The amount of refrigerant that flows through the orifice plate is determined by ____
A. THE NUMBER OF ECONOMIZER STAGES
B. THE NUMBER OF COMPRESSION STAGES
C. TEMPERATURE OF REFRIGERANT IN THE HIGH SIDE
D. DIFFERENCE IN PRESSURE BETWEEN HIGH AND LOW SIDES
Difference in pressure between high and low sides
Unloaders are used to
INCREASE CAPACITY
STOP FLOW OF REFRIGERANT WITHOUT STOPPING
REDUCE CAPACITY
START FLOW OF REFRIGERANT THROUGH SYSTEM
Reduce capacity
Semi-Hermetic compressors may be better to use than hermetic compressors because hermetic compressors ____
ARE FULLY ENCLOSED AND CANNOT BE SERVICED ON SITE
ARE EASIER TO GET TO
ARE MORE DIFFICULT TO GET TO
ARE MORE EXPENSIVE
Are fully enclosed and cannot be serviced on site
When conducting a routine tour of plant operation a RMO observes a significant increase in superheat temp. For the refrigerating fluid entering a reciprocating compressor. The most likely cause for this condition is ____
SCALE PARTICLES LODGED IN THE TEV VALVE
UNRAVELING OF THE INSULATION PROTECTING THE TEV VALVE THERMAL BULB
BUILD-UP OF NONCONDENSABLES IN THE CONDENSER
OVERCHARGE OF REFRIGERANT
Scale particles lodged in the TEV valve
A room thermostat controls the liquid line solenoid valve in the commercial refrigeration system. The compressor is activated by ____
THE HIGH PRESSURE CUT IN
THE LOW SIDE PRESSURE STAT
THE THERMOSTATIC EXPANSION VALVE
THE THERMOSTAT THAT ACTIVATES THE SOLENOID VALVE
The low side pressure stat
WHILE MONITORING THE OPERATION OF A RECIPROCATING REFRIGERATING UNIT YOU OVERSEE THAT THE CYCLING TIMES ARE NORMAL, COMPRESSOR COMPRESSION AND TEMP ARE THE ONLY READING THAT ARE OUTSIDE THE NORMAL RATE. UNDER THESE CONDITIONS SERVICE REQUIREMENTS WOULD INDICATE INSPECTING FOR
FAULTY MACHINE CONTROL
PROPER REFRIGERATION CHARGE
FAULTY COMPRESSOR VALVES
POOR CONDENSER OPERATION / DIRTY TUBES
Faulty compressor valves
Which of the following ASHRAE safety groups is the most dangerous
A1
A2
B2
B3
B3
You are an RMO assigned to a facility where a refrigerant has been recently changed from a flammable refrigerant to R-22, at the moment you are planning to braze metal. On such making a repair in the machinery room, under these circumstances you ____
MUST ENSURE THE FLAME IS ENCLOSED AND VENTED TO OPEN AIR
MAY MAKE REPAIRS AT LEAST 25 FEET FROM THE REFRIGERANT UNIT
MAY MAKE REPAIRS WITHOUT ANY RESTRICTIONS IF THE REFRIGERATING UNIT IS SHUT DOWN
MAY NOT MAKE REPAIR UNDER ANY CIRCUMSTANCES
Must ensure the flame is enclosed and vented to open air
An operator has been assigned to run a centrifugal compressor. Of the following actions a capacity control is most likely to achieve through _____
BYPASS DISCHARGE GAS
ADJUSTMENT OF THE IMPELLER INLET GUIDE PRE-ROTATION VANES
CONDENSER PRESSURE VARIATION
ADDING RE-EXPANSION VOLUME
Adjustment of the impeller inlet guide pre-rotation vanes
An RMO needs to vary the flow of refrigerant in the system. A continuous variation in the flow of the system does not include the ____
SOLENOID VALVE
HIGH SIDE FLOAT
THERMAL EXPANSION VALVE
CAPILLARY TUBE
Solenoid valve
An operator has been assigned to a large reciprocating machine without unloaders of the following, safety proper procedure for starting the machine is ____
FILTER SUCTION AND DISCHARGE VALVES
SUCTION VALVE AND DISCHARGE BYPASS BOTH OPEN
SUCTION BYPASS AND DISCHARGE VALVE BOTH OPEN
DISCHARGE BYPASS AND SUCTION VALVE BOTH CLOSED
Suction valve and discharge bypass both open
An operator has been assigned to run a reciprocating compressor. The following action capacity control would most likely be achieved through ____
OPENING THE SUCTION VALVES WITH SOME FORM OF CONTROL
CONTROLLING THE DISCHARGE PRESSURE
CHANGING THE STROKE AND ADDING RE-EXPANSION VOLUME
RETURNING THE DISCHARGE GAS TO SUCTION
Opening the suction valve with some form of control
If a centrifugal compressor is being used in a refrigerations system, and is affected by the condenser, the condenser may be improved by ____
INCREASING THE AMOUNT OF SUPERHEAT
INCREASING THE AMOUNT OF SUB-COOLING
DECREASE THE AMOUNT OF SUPERHEAT
DECREASE THE AMOUNT OF SUB-COOLING
Increasing the amount of subcooling
An operator is using a sling psychrometer to measure dry and wet bulb temp on a roof of a building where the cooling tower is located. If during the day the temp remains constant, and wet bulb drops by 5F, and all other conditions remain unchanged, the operator should see ____
HIGH COOLING WATER BEING RETURNED
RISE IN CONDENSER HEAD PRESSURE
LOWER COOLING WATER TEMPERATURE RETURN
NO NOTICEABLE EFFECT OF THE COOLING TOWER TEMP BEING RETURNED
Lower cooling water temperature return
Upon being assigned to a facility during inspection of the facility, you find there has been failure to maintain water treatment. Inspecting the condenser water the first evidence should be ____
DECREASE IN SUPER HEAT TEMP ENTERING COMPRESSOR
AN INCREASE IN COMPRESSOR HEAD PRESSURE
AN INCREASE IN THE FLOW RATE OF NONCONDENSABLES
CONDENSER TO METERING DEVICE FROZEN
An increase in compressor head pressure
What is the purpose of the recovery tank when operating a refrigerant machine?
TO COOL THE REFRIGERANT
TO STORE EXCESS REFRIGERANT
TO FILTER IMPURITIES FROM THE REFRIGERANT
TO INCREASE COMPRESSOR EFFICIENCY
To store excess refrigerant
An RMO would expect a relief valve to start functioning (for the section of refrigerant one system being protected) at a pressure most closest to ____
5% OVER DESIGN PRESSURE
THE DESIGN PRESSURE
RECOMMENDED OPERATING PRESSURE FOR NORMAL COOLING CONDITIONS
20% BELOW DESIGN PRESSURE
The design pressure
When charging a system with liquid refrigerant with a set of manifold gauges, what position are the valves on the manifold?
HIGH AND LOW VALVES BACKSEATED
HIGH AND LOW VALVES FRONTSEATED
HIGH SIDE BACKSEATED, LOW SIDE FRONTSEATED
HIGH SIDE FRONTSEATED, LOW SIDE BACKSEATED
High side backseated, low side front seated
On the liquid line, which is the correct order of placement of the accessories?
SOLENOID VALVE, SIGHT-GLASS, AND DRIER
DRIER, SIGHT-GLASS, AND SOLENOID VALVE
DRIER, SOLENOID VALVE, AND SIGHT-GLASS
NONE OF THE ABOVE
Drier, solenoid valve, and sightglass
During a particular round an operator notices that the suction line and part of the compressor are frosted, the most likely cause of this condition is ____
NOT ENOUGH REFRIGERANT IN SYSTEM
EXPANSION VALVE OPEN TOO WIDE
THE COMPRESSOR IS RUNNING CONTINUALLY
COMPRESSOR VALVES ARE LEAKING
Expansion valve open too wide
TXV power heads are color coded to match refrigerant charge in the system. What color would the power head have if it was charged with R-22?
ORANGE
GREEN
YELLOW
WHITE
Green
When charging an R-12 reciprocating refrigeration system, an operator would want to use warm water to increase the release rate of refrigerant from the drum. To perform this operation the water temp should not exceed the degree of ____ F
80°F
90°F
110°F
130°F
90F
According to the safety handbook, how much refrigerant can be recovered into a 60 on container
60 LBS
45 LBS
30 LBS
15 LBS
45 lbs
During a walk through the engine room the RMO notices excessive superheat at the evaporator outlet, this would most likely be caused by ____
STARVED EVAPORATOR
LEAK IN SYSTEM
LOW REFRIGERANT CHARGE
ANY OF THE ABOVE
Any of the above