Understanding NEC Articles 312 & 314 Flashcards
Article _____ covers the installation and construction specifications of cabinets cutout boxes and meter socket enclosures.
Answer 1: 300
Answer 2: 310
Answer 3: 312
Answer 4: 314
Answer 3: 312
312.1
Cabinets cutout boxes and meter socket enclosures installed in wet locations shall be _____.
Answer 1: waterproof
Answer 2: raintight
Answer 3: weatherproof
Answer 4: watertight
Answer 3: weatherproof
312.2
In walls constructed of wood or other _____ material electrical cabinets shall be flush with the finished surface or project therefrom.
Answer 1: nonconductive
Answer 2: porous
Answer 3: fibrous
Answer 4: combustible
Answer 4: combustible
312.3
Noncombustible surfaces that are broken or incomplete shall be repaired so there will be no gaps or open spaces greater than _____ at the edge of a cabinet or cutout box employing a flush-type cover.
Answer 1: 1⁄32 in.
Answer 2: 1⁄16 in.
Answer 3: 1⁄8 in.
Answer 4: ¼ in.
Answer 3: 1⁄8 in.
312.4
Where cable is used each cable shall be _____ to the cabinet cutout box or meter socket enclosure.
Answer 1: secured
Answer 2: supported
Answer 3: strapped
Answer 4: stapled
Answer 1: secured
312.5(C)
Nonmetallic-sheathed cables can enter the top of surface-mounted cabinets cutout boxes and meter socket enclosures through nonflexible raceways not less than 18 in. and not more than _____ in length if all of the required conditions are met.
Answer 1: 3 ft
Answer 2: 10 ft
Answer 3: 25 ft
Answer 4: 100 ft
Answer 2: 10 ft
312.5(C) Ex 1
The minimum wire-bending space and gutter width at terminals for 4/0 AWG entering an enclosure is _____.
Answer 1: 4 in.
Answer 2: 6 in.
Answer 3: 7 in.
Answer 4: 8 in.
Answer 1: 4 in.
312.6(A)(2) Table
The minimum wire-bending space and gutter width at terminals for 500 kcmil entering an enclosure is _____.
Answer 1: 4 in.
Answer 2: 6 in.
Answer 3: 7 in.
Answer 4: 8 in.
Answer 2: 6 in.
312.6(A)(2) Table
Screws or other fasteners installed in the field that enter wiring spaces of cabinets and cutout boxes shall be as provided by or specified by the manufacturer or _____.
Answer 1: screws shall be machine type
Answer 2: other fasteners shall have blunt ends
Answer 3: screws or other fasteners shall extend no more than 1/4 in. into the enclosure unless the end is protected with an approved means
Answer 4: any of these
Answer 4: any of these
312.10(1), (2), and (3)
Screws or other fasteners installed in the field that enter wiring spaces of cabinets and cutout boxes shall be permitted to extend into the enclosure not more than 7⁄16 in. if located within _____ of an enclosure wall.
Answer 1: 1⁄8 in.
Answer 2: 1/4 in.
Answer 3: 3⁄8 in.
Answer 4: 1/2 in.
Answer 3: 3⁄8 in.
312.10(3) Ex
The installation and use of all boxes and conduit bodies used as outlet device junction or pull boxes depending on their use and handhole enclosures are covered within _____.
Answer 1: Article 110
Answer 2: Article 200
Answer 3: Article 300
Answer 4: Article 314
Answer 4: Article 314
314.1
Nonmetallic boxes can be used with _____.
Answer 1: nonmetallic sheaths
Answer 2: nonmetallic raceways
Answer 3: flexible cords
Answer 4: all of these
Answer 4: all of these
314.3
Where internal _____ means are provided between all entries nonmetallic boxes shall be permitted to be used with metal raceways or metal-armored cables.
Answer 1: grounding
Answer 2: bonding
Answer 3: connecting
Answer 4: splicing
Answer 2: bonding
314.3 Ex 1
Screws or other fasteners installed in the field that enter wiring spaces penetrating a wall of a pull or junction box exceeding 100 cu in. shall extend no more than ¼ in. or more than 7⁄16 in. if located within _____of cabinets and cutout boxes of an adjacent box wall.
Answer 1: 1⁄8 in.
Answer 2: 1/4 in.
Answer 3: 3⁄8 in.
Answer 4: 1/2 in.
Answer 3: 3⁄8 in.
314.5(5)
Screws or other fasteners installed in the field that enter wiring spaces penetrating a wall of a pull or junction box not exceeding 100 cu in. and not covered in 314.23(B)(1) shall be made _____.
Answer 1: within 1⁄8 in. of the box interior
Answer 2: within 1/4 in. of the box interior
Answer 3: within 3⁄8 in. of the box interior
Answer 4: flush with the box interior
Answer 4: flush with the box interior
314.5(6)
In accordance with Article 314 screws or other fasteners installed in the field that enter wiring spaces penetrating the wall of a conduit body shall be made _____.
Answer 1: within 1⁄8 in. of the conduit body
Answer 2: within 1/4 in. of the conduit body
Answer 3: within 3⁄8 in. of the conduit body
Answer 4: flush with the conduit body
Answer 4: flush with the conduit body
314.5(7)
According to the NEC the volume of a 3 in. × 2 in. × 2 in. device box for conductor fill is _____.
Answer 1: 8 cu in.
Answer 2: 10 cu in.
Answer 3: 12 cu in.
Answer 4: 14 cu in.
Answer 2: 10 cu in.
314.16(A) Table
A metal box sized _____ can accommodate nine 12 AWG conductors.
Answer 1: 4 in. × 4 in. × 1¼ in.
Answer 2: 3¾ in. × 2 in. × 3 in.
Answer 3: 3¾ in. × 2 in. x 3½ in.
Answer 4: none of these
Answer 3: 3¾ in. × 2 in. x 3½ in.
314.16(A) Table
The number of 12 AWG THWN-2 conductors permitted in a 4 in. × 4 in.× 1 1/2 in. box is _____.
Answer 1: 7
Answer 2: 9
Answer 3: 11
Answer 4: 13
Answer 2: 9
314.16(A) Table
The total volume occupied by two internal cable clamps six 12 AWG conductors and a single-pole switch is _____.
Answer 1: 2.00 cu in.
Answer 2: 4.50 cu in.
Answer 3: 14.50 cu in.
Answer 4: 20.25 cu in.
Answer 4: 20.25 cu in.
314.16(B) and (B)(1) Table
When counting the number of conductors in a box a conductor running through the box with an unbroken loop or coil not less than twice the minimum length required for free conductors shall be counted as _____ conductor volume(s) in accordance with Table 314.16(B)(1).
Answer 1: one
Answer 2: two
Answer 3: three
Answer 4: four
Answer 2: two
314.16(B)(1)
Where one or more internal cable clamps are present in the box a single volume allowance shall be made based on the _____ present in the box.
Answer 1: largest conductor
Answer 2: smallest conductor
Answer 3: average conductor size
Answer 4: number of devices
Answer 1: largest conductor
314.16(B)(2)
Where a luminaire stud or hickey is present in the box _____ volume allowance shall be made for each type of fitting based on the largest conductor present in the box.
Answer 1: a single
Answer 2: a double
Answer 3: a ¼
Answer 4: no additional
Answer 1: a single
314.16(B)(3)
For the purposes of determining box fill each device or utilization equipment in the box which is wider than a single device box counts as two volume allowances for each _____ required for the mounting.
Answer 1: in.
Answer 2: ft
Answer 3: gang
Answer 4: box
Answer 3: gang
314.16(B)(4)