What are the three common RCS
Midpoint RCS Paralleling Tie RCS Generation RCS (RCSG)
Must you disable LOV or time delay on RCS before paralleling or TIE?
Yes
When should the RCS operate on LOV
between 30-35 secs maximum of 35 sec
at what AC potential voltage loss will the LOV open the RCS
when AC voltage loss is between 30-40 percent of normal operating voltage
Prior to removing any control panel fuse what must you do?
place the RCS in LOCAL NON AUTOMATIC or the RCS may operate
when does the automatic circuit recloser operate
15 secs and 55 secs
what are the two main reasons RCS beyond AR are equipped with LVA (low of voltage automatic) relay to non automatic
a. Permanent faults on the source side of the AR would result in an unnecessary automatic operation of the RCS device.
b. Field ARs are typically configured with a 30-second automatic reclose. To avoid subjecting the RCS device to fault current and energy beyond its design, a line section should never be tested unless the RCS device is fully open.