SW Flashcards
State SW pump start interlocks
Train TS signal is reset
Associated discharge valve is closed
Associated CT pumps discharge valve is closed
State when SW pump starts on EPS
starts at step 8 (HR8)
5 second time delay if a CBS pump started
State time delay for SW pump discharge valve
opens 15 seconds after pump starts
closes if pumps stops
State what auto starts SW pumps
same train pump breaker trips open
State what trips SW pumps
CS to stop
TA signal
Overcurrent and undervoltage
State starting interlocks for CT pumps
No overloads
Test recirc valve 20-70% open
Discharge valve closed
State Time delay for CT pump discharge valve
10 seconds on TA only
Not in manual
CW ocean pumps must be in PTL for to restart after LOP
State auto close of SW-V-4,5, 74, 76
TA
SI
LOP (SW-V-4,5)
State interlocks for SW-V-75
There are no interlocks for SW-V-75
When does DG Jacket water HX SW outlet valves open
SW-V-16/18 open on EDG Low and High speed relay (125/375 RPM)
State T.S. limit on CT level and Temperature
Level: 42.15’
Temp: 70F
State TA signal signals
Either SW pump per train with its breaker closed for >28 seconds and 2/3 pressure Lo-Lo for >3 seconds - >29.9# - A Train - >28.5# - B Train Manual LOP when already on tower
State what repositions on TA
Running SW pump is tripped and locked out
CT pump starts
Closes SW-V-4/5/74/76
Open PCCW HX SW outlets SW-V-15/17
Opens Heat Loads return CT SW-V-34/23
Closes Primary Heat Loads returns SW-V-20/19