Understanding NEC Article 230 Flashcards

(60 cards)

1
Q

The Code does not cover installations under the exclusive control of an electric utility such as _____.
Answer 1 service drops or service laterals
Answer 2 electric utility office buildings
Answer 3 electric utility warehouses
Answer 4 electric utility garages

A

Answer 1 service drops or service laterals

90.2(D)(5)(a)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

A service drop is defined as the overhead conductors between the serving utility and the _____.
Answer 1 service equipment
Answer 2 service point
Answer 3 grounding electrode conductor
Answer 4 equipment grounding conductor

A

Answer 2 service point

100 Service Drop

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

The underground conductors between the utility electric supply system and the service point are known as the _____.
Answer 1 utility service
Answer 2 service lateral
Answer 3 service drop
Answer 4 main service conductors

A

Answer 2 service lateral

100 Service Lateral

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

The _____ is the point of connection between the facilities of the serving utility and the premises wiring.
Answer 1 service entrance
Answer 2 service point
Answer 3 overcurrent protection
Answer 4 beginning of the wiring system

A

Answer 2 service point

100 Service Point

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Where a feeder supplies continuous loads or any combination of continuous and noncontinuous loads the conductor ampacity shall be no less than the noncontinuous load plus _____ of the continuous load.
Answer 1 80 percent
Answer 2 100 percent
Answer 3 125 percent
Answer 4 150 percent

A

Answer 3 125 percent

215.2(A)(1)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Feeder grounded conductors not connected to an overcurrent device can be sized at _____ of the continuous and noncontinuous load.
Answer 1 80 percent
Answer 2 100 percent
Answer 3 125 percent
Answer 4 150 percent

A

Answer 2 100 percent

215.2(A)(1) Ex 3

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Service conductors and equipment for control and protection of services not over 1000V ac or 1500V dc nominal and their installation requirements are covered in Article _____.
Answer 1 210
Answer 2 220
Answer 3 230
Answer 4 240

A

Answer 3 230

230.1

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

If necessary to meet capacity requirements additional services are permitted for a single building or other structure by _____.
Answer 1 the registered design professional
Answer 2 special permission
Answer 3 the engineer of record
Answer 4 master electricians

A

Answer 2 special permission

230.2(C)(3)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Additional services are permitted for different voltages frequencies or phases or for different uses such as for _____.
Answer 1 gymnasiums
Answer 2 different rate schedules
Answer 3 flea markets
Answer 4 special entertainment events

A

Answer 2 different rate schedules

230.2(D)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Where a building or structure is supplied by more than _____ a permanent plaque or directory shall be installed at each service disconnect location denoting all other services supplying that building or structure and the area served by each.
Answer 1 one service
Answer 2 two services
Answer 3 three services
Answer 4 six services

A

Answer 1 one service

230.2(E)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Service conductors supplying a building or other structure shall not _____ another building or other structure.
Answer 1 be installed on the exterior walls of
Answer 2 pass through the interior of
Answer 3 be installed underneath
Answer 4 span the roof of

A

Answer 2 pass through the interior of

230.3

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Service conductors shall be considered outside of a building or other structure where installed under not less than _____ of concrete beneath a building or other structure.
Answer 1 2 in.
Answer 2 4 in.
Answer 3 5 in.
Answer 4 6 in.

A

Answer 1 2 in.

230.6(1)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Circuit conductors other than service conductors shall not be installed in the same _____ as the service conductors.
Answer 1 raceway or cable
Answer 2 handhole enclosure
Answer 3 underground box
Answer 4 all of these

A

Answer 4 all of these

230.7

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Where a service _____ enters a building or structure it shall be sealed in accordance with 300.5(G) and 300.7(A).
Answer 1 raceway
Answer 2 cable assembly
Answer 3 cable tray
Answer 4 any of these

A

Answer 1 raceway

230.8

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

Service conductors installed as unjacketed multiconductor cable shall have a minimum clearance of _____ from windows that are designed to be opened doors porches balconies ladders stairs fire escapes or similar locations.
Answer 1 3 ft
Answer 2 4 ft
Answer 3 6 ft
Answer 4 10 ft

A

Answer 1 3 ft

230.9(A)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

The vertical clearance of final spans of overhead service conductors above or within _____ measured horizontally of platforms projections or surfaces that will permit personal contact shall be maintained.
Answer 1 3 ft
Answer 2 4 ft
Answer 3 5 ft
Answer 4 6 ft

A

Answer 1 3 ft

230.9(B)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
17
Q

Overhead service conductors shall not be installed beneath openings through which materials may be moved such as openings in farm and commercial buildings and shall not be installed where they obstruct _____ these building openings.
Answer 1 entrance to
Answer 2 egress from
Answer 3 access to
Answer 4 a safe descent from

A

Answer 1 entrance to

230.9(C)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
18
Q

Vegetation such as _____ shall not be used for support of overhead service conductors or service equipment.
Answer 1 shrubs
Answer 2 trees
Answer 3 potted plants
Answer 4 all of these

A

Answer 2 trees

230.10

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
19
Q

Service-drop conductors shall have _____.
Answer 1 sufficient ampacity to carry the load
Answer 2 adequate mechanical strength
Answer 3 sufficient ampacity to carry the load or adequate mechanical strength
Answer 4 sufficient ampacity to carry the load and adequate mechanical strength

A

Answer 4 sufficient ampacity to carry the load and adequate mechanical strength

230.23(A)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
20
Q

The minimum size service-drop conductor permitted is _____ copper or _____ aluminum or copper-clad aluminum.
Answer 1 8 AWG 8 AWG
Answer 2 8 AWG 6 AWG
Answer 3 6 AWG 8 AWG
Answer 4 6 AWG 6 AWG

A

Answer 2 8 AWG 6 AWG

230.23(B)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
21
Q

Overhead service conductors installed over roofs shall have a vertical clearance of not less than _____ above the roof surface.
Answer 1 3 ft
Answer 2 4 ft
Answer 3 5 ft
Answer 4 8 ft 6 in.

A

Answer 4 8 ft 6 in.

230.24(A)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
22
Q

Where the voltage between conductors does not exceed 300 and the roof has a slope of 4 in. in 12 in. or greater a reduction in clearance to _____ over the roof is permitted.
Answer 1 3 ft
Answer 2 4 ft
Answer 3 5 ft
Answer 4 8 ft

A

Answer 1 3 ft

230.24(A) Ex 2

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
23
Q

Where the voltage between conductors does not exceed 300 a reduction in clearance above only the overhanging portion of the roof to not less than _____ shall be permitted if not more than 6 ft of overhead service conductors pass above the roof overhang 4 ft horizontally.
Answer 1 12 in.
Answer 2 18 in.
Answer 3 2 ft
Answer 4 5 ft

A

Answer 2 18 in.

230.24(A) Ex 3

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
24
Q

The requirement to maintain a 3-foot vertical clearance from the edge of a roof does not apply to the final conductor span where the service drop is attached to _____.
Answer 1 a service pole
Answer 2 the side of a building
Answer 3 an antenna
Answer 4 the base of a building

A

Answer 2 the side of a building

230.24(A) Ex 4

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
25
Overhead service conductors shall have a minimum clearance from final grade of _____ above areas or sidewalks accessible only to pedestrians measured from final grade or other accessible surface where the voltage does not exceed 150V to ground. Answer 1 8 ft Answer 2 10 ft Answer 3 12 ft Answer 4 15 ft
Answer 2 10 ft | 230.24(B)(1)
26
Overhead service conductors shall have a minimum vertical clearance of _____ from final grade over residential property and driveways as well as over commercial areas not subject to truck traffic where the voltage does not exceed 300V to ground. Answer 1 10 ft Answer 2 12 ft Answer 3 15 ft Answer 4 18 ft
Answer 2 12 ft | 230.24(B)(2)
27
The minimum clearance for overhead service conductors that pass over public streets alleys roads parking areas subject to truck traffic is _____. Answer 1 10 ft Answer 2 12 ft Answer 3 15 ft Answer 4 18 ft
Answer 4 18 ft | 230.24(B)(4)
28
The minimum point of attachment of overhead service conductors to a building shall not be less than _____ above finished grade. Answer 1 8 ft Answer 2 10 ft Answer 3 12 ft Answer 4 15 ft
Answer 2 10 ft | 230.26
29
Where conduits are used as service masts hubs shall be _____ for use with service-entrance equipment. Answer 1 identified Answer 2 approved Answer 3 of a heavy-duty type Answer 4 listed
Answer 1 identified | 230.28(A)
30
Underground service conductors shall have _____. Answer 1 adequate mechanical strength Answer 2 no splices Answer 3 90°C conductors Answer 4 sufficient ampacity for the loads calculated
Answer 4 sufficient ampacity for the loads calculated | 230.31(A)
31
Underground copper service conductors shall not be smaller than _____. Answer 1 3 AWG Answer 2 4 AWG Answer 3 6 AWG Answer 4 8 AWG
Answer 4 8 AWG | 230.31(B)
32
Underground service conductors that supply power to limited loads of a single branch circuit shall not be smaller than _____. Answer 1 14 AWG copper Answer 2 14 AWG aluminum Answer 3 12 AWG copper Answer 4 12 AWG aluminum
Answer 3 12 AWG copper | 230.31(B) Ex
33
Underground service conductors shall be protected from damage in accordance with _____ including minimum cover requirements. Answer 1 240.6(A) Answer 2 300.5 Answer 3 310.16 Answer 4 430.52
Answer 2 300.5 | 230.32
34
The general requirement for each service drop set of overhead service conductors set of underground service conductors or service lateral is that it shall supply _____ set(s) of service-entrance conductors. Answer 1 only one Answer 2 only two Answer 3 up to six Answer 4 an unlimited number of
Answer 1 only one | 230.40
35
One set of service-entrance conductors connected to the _____ side of the normal service disconnecting means shall be permitted to supply each or several systems covered by 230.82(5) or 230.82(6). Answer 1 supply Answer 2 load Answer 3 high Answer 4 low
Answer 1 supply | 230.40 Ex 5
36
The minimum service-entrance conductor size shall have an ampacity not less than the maximum load to be served after the application of any _____ factors. Answer 1 adjustment Answer 2 correction Answer 3 demand Answer 4 adjustment or correction
Answer 4 adjustment or correction | 230.42(A)(2)
37
Wiring methods permitted for service-entrance conductors include _____. Answer 1 Type IGS cable Answer 2 Type NM cable Answer 3 Type UF cable Answer 4 all of these
Answer 1 Type IGS cable | 230.43(2)
38
Wiring methods permitted for service-entrance conductors include _____. Answer 1 rigid metal conduit Answer 2 electrical metallic tubing Answer 3 PVC conduit Answer 4 all of these
Answer 4 all of these | 230.43(3), (5), and (11)
39
Power distribution blocks installed on service conductors shall be _____ suitable for use on the line side of the service equipment or equivalent. Answer 1 approved as Answer 2 identified as Answer 3 labeled Answer 4 marked
Answer 4 marked | 230.46
40
Underground service-entrance conductors shall be protected against _____ damage. Answer 1 physical Answer 2 extensive Answer 3 severe Answer 4 impact
Answer 1 physical | 230.50(A)
41
Service-entrance cables which are not installed underground where subject to physical damage shall be protected by _____. Answer 1 rigid metal conduit Answer 2 IMC Answer 3 Schedule 80 PVC conduit Answer 4 any of these
Answer 4 any of these | 230.50(B)(1)(1), (2), and (3)
42
Service heads on raceways or service-entrance cables and goosenecks in service-entrance cables shall be located _____ the point of attachment unless impracticable. Answer 1 above Answer 2 below Answer 3 even with Answer 4 any of these
Answer 1 above | 230.54(C)
43
To prevent the entrance of _____ service-entrance conductors shall be connected to the service drop or overhead service conductors either below the level of the service head or below the level of the termination of the service-entrance cable sheath. Answer 1 rain Answer 2 snow Answer 3 ice crystals Answer 4 moisture
Answer 4 moisture | 230.54(F)
44
Service-entrance and overhead service conductors shall be arranged so that _____ will not enter the service raceway or equipment. Answer 1 dust Answer 2 vapor Answer 3 water Answer 4 lightning
Answer 3 water | 230.54(G)
45
On a three-phase 4-wire delta-connected service where the midpoint of one phase winding is grounded the service conductor having the higher phase voltage-to-ground shall be durably and permanently marked by an outer finish that is _____ in color or by other effective means at each termination or junction point. Answer 1 orange Answer 2 red Answer 3 blue Answer 4 any of these
Answer 1 orange | 230.56
46
Barriers shall be placed in service equipment such that no uninsulated ungrounded service busbar or service _____ is exposed to inadvertent contact by persons or maintenance equipment while servicing load terminations with the service disconnect in the open position. Answer 1 phase conductor Answer 2 neutral conductor Answer 3 terminal Answer 4 disconnect
Answer 3 terminal | 230.62(C)
47
The service disconnecting means shall be marked to identify it as being suitable for use as service equipment and shall be _____. Answer 1 weatherproof Answer 2 listed or field evaluated Answer 3 approved Answer 4 moisture resistant
Answer 2 listed or field evaluated | 230.66(A)
48
Where the service equipment for areas of nursing homes and limited care facilities used exclusively as _____ is replaced a surge-protective device (SPD) shall be installed. Answer 1 patient sleeping rooms Answer 2 critical care areas Answer 3 public areas Answer 4 emergency egress
Answer 1 patient sleeping rooms | 230.67(A)(4) and 230.67(D)
49
SPD's required by 230.67(A) shall be an integral part of the service equipment or shall be located _____. Answer 1 immediately adjacent thereto Answer 2 within 3 ft of the service equipment Answer 3 within 10 ft of the service equipment Answer 4 within sight of the service equipment
Answer 1 immediately adjacent thereto | 230.67(B)
50
The surge-protective device (SPD) required for a dwelling unit shall be _____. Answer 1 Type 1 or 2 Answer 2 Type 2 or 3 Answer 3 Type 3 Answer 4 Type 4
Answer 1 Type 1 or 2 | 230.67(C)
51
A service disconnecting means shall be installed at a(an) _____ location. Answer 1 dry Answer 2 readily accessible Answer 3 outdoor Answer 4 indoor
Answer 2 readily accessible | 230.70(A)(1)
52
A service disconnecting means shall not be installed in _____. Answer 1 bathrooms Answer 2 hallways Answer 3 outside Answer 4 electrical rooms
Answer 1 bathrooms | 230.70(A)(2)
53
The additional service disconnecting means for fire pumps emergency systems legally required standby or optional standby services shall be installed remote from the one to six service disconnecting means for normal service to minimize the possibility of _____ interruption of supply. Answer 1 intentional Answer 2 accidental Answer 3 simultaneous Answer 4 prolonged
Answer 3 simultaneous | 230.72(B)
54
For installations consisting of not more than two 2-wire branch circuits the service disconnecting means shall have a rating of not less than _____. Answer 1 15A Answer 2 20A Answer 3 25A Answer 4 30A
Answer 4 30A | 230.79(B)
55
_____ are permitted to be connected to the supply side of the service disconnecting means. Answer 1 Cable limiters Answer 2 Meter sockets Answer 3 Solar PV systems Answer 4 all of these
Answer 4 all of these | 230.82(1), (2), and (6)
56
A meter-mounted transfer switch shall be listed and be capable of transferring _____. Answer 1 the load served Answer 2 125 percent of the continuous load served Answer 3 the maximum short-circuit current Answer 4 all of these
Answer 1 the load served | 230.82(11)
57
For one- and two-family dwelling unit service conductors an emergency disconnecting means shall be installed in a readily accessible _____ location. Answer 1 indoor Answer 2 outdoor Answer 3 indoor or outdoor Answer 4 enclosed
Answer 2 outdoor | 230.85(A)(1)
58
The markings for the required emergency disconnecting means for one- and two-family dwelling services shall _____. Answer 1 be permanently affixed and be sufficiently durable to withstand the environment involved Answer 2 be located on the outside front of the disconnect enclosure with red background and white text Answer 3 have lettering at least 1⁄2 in. high Answer 4 all of these
Answer 4 all of these | 230.85(E)(2)(1), (2), and 110.21(B)(2)
59
Each _____ service conductor shall have overload protection. Answer 1 overhead Answer 2 underground Answer 3 ungrounded Answer 4 individual
Answer 3 ungrounded | 230.90
60
Ground-fault protection of equipment shall be provided for solidly grounded wye electrical services of more than 150V to ground but not exceeding 1000V phase-to-phase for each service disconnecting means rated _____ or more. Answer 1 1000A Answer 2 1500A Answer 3 2000A Answer 4 2500A
Answer 1 1000A | 230.95