What are the three common RCS

A
Midpoint RCS
Paralleling Tie RCS
Generation RCS (RCSG)
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Must you disable LOV or time delay on RCS before paralleling or TIE?

A

Yes

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

When should the RCS operate on LOV

A

between 30-35 secs maximum of 35 sec

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

at what AC potential voltage loss will the LOV open the RCS

A

when AC voltage loss is between 30-40 percent of normal operating voltage

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Prior to removing any control panel fuse what must you do?

A

place the RCS in LOCAL NON AUTOMATIC or the RCS may operate

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

when does the automatic circuit recloser operate

A

15 secs and 55 secs

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

what are the two main reasons RCS beyond AR are equipped with LVA (low of voltage automatic) relay to non automatic

A

a. Permanent faults on the source side of the AR would result in an unnecessary automatic operation of the RCS device.
b. Field ARs are typically configured with a 30-second automatic reclose. To avoid subjecting the RCS device to fault current and energy beyond its design, a line section should never be tested unless the RCS device is fully open.