Refrigerant Machine Operator Practice Test #3 Flashcards
(101 cards)
AS AN RMO YOU ENTER A SYSTEM OF A RECIPROCATING REFRIGERATION UNIT. THIS SYSTEM HAS A 150 LB. REFRIGERANT CHARGE, YOU WOULD EXPECT TO FIND STOP VALVES:
ON THE INLET SUPPLY AND DISCHARGE LINE
BEFORE AND AFTER LIQUID BULL’S EYE SIGHT GLASS
ON THE INLET LINE OF THE CONDENSER RECEIVER
ON THE INLET TO EACH COMPRESSOR
ON THE INLET LINE OF THE CONDENSER RECEIVER
HOW DO YOU INCREASE THE PRESSURE OF A CENTRIFUGAL COMPRESSOR?
VARIABLE GUIDE VANES
INCREASE SUB COOL LEVEL
INCREASE SPEED OF MOTOR
ALL OF THE ABOVE
INCREASE SPEED OF MOTOR
THE STRENGTH OF THE STRONG LIQUOR IN AN ABSORPTION SYSTEM DECREASES AS THE:
EXPANSION VALVE IS OPENED
CONDENSER PRESSURE DECREASES
EVAPORATOR LOAD INCREASES
EVAPORATOR LOAD DECREASES
EVAPORATOR LOAD DECREASES
WHAT IS A STEAM JET ON A SURFACE CONDENSER USED FOR?
TO CREATE HIGH PRESSURE TO MAINTAIN HIGH STEAM VELOCITY
TO MAINTAIN STEAM LEVEL INSIDE CONDENSER
TO CREATE PROPER EXHAUST VACUUM
ALL OF THE ABOVE
TO CREATE PROPER EXHAUST VACUUM
AXVs MAINTAIN CONSTANT EVAPORATOR PRESSURE, THEY ALSO:
CLOSE WHEN THE LOAD INCREASES
ARE USED WHEN THERE IS A WIDE RANGE IN LOAD
ARE AFFECTED BY CONDENSER HEAD PRESSURE
REQUIRE OTHER SAFETY DEVICES WHEN BEING USED IN EVAPORATORS THAT CHILL WATER
CLOSE WHEN THE LOAD INCREASES
IF THE UNLOADER FAILS TO OPERATE WHEN NEEDED, WHAT WOULD HAPPEN?
EVAPORATOR PRESSURE WILL REMAIN UNAFFECTED
EVAPORATOR TEMPERATURE WILL GO DOWN
COMPRESSOR WILL SHORT CYCLE
COMPRESSOR WOULD VIBRATE
EVAPORATOR TEMPERATURE WILL GO DOWN
A CENTRIFUGAL PUMP OPERATES AT 92 FEET HEAD. WHAT WOULD BE THE CORRESPONDING PRESSURE IN PSIG BE CLOSEST TO?
180
20
40
90
40
2.31 feet of head to psi
THE ELECTRIC POWER DELIVERED TO A LIQUID LINE SOLENOID VALVE IS MEASURE IN:
OHMS
VOLTAGE
AMPS
WATTS
WATTS
Watts is the unit of power, or rate which energy is transferred or consumed
ON THE HIGH SIDE OF THE SYSTEM, LIQUID STOP VALVES SHOULD BE PLACED:
IN FRONT AND AFTER THE BULL’S EYE SIGHT GLASS
ON THE SUCTION LINE AND DISCHARGE LINE AFTER THE COMPRESSOR
IN FRONT OF AND AFTER THE MUFFLER
ALL OF THE ABOVE
IN FRONT AND AFTER THE BULL’S EYE SIGHT GLASS
A WATER REGULATING VALVE IS CONNECTED TO THE OUTLET OF THE CONDENSER. WHAT IS THIS VALVE DESIGNED TO DO?
MAINTAIN A CONDENSER PRESSURE WITHIN PRESET LIMITS
MAINTAIN A CONSTANT WATER PRESSURE
MAINTAIN A CONSTANT WATER TEMPERATURE
MAINTAIN A CONSTANT CONDENSER PRESSURE
MAINTAIN A CONSTANT CONDENSER PRESSURE
THE AUTOMATIC EXPANSION VALVE (AEV) IS USED INSTEAD OF A TEV. IT MAINTAINS A CONSTANT PRESSURE ON THE EVAPORATOR. ANOTHER FUNCTION IT MAY HAVE IS:
WORKS WELL ON VARIABLE LOADS
ALLOWS REFRIGERANT ON RISE IN PRESSURE
NEEDS TEMPERATURE CONTROL TO PROTECT EVAPORATOR FROM FREEZING UP FROM COLD WATER
ON WATER TYPE EVAPORATOR, FREEZING WILL NOT OCCUR
ON WATER TYPE EVAPORATOR, FREEZING WILL NOT OCCUR
WHEN READING THE HP OF A THREE PHASE MOTOR USING A CLAMP ON AMMETER YOU WOULD:
TAKE MEASUREMENT ON ALL 3 PHASES
TAKE MEASUREMENT ON ONE PHASE ONLY
AMMETER ONLY READS AMPS
TAKE VOLTAGE MEASUREMENT
AMMETER ONLY READS AMPS
IN AN AMMONIA ABSORPTION SYSTEM THE ANALYZER IS LOCATED BETWEEN THE:
GENERATOR AND RECTIFIER
ABSORBER AND EVAPORATOR
RECTIFIER AND CONDENSER
CONDENSER AND RECEIVER
GENERATOR AND RECTIFIER
THE PRESSURE OF WATER GOING THROUGH A SHELL AND TUBE CONDENSER IS PROPORTIONAL TO THE SQUARE OF ITS VELOCITY. IF ITS VELOCITY ORIGINALLY WAS 40 AND IT’S ORIGINAL PRESSURE WAS HALVED, WHAT WOULD THE VELOCITY BE?
40
30
20
10
10
The pressure of water going through a shell and tube condenser is proportional to the square of its velocity. If the original velocity was 40 and the original pressure was halved, the new velocity can be calculated by taking the square root of the original velocity and multiplying it by the square root of the original pressure. In this case, the square root of 40 is 6.32, and the square root of 0.5 (halved pressure) is 0.71. Multiplying these two values together gives a new velocity of approximately 4.49, which is closest to 10. Therefore, the new velocity would be 10.
A SAFETY HEAD IS:
PRESSURE RELIEF VALVE INSIDE THE COMPRESSOR
PRESSURE RELIEF VALVE AT TOP OF THE HEAD
VALVE PLATE BEING HELD DOWN BY A SPRING
HIGH SIDE PRESSURE IN SYSTEM BELOW DESIGN PRESSURE
VALVE PLATE BEING HELD DOWN BY A SPRING
THE TYPE OF REFRIGERANT IN THE FEELER BULB ON A SYSTEM WOULD BE:
SAME AS REFRIGERANT IN SYSTEM
HIGHLY FLAMMABLE / HIGHLY TOXIC
NON FLAMMABLE / NON TOXIC
WOULD BE DIFFERENT TYPE OF REFRIGERANT THAN THE ONE IN THE SYSTEM
NON FLAMMABLE / NON TOXIC
WHAT IS A MAJOR ADVANTAGE OF HAVING A TWO STAGE CENTRIFUGAL COMPRESSOR WITH IMPELLERS BACK TO BACK?
LOWER THRUST LOAD ON BEARINGS
ONE OF THE IMPELLERS CAN BE STOPPED TO ADJUST TO THE LOAD CONDITIONS
YOU CAN USE DIFFERENT EVAPORATORS TO FEED DIFFERENT REFRIGERANTS TO EACH
THEY CAN BE OPERATED AT A LOWER SPEED THAN THE SINGLE STAGE
THEY CAN BE OPERATED AT A LOWER SPEED THAN THE SINGLE STAGE
A MOTOR PULLEY HAS A DIAMETER OF 3” AND RUNS AT 1,400 RPMs. THE FAN PULLEY HAS A DIAMETER OF 5¼”, AT HOW MANY REVOLUTIONS PER MINUTE DOES THE FAN PULLEY REVOLVE?
800 RPMs
1600 RPMs
200 RPMs
1800 RPMs
800 RPMs
The speed of rotation of a pulley is inversely proportional to its diameter. In this case, the motor pulley has a smaller diameter than the fan pulley, so it will rotate faster. The ratio of the diameters is 3/5.25 (3 divided by 5.25), which is approximately 0.571. Since the motor pulley rotates at 1,400 RPMs, the fan pulley will rotate at 0.571 times that speed, which is approximately 800 RPMs.
HOW DO YOU KEEP PROPER WATER LEVEL IN THE HOT WELL?
SLOW TURBINE DOWN
ALTERNATE SPEED OF TURBINE
VERY FLOW OF CONDENSER WATER
WITH OVERBOARD AND RECYCLING VALVE
WITH OVERBOARD AND RECYCLING VALVE
TO PREVENT AGAINST STRUCTURAL COLLAPSE IN PIPE WORK, WHEN INSTALLING BENDED COPPER TUBING:
USE ANNEALED COPPER
USE A SPRING BENDER
USE A LARGE RADIUS
USE BRAZED ELBOWS
USE A LARGE RADIUS
FOR SYSTEMS CONTAINING 50 LBS OF REFRIGERANT, STOP VALVES ARE REQUIRED:
AT INLET OF EACH COMPRESSOR
AT INLET OF LIQUID RECEIVER
BEFORE AND AFTER SIGHT GLASS
NOT REQUIRED
AT INLET OF EACH COMPRESSOR
THE SUCTION SERVICE VALVE ON A RECIPROCATING MACHINE IS FRONT SEATED. YOU HAVE EVACUATED DOWN TO 25” Hg. YOU SHUT VACUUM PUMP OFF AND LOW SIDE PRESSURE RISES IMMEDIATELY. WHAT IS THE CAUSE?
FAULTY SUCTION SERVICE VALVE
FAULTY (SUCTION) COMPRESSOR VALVE
FAULTY DISCHARGE VALVE
FAULTY LIQUID LINE STOP VALVE
FAULTY (SUCTION) COMPRESSOR VALVE
WHAT IS THE MINIMUM HEIGHT LEVEL INSIDE THE MACHINERY ROOM EXHAUST?
LESS THAN 5’
MORE THAN 5’
25’
50’
LESS THAN 5’
AN ELECTRICAL WIRING SCHEMATIC WOULD SHOW:
THE PATH OF ELECTRICITY IN THE CIRCUIT
THE DIAGRAM OF A SWITCH
A POINT TO POINT PICTURE OF ALL THE WIRING IN THE CIRCUIT
ONLY DC WIRING
THE PATH OF ELECTRICITY IN THE CIRCUIT