Set 2 Flashcards
(38 cards)
- 0PGP03-ZF-0018, Fire Protection System Functionality Requirements*
- *
What buildings/structures does this procedure apply to?
Those containing Safe Shutdown Systems
(RCB, EAB, MAB, ECWIS, FHB, DGB, IVC, FPH, TGB, AFWSTs)
- 0PGP03-ZF-0018, Fire Protection System Functionality Requirements*
- *
Definition of Functional ?
A fire protection/detection/barrier system, subsystem, component, or device SHALL be FUNCTIONAL or have FUNCTIONALITY when it is capable of performing its specified design purpose(s), and when all necessary attendant instrumentation, controls, electrical power, cooling or seal water, lubrication, fuel, or other auxiliary equipment that are required for the system, subsystem, component, or device to perform its design purpose(s) are also capable of performing their related design purpose(s).
- 0PGP03-ZF-0018, Fire Protection System Functionality Requirements*
- *
Who is responsible for knowing status of fire protection systems, operating them, and ensuring compensatory measures taken as appropriate?
Shift Manager
- 0PGP03-ZF-0018, Fire Protection System Functionality Requirements*
- *
FIre Protection System Functionality Requirements
The FIRE PROTECTION WATER SUPPLY SYSTEM SHALL be functional at all times with
1) each of the two fire water storage tanks containing a minimum of 300,000 gallons,
and
2) two fire water pumps, each capable of 2500 gpm, taking suction from the two fire water storage tanks and discharging into the fire water underground ring main piping.
A flow path SHALL be maintained from the discharge of the fire water pumps to the isolation valves for each sprinkler/spray system, hydrant, and hose station required by this procedure to be functional:
- 0PGP03-ZF-0018, Fire Protection System Functionality Requirements*
- *
IF only one pump is functional, THEN …
restore one additional pump to functional status or provide an alternate pump within 7 days.
- 0PGP03-ZF-0018, Fire Protection System Functionality Requirements*
- *
IF only one water supply is functional (total available volume greater than or equal to 300,000 gallons but less than 600,000 gallons), THEN …
restore the nonfunctional/impaired water supply to functional status or establish an alternate water supply within 7 days.
- 0PGP03-ZF-0018, Fire Protection System Functionality Requirements*
- *
IF both water sources (tanks, pumps, or a combination) are nonfunctional/impaired, THEN …
restore at least one water supply source or establish an alternate fire water supply within 24 hours.
- 0PGP03-ZF-0018, Fire Protection System Functionality Requirements*
- *
IF the fire water underground ring main or discharge header is nonfunctional/impaired (a flowpath as described in 4.3 is not maintained), THEN …
restore the distribution piping or establish temporary distribution (piping or hose line jumpers) within 24 hours. See Addendum 5 for valves associated with the fire water underground ring main piping.
- 0PGP03-ZF-0018, Fire Protection System Functionality Requirements*
- *
When are the sprinkler or spray systems required to be functional ?
The SPRINKLER or SPRAY SYSTEMS identified in Addendum 2 SHALL be functional whenever the equipment protected by them is required to be operable by Technical Specifications:
w/in 1 hr establish continuous or hourly firewatch depending if area contains redundant safety equipment or not
- 0PGP03-ZF-0018, Fire Protection System Functionality Requirements*
- *
When is the Halon System in the relay room required to be functional ?
The HALON SYSTEM in the Relay Room portion of the Electrical Auxiliaries Building (Fire Area 1, Zone 032) SHALL be functional whenever equipment in the Relay Room is required to be operable by the Technical Specifications. Only one bank of bottles, Main or Reserve, is required for the Halon system to be functional.
- 0PGP03-ZF-0018, Fire Protection System Functionality Requirements*
- *
Which fire hydrants are required to be functional and when?
Yard FIRE HYDRANT #13 SHALL be functional whenever equipment in the Essential Cooling Water Intake Structure is required to be operable by the Technical Specifications,
Yard FIRE HYDRANTS #7 AND #20 SHALL be functional whenever the Auxiliary Feedwater Tanks are required to operable by the Technical Specifications, and
Yard FIRE HYDRANT #10 SHALL be functional whenever equipment in the Fire Pump House is required to be functional per this procedure:
Comp Measure - within 1 hr provide additional 2 1/2” hose to connect to different hydrant
- 0PGP03-ZF-0018, Fire Protection System Functionality Requirements*
- *
Fire rated assemblies (walls, cable tray enclosures, other fire barriers, etc.) and sealing devices are required to be operable …
FIRE RATED ASSEMBLIES separating safe shutdown fire areas or separating portions of redundant systems important to safe shutdown within a fire area, and SEALING DEVICES in fire rated assembly penetrations (fire doors; fire rated elevator doors; fire dampers; and cable, piping, and ventilation duct penetration seals) SHALL be functional whenever equipment protected by the fire rated assemblies is required to be operable by the Technical Specifications. Functional status for fire doors SHALL include self-closing and latching where such features are installed.
Comp measure - hourly firewatch if 1 side of assembly/sealing device impaired: continuous if both
- 0PGP03-ZF-0018, Fire Protection System Functionality Requirements*
- *
Fire Detection System Instrumentation listed in Addendum 4 required when …
The FIRE DETECTION SYSTEM instrumentation identified in Addendum 4 SHALL be functional whenever equipment protected by the fire detection instrumentation is required to be operable by the Technical Specifications:
Comp measure - within 1 hr establish hourly firewatch unless in RCB, then inspect every 8 hrs or monitor RCB temp hourly
- 0PGP03-ZF-0001, Fire Protection Program*
- *
Major purposes of this procedure
Describes establishment of fire watch
Provides mechanism for Fire Marshal to evaluate work activities with transient fire loads
Administrative controls for fire prevention during work activities
- 0PGP03-ZF-0001, Fire Protection Program*
- *
Continuous fire watch
The act of monitoring an area for signs of a fire without leaving the assigned area until relieved by another qualified Fire Watch person, or when the posting is closed. The definition of continuous may also be extended to include entering the assigned area once every 15 minutes, and will be annotated on the Fire Watch log sheet by the Fire Marshal (FM).
- 0PGP03-ZF-0001, Fire Protection Program*
- *
Fire Barrier
those components of construction (walls and floors and their supports including beams, joists, and columns; penetration seals or closures; fire doors and fire dampers) that are rated by approved laboratories in hours of resistance to fire or are described in the FHAR or UFSAR and approved by the Nuclear Regulatory Commission (NRC).
- 0PGP03-ZF-0001, Fire Protection Program*
- *
Fire Watch
The action of monitoring for a fire in an assigned area in which fire detection or suppression capability is impaired, fire barriers are breached, or work is being performed which could increase the likelihood or consequences of fire. The monitoring may be performed hourly or continuously.
- 0PGP03-ZF-0001, Fire Protection Program*
- *
Ignition Source
A process that requires the use of open flame, spark or, heat producing equipment. This includes but is not limited to: cutting and welding, grinding, spark-producing operations, open burns, and the use of melting pots, portable furnaces, and gas fired burners, or heaters.
DOES NOT include hand held heat guns and electric soldering irons.
- 0PGP03-ZF-0001, Fire Protection Program*
- *
Impairment
The degradation of a fire protection system or feature that adversely affects the ability of the system or feature to perform its intended function (RG 1.189). This includes licensing and property protection components. An impairment may be
“anticipated” - planned/scheduled work OR “unanticipated” - a failure discovered during testing or plant rounds/walkdowns.
- 0PGP03-ZF-0001, Fire Protection Program*
- *
Who is responsible for maintaing site fire brigade , protection, and detection systems ?
The Manager, Operations is responsible to maintain a site fire brigade and operate and monitor the site fire protection and detection systems.
- 0PGP03-ZF-0001, Fire Protection Program*
- *
Additional requirements for TIG welding
The applicable Control Room SHALL be contacted when TIG welding inside the Power Block, as this may have an effect on radiation monitors and nuclear instrumentation.
- 0PGP03-ZF-0001, Fire Protection Program*
- *
Required actions for missed/late fire watch
Fire Watch personnel SHALL contact the Shift Manager AND the FM immediately, if a continuous watch is missed or is late OR an hourly round is missed (not performed during the clock hour) for any reason.
Initiate CR
The FM, Shift Manager or designee SHALL sign the last sheet of the Fire Watch Log AND indicate the date and time. This may also be performed per telecon, as required.
- 0PGP03‑ZF‑0011, STPEGS Fire Brigade*
- *
Fire Brigade Staffing
A trained plant fire brigade will be equipped and available at all times.
Each shift fire brigade SHALL consist of five members of the Operations shift crew with specific personnel designated to serve as the Fire Brigade Leader, two members with safe shutdown systems training, and two qualified members.
The Fire Brigade Leader SHALL NOT be the Shift Manager.
- 0PGP03‑ZF‑0011, STPEGS Fire Brigade*
- *
Fire Brigade Duties
The fire brigade SHOULD be utilized to combat fires that affect safety‑related equipment. SM/US discretion is required for any other response.
The Fire Brigade Leader SHALL:
Establish and maintain communications with the control room.
Verify the proper complement of fire brigade members is available on shift and arrange for replacements if necessary.
Request and coordinate the efforts of the fire brigade with offsite fire departments, if outside assistance is requested.
Direct the fire brigade members in firefighting efforts using the fire preplan for the affected area and this procedure for guidance.
Request that the Control Room staff arrange any support personnel or equipment that the Fire Brigade Leader deems appropriate.
Complete Form 6, Fire Report and notify the FM or designee for any fires on site whether or not the Fire Brigade was called out.
The Fire Brigade Leader has ready access to keys for any locked doors.
The Fire Brigade members SHALL:
transport fire suppression and support equipment to the fire scene, suppress fires and perform salvage operations as directed by the Fire Brigade Leader.