach to the boiler

A

True

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Saftey valves on steam boilers are desugn to open slowly

A

False

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

The sefety valve should chatter to prevent damage to the disk

A

False

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Safety valves are tested only by performing a try lever test

A

False

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

A safety valve try lever test is performed with the boiler at 15 psi or higher

A

False

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

The steam pressure gauge must be connected to the higher part of the steam side of the boiler

A

True

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

A siphon is connected between the boiler and the steam pressure gauge to prevent water from entering the bourdom tube

A

False

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

A slow gauge reads less pressure than is actually in the boiler

A

True

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Live steam allowed to enter the bourdom tube of a steam pressure gauge will damage the gauge

A

True

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

The water column should be blown down once a shift

A

True

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

The water column is used to indicate the water level in the blowdown tank

A

False

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

With the boiler in ita NOWL the gauge glass is aproximately half full

A

True

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

The purpose of the water column is to slow down the turbulance of the boiler

A

True

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

In low pressure steam boilers, two methods of determining water level are try cocks and gauge glasses

A

True

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

Gauge glasses are calibrated in pounds per square inch

A

False

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

With the water at the NOWL, steam is discharge from the bottom try cock when it opened

A

False

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
17
Q

With the water at the NOWL, the middle try cock discharges a mixture of water and steam when it opened

A

True

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
18
Q

With water at the NOWL, water is dischage from the top try cock when opened

A

False

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
19
Q

If the top line of the gauge glass is closed or clogged, the glass will fill with water

A

True

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
20
Q

If the bottom line to the gauge glass is close or clogged, the glass will be empty

A

False

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
21
Q

To ensure the lines to the gauge glass are clear, it is recomended that the gauge glass be blown down at least once a month

A

False

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
22
Q

The bottom blowdown line must be conected to the highest part of the steam side of the boiler

A

False

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
23
Q

A high surface tension on boiler water can lead to foaming

A

True

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
24
Q

Surface impurities are remove from the boiler by using the bottom blowdown valves

A

False

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
25
Boilers equipped with a quick-opening valve and a slow-opening valve must have the quick-opening valve closest to the boiler
True
26
Only watertube boilers have bottom blowdown valves
False
27
A high water level in a boiler can lead to carryover
True
28
When dumping a boiler there should be a maximum steam pressure in the boiler to force water from the boiler
False
29
To correct a high water level condition, the operator must open the bottom blowdown valve
True
30
Bottom blowdown valves are used when dumping the boiler
True
31
A fusible plug is the last warning the operator has of a dangerous low water condition in the boiler
True
32
The core of the fusible plug melts at approximately 450 F
True
33
The boiler vent should be open when filling the boiler with water
True
34
A burner should always start in high fire to ensure enough fuel for ignition
False
35
The_____is the most importan valve on a boiler
Safety valve
36
The MAWP on a low pressure boiler is ____psi
15 psi
37
Total force on a safty valve is equel to _____
Area times pressure
38
The ASME code states that boiler with over _____squere feet of heating surface must have two or more safty valves
500 square feet
39
The area of a safety valve 4" in diameter is_____square inches
12.5664
40
The only valve permitted between the safety valve and the boiler is?
None. No valve is permitted
41
The range of the pressure gauge should be____times the MAWP of the boiler
1 1/2 to 2
42
In some states_____safety valves are permitted on steam boiler
Spring-loaded pop-off
43
The total force on a safety valve 2 1/2" in diameter with a steam pressure of 15 psi is_____
73.63125
44
The steam pressure gauge on the boiler is calibrated to read_____
Pounds per square inch
45
Steam is prevented from entering the bourdon tube of the pressure by a
Siphon
46
A_____pressure gauge can read either vacuum or pressure
Compound
47
Vacuum is pressure_____pressure
Below atmospheric
48
Safety valves are designed to popopen and stay open untel there is_____psi drop in pressure
2 to 4
49
The water column is located at the NOWL of a low pressure steam boiler, so the lowest visible part of the gauge glass is_____above the highest heating surface
One inch
50
Blowback is the_____in the boiler after the safety valve has opened
Drop in pressure
51
Impurities that build up on the surface of the water in the boiler prevents_____from breaking though the surface of the water
Steam
52
To prevent a vacuum from forming when taking the boiler off-line, the____must be open when pressure is still on the boiler
Boiler vent
53
The operating range of the boiler is control by the______
Pressure control
54
The______regulates the high and low fire of the boiler
Modulating pressure control
55
The best time to blow down a boiler to remove sludge and sediment is when the boiler is under a____load
Light
56
According to the ASME code, a try lever test on safety valves should be performed every_____ the boiler is in operation
30 days
57
The capacity of a safety valve is measured by the amount of steam that can be discharged per_____
Hour
58
The safety calve on a low pressure boiler is designed to open when pressure in the boiler exceeds____
The safety valve setting
59
After the total force of the steam has lifted the safety valve off its seat, steam enters the______
Huddling chamber
60
_______causes false water level readings in the gauge glass
Foaming
61
On an additive pressure control,_____pressure plus_____pressure equels_____pressure
Cut-in, differential, cut-out